3. MAINTENANCE

Under normal circumstances, no maintenance should be required. If clean dry air is not used the orifice can become blocked. To

clean, first turn off supply air, unscrew and remove orifice assembly. The unplug orifice by using a wire that has a smaller 

diameter than 0.015 in. (0.38 mm). Use compressed air to blow out any loose particles inside the orifice assembly. Replace 

orifice assembly back into unit.

4. TROUBLESHOOTING

PROBLEM

CHECK

No output or low output 

Zero adjustment
Supply pressure too low
Clogged orifice

Leakage

Connections

Low or improper span

Zero and Span adjustments
Supply pressure too low
Output leakage

Erratic operation

Electrical input signal
Loose wires or connections
Liquid in air supply

Lead Wire

Bonnet

O-Ring

O-Ring