TRI02SYS 02LINE 10020085 Installation And Operating Manual Download Page 3

 
 

  

TOC1501NUab_0816

 

 

      

                       3/4 

TRI

0

2

SYS

 sarl 

 

8 grande rue le village, 21160 FLAVIGNEROT

 

 
 
 
 
 

  

 
 

  

1.1 Use 

The 1 channel  bidirectional din rail receiver             

10020085

 is used to receive radio signals 

from  switch  transmitters,  sensors  or  in  communication  with  gateway  (see  compatibility  table 
§6.1).  Associated  as  sensor  (see  §5.2)  on  BMS  products,  one  can  get  an  acknowledgment  to 
each  change  or  an  access  to  advanced  functions  such  as  radio  test  function  (see  §6.3).  It  is 
used for switching loads, e.g. incandescent, halogen, fluorescent tubes, halogen lamps with TBT 
ferromagnetic transformer and electronic, power contactor or small motors. 
Before any use, the transmitters must be allocated to a receiver. Each sensor or transmitter can 
control an unlimited number of receivers. 

   

Note:

 

Read the operating manual carefully before initial use. 

    

1.2 Guarantee terms 

This operating manual is an integral part of the device and our guarantee terms. It must always 
be  delivered  to  the  user. We  reserve  the  right  to  modify  the  technical  design  of  these  devices 
without warning.                   products are manufactured and their quality checked by making use 
of  the  latest  technologies  and  taking  into  account  the  applicable  national  and  international 
directives. If nevertheless a fault arises,                undertakes to remedy the default as follows, 
without  prejudicing  the  rights  of  the  end  customer  that  arise  from  the  sales  contract  with  his 
reseller. 
If the event of exercising of a legitimate and regular right,                  , may at its sole discretion, 
rectify  the  device  fault  or  supply  a  fault-free  device.  Any  claim  beyond  this  and  all  claims  for 
consequential damages are excluded. 
A legitimate fault exists if the device cannot be used at the time of delivery to the end customer 
because  of  a  design  or  manufacturing  defect  or  if  its  practical  use  is  severely  limited.  The 
guarantee is  void  in  cases of  natural  wear  and  tear, incorrect  use, incorrect  connection, where 
the device has been repaired or external influence. The guarantee period is 24 months (from the 
date of invoicing). French law applies to the regulation of guarantee rights. 

    

1.3 Recycling of the device 

To recycle the device, conform to the legislation and standards in force in the country of use. 

  

 

  

  

WARNING! Risk of electric shocks! (See UTE C18-510) The device contains live 
internal  components.  Risk of  wounds  or  injuries  if  contact occurs!  All  work  on 
the mains supply network and the device must only be carried out by authorised 
professional technicians. 

• Before carrying out any work, switch-off and isolate the device. 
• Secure the device to prevent it being switched back on. 
• Check the device is in a zero-volts state.   
• Carefully reclose the casing before reconnecting to mains power.

 

  

Observe the following points: 

• The laws, standards and directives in force. 
• Best practice at the time of installation. 
• The device operating manual. 
• An operating manual can only give general instructions. They must be interpreted in the context 
of a specific installation. 
The device is intended solely for use conforming to its purpose. Any repairs or modifications by 
the  user  are  forbidden!  Do  not  use  with  other  devices  the  operation  of  which  could  endanger 
people, animals or property. 

  
    

 
 

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

 

  

 

  
  

Remarque:

 

The signal strength between the transmitter and the receiver decreases as the 

distance increases. Where there is a line of sight connection, the range is approximately 30m in 
corridors and 100 m in large workshops or halls.  
The range can be increased with a                repeater

 

 

 

 

4.1 Safety instructions 

The installation and initial use must only be performed by authorised qualified electricians. The 
electrical  installation  must  be  placed  off-load  before  connection  it  to  the  mains  (230V~/50Hz). 
Conform to the legislation and standards in force in the country of use. 

  

4.2 Installation 

•  This product is designed for indoor use. It is maintenance free. 
•    This  product  is  intended  for  installation  only  on  horizontal  DIN  rail,  in  an  electrical  panel 
(mounted on a vertical wall) with compulsory installation of a plastron which will be connected to 
the ground of the installation if it is metallic. 
•    For  compliance  with  the  standard  reference,  height  of  the  plastron  (compared  to  the  above 
DIN rail) must not exceed 48mm with a minimum thickness of 1mm. 
 

 
•  NEVER  install  the  receiver  in  a  metal  casing  or  in  the  immediate  vicinity  of  large  metallic 
objects. 
•  Installation on the ground or close to the ground is not recommended. Thank you to refer to 
the installation standards of each country. 
•  Although 

NO

 output is internally connected, to the upper power to 400W it is obligatory to link 

externally. 
•  Protect the supply line with a circuit breaker 

2A curve C

 adapted to the installation place. 

•  For the controlled power over 400W, the output contact must be supplied with the same supply 
line as the product, but protected separately with a circuit breaker 

16A curve C 

adapted to the 

installation place.

   

  

 

  

 
 
  
 
 
 
 
 

 

Note 

:  

 

 

 - The two 

L

 terminals are 

  internally connected 
 - The two 

NO

 terminals are 

  internally connected 
 - See section 6.2 for 
  Changeover of state/ 

  operating 

  
 
 
 
 

4.3 Initial use 

•  Connect power to the electrical installation after it has been installed. 
•  Program the transmitter on the receiver (see § 5), or as sensor (see §5.2) on BMS product or 
diagnostic product (see §6.3). 

  

 
 

  

For programming the receiver must be connected to the mains. The programming is conserved 
during a power failure. 
A small insulated screwdriver shall be used on the unit to activate the 

LRN

 or 

CLR 

buttons

.

 

   

5.1 Programming mode or transmitter deletion mode

 

  

          

N.B.!

 A transmitter must not be further away than 5 m from receiver in learn mode. The  

          receiver has a limited range ! 

  

To enter the programming mode, short press (approximately 0,5s) the 

LRN 

button. This mode is 

confirmed by the regular flashing of 

LED

     a)  To  associate  a  transmitter  simply  press  on  one  of  the  switches  or  press  the 

LRN

  button 

(see §6.2). The receiver will acknowledge its recording in memory by maintaining the 

LED

 on for 

4  seconds.  As  soon  as  flashing  LED  starts  again,  another  transmitter  can  be  associated  or 
cleared. 
     b) To clear a transmitter simply press on one of the switches or press the 

LRN

 button of the 

desired  sensor  (see  §6.2).  The  receiver  will  acknowledge  its  clearing  off  the  memory  by 
maintaining the 

LED

 off for 4 seconds. As soon as flashing LED starts again, another transmitter 

can be associated or cleared. 

     c) The transmitter association or deleting, may also be performed through the UTE

1

 protocol 

(Universal TEach-in) of EnOcean. 
To exit programming mode, short press (approximately 0.5s) the 

LRN 

button. The output is 

confirmed by the stopping of regular flashing of the 

LED

  

 

Notes : 

– No transmitter is programmed in the receiver as supplied state. 
–  When  using  BMS  products,  mono  or  multi-channel,  programming  must  be  performed  alone 
and channel by channel: you must exit the programming mode between each channel, by short 
press the 

LRN

 button and within 5 seconds after the start of 

LED 

acquittal. 

– Up to 32 switch, transmitters and sensors can be allocated to each channel. 
–  If  the  memory  is  full,  the  receiver  exits  programming  mode  upon  an  additional  association 
attempt. 
– The transmitters are alternatively programmed or cleared in the event of several activations! 
–  For  transmitter  of  EEP  4BS  type,  a  programming  acknowledgment  frame  (4BS  Teach-in 
variation 3

1

) is always sent. 

–  If no button is pressed, learn mode stop automatically after 30 s. 

  

5.2 Sensor mode

 

The  receiver   

                       

10020085

  once  associated  with  a  BMS  product,  transmits  an 

acknowledgment  to  each  change  of  output  state.  In  addition,  advanced  features  such  as 

querying and change of remote state become available under the profil EEP D2-01-01

1

 : 

     a) Enable on the BMS Product in the programming mode (see the instructions). 
     b) Short press (approximately 0,5s) the 

LRN 

button (product 

10020085

)

 for send association 

frames of UTE

1

 type. These emissions, every 3 seconds are indicated by the regular flashing of 

the 

LED

 until the exit of this mode by a short press (approximately 0.5s) on the 

LRN

 button; the 

output is confirmed by the stopping of regular flashing of the 

LED

     c) The association with this BMS product is validated upon receipt of a positive response of 

UTE

1

 type. This is confirmed, on the receiver, by maintaining the 

LED

 on for 4 seconds. 

  

5.3 Clearing off all the programmed transmitters

 

Press the 

CLR

 button for approximately 2s. Clearing is confirmed by the regular flashing of 

LED

The receiver returns automatically to programming mode. 
To  exit  programming  mode,  short  press  (approximately  0,5s)  the 

LRN 

button.  The  output  is 

confirmed by the stopping of regular flashing of the 

LED

 
 
 
 
 
 
 
 
 
 
 

1

 frame description is described in the 

EnOcean Equipment Profiles

 

EEP2.6 

document available 

on 

www.enocean-alliance.org/en/enocean_standard

  

  

 1. General 

 2. Safety 

 3. Technical characteristics 

Degree of protection 

 

 

IP20 with plastron

 

Range in buildings

 

 

Masonry

 

 

20m, through 3 walls at most

 

Reinforced concrete

 

 

10m, through 1 wall/ceiling at most

 

Plasterboard / wood

 

 

30m, through 5 walls at most

 

Transmission frequency

 

 

868,3 MHZ

 

Power supply

 

 

230V     / 50 Hz

 

Ambient temperature

 

 

from -10°C to +45°C

 

Storage temperature

 

 

from -20°C to +80°C

 

Terminal capacity

 

 

1x1,5

2

 à 2,5

2

 max rigid

 

 

General characteristics

 

 

Output (zero potential)

 

1 contact micro distance (µ) opening 
contact, I

min

=100mA

 

 

max µ16A/3500VA resistive (cos 

φ=1) 

     2300W incandescent/halogen 
     800W inductive (cos φ= 0,4 à 0,6) 

  

       /        1500W/2300W TBT halogen 
          

(Uncompensated) 

1000W fluorescent 

0

2

LINE

 

 5. Programming 

Installation altitude

 

 

2000m max.

 

 4. Installation and initial use 

7mm 

Category receiver

 

 

2

 

 

Installation and operating manual 

 1 channel 16A bidirectional din rail receiver 
  
 Réf. 

10020085 

Ambient humidity

 

 

from 0 to 75%hr (without condensation)

 

EnOcean Equipment Profile 

 

D2-01-01

 

0

2

LINE

 

0

2

LINE

 

TRI

0

2

SYS

 

TRI

0

2

SYS

 

TRI

0

2

SYS

 

  LED display 

  

Output status 

  Programming 

 
 

 

 CLR button 

  

Cancels all 

transmitters 

 

  

LRN button 

  

Learn mode 

Connection drawing for a 
lighting application 

≤ 400W : 

Connection drawing for a resistive 
load application ≤ 3500W : 

Output NO : 
     - load disconnected when off 
 
Gate C : 
     - power contacts 

 
 
 
 
 
 

LN

 : Mains 

230V~ / 50 Hz 


C2A

 


C2A 

 

C16A 

 

Load 

 

EN 

Summary of Contents for 02LINE 10020085

Page 1: ...au lieu d installation Remarque Les deux bornes L sont reliées en interne Les deux bornes NO sont reliées en interne Pour le changement d état repos travail voir 6 2 4 3 Mise en service Mettre l installation électrique sous tension après la pose Programmer voir 5 l émetteur sur le récepteur ou en tant que capteur voir 5 2 sur des produits de GTB ou de diagnostique voir 6 3 Pour la programmation le...

Page 2: ... les touches LRN et CLR simultanément Ce mode est confirmé par le clignotement orange régulier de la DEL c Pour sortir de cette fonction appuyez brièvement environ 0 5s sur la touche LRN Ce mode est confirmé par l arrêt du clignotement régulier de la DEL En l absence d activité de test cette fonction s arrête automatiquement au bout de 30 secondes 1 pour plus de détail voir le document EnOcean Equ...

Page 3: ...ected The two NO terminals are internally connected See section 6 2 for Changeover of state operating 4 3 Initial use Connect power to the electrical installation after it has been installed Program the transmitter on the receiver see 5 or as sensor see 5 2 on BMS product or diagnostic product see 6 3 For programming the receiver must be connected to the mains The programming is conserved during a...

Page 4: ...usly This mode is confirmed by the flashing orange regular of LED c To exit this function short press approximately 0 5s on the LRN button the output is confirmed by the stopping of regular flashing of the LED In the absence of test activity this function stops automatically after 30 seconds 1 frame description is described in the EnOcean Equipment Profiles EEP2 6 document available on www enocean...

Reviews: