Trenton THP073HA Installation Instructions Manual Download Page 3

CAPACITY DATA 

High and Medium Temperature Models - Capacity @ 7 F.P.I.

Average Air Throw - ft (m)

 

STANDARD FAN

 AND MOTOR

OPTIONAL

THROW BOOSTER

110

 (33)

150 

(46)

†  Measured in open space. Actual throw may be less in real applications.

Derate capacity by 0.92 and CFM by .85 for Throw Booster Option.
For R449A, use R448A data.

High/Med. Temp. Models 

THP

073HA

086HA

113HA

130HA

154HA

170HA

189HA

233HA

252HA

278HA

Capacity 

BTUH 

(WATTS)

Evap 

Temp.

25°F 

(-4°C)

R407A

R448A

69350

81700

107350

123500

146300

161500

179600

221400

239400

264100

(20313)

(23930)

(31443)

(36173)

(42852)

(47303)

(52590)

(64834)

(70120)

(77355)

R407C

65700

77400

101700

117000

138600

153000

170100

209700

226800

250200

(19244)

(22670)

(29788)

(34269)

(40596)

(44814)

(49822)

(61421)

(66430)

(73283)

R404A

R507

73000

86000

113000

130000

154000

170000

189000

233000

252000

278000

(21382)

(25189)

(33098)

(38077)

(45107)

(49793)

(55358)

(68246)

(73811)

(81426)

R22

69350

81700

107350

123500

146300

161500

179600

221400

239400

264100

(20313)

(23930)

(31443)

(36173)

(42852)

(47303)

(52590)

(64834)

(70120)

(77355)

R134a

65700

77400

101700

117000

138600

153000

170100

209700

226800

250200

(19244)

(22670)

(29788)

(34269)

(40596)

(44814)

(49822)

(61421)

(66430)

(73283)

Air  Flow

 CFM 

(

L/S)

16400

(7740)

15200

(7174)

15600

(7362)

22800

(10760)

24700

(11657)

23500

(11091)

25400

(11987)

35600

(16801)

33800

(15952)

31000

(14630)

Refrigerant ** 

Charge 

R407A

 

 LB. (KG)

22

(10)

30

(14)

44

(20)

44

(20)

55

(25)

66

(30)

97

(44)

108

(49)

130

(59)

173

(78)

Capacities rated using 10°F 

(5.6°C)

 TD & 100°F 

(38°C)

 liquid temperature.

Capacities at other TD within a range of 8 to 15 °F 

(4.4 to 8.3°C)

 are directly proportional to TD, or use formula:  Capacity = Rated capacity ÷ 10 x TD.

For capacities at TD outside of range 8 to 15 °F 

(4.4 to 8.3°C)

, or liquid temperature lower than 75°F 

(24°)

, consult factory.

Capacities for R448A, R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated suction 
temperature and the temperature feeding the evaporator. For dew point ratings, consult factory.

** REFRIGERANT CHARGE CONVERSION FACTORS

R448A

R407C

R404A

R507

R22

R134a

0.96

0.99

0.92

0.93

1.02

1.03

THP

60Hz

23/06/17

T30-THPA-PDI-5

- 3 -

Summary of Contents for THP073HA

Page 1: ...ation 11 Product Support Resources Service Parts Troubleshooting Warranty etc 11 As Built Service Parts List BACK High Profile Evaporator High Medium Temperature Air Defrost Electrical Power 208 230 3...

Page 2: ...gerants Heavy gauge textured aluminum cabinet with galvanized steel hangers support channels and end plates Hinged access panels with removable hinge pins and captive fasteners Hinged drain pan with r...

Page 3: ...313 23930 31443 36173 42852 47303 52590 64834 70120 77355 R134a 65700 77400 101700 117000 138600 153000 170100 209700 226800 250200 19244 22670 29788 34269 40596 44814 49822 61421 66430 73283 Air Flow...

Page 4: ...C AMPACITY A MAX FUSE AMPS 073HA T4A 2 1 4 8 2200 5 4 15 6 2 1740 7 15 086HA T4A 2 1 4 8 2200 5 4 15 6 2 1740 7 15 113HA T4A 2 1 5 5 6 2980 6 3 15 6 2 2560 7 15 130HA T4A 3 1 7 2 3300 7 8 15 9 3 2610...

Page 5: ...WIRING DIAGRAM STANDARD UNITS THP 60Hz 23 06 17 T30 THPA PDI 5 5...

Page 6: ...WIRING DIAGRAM E EC Motor Packaged Assembly THP 60Hz 23 06 17 T30 THPA PDI 5 6...

Page 7: ...WIRING DIAGRAM M EC Motor Motor Only Conventional Shafted Style Motor THP 60Hz 23 06 17 T30 THPA PDI 5 7...

Page 8: ...DIMENSIONAL DATA 2 Fan Models 3 Fan Models Drain connections 1 1 4 FPT THP 60Hz 23 06 17 T30 THPA PDI 5 8...

Page 9: ...3 4 4 4 Distributor Conn OD Sweat Inches mm 1 1 8 29 1 3 8 35 1 3 8 35 1 3 8 35 1 3 8 35 1 5 8 41 1 3 8 35 1 3 8 35 1 3 8 35 1 5 8 41 Suction Conn OD Sweat Inches mm 1 5 8 41 1 5 8 41 2 1 8 54 2 1 8...

Page 10: ...line to prevent condensate from freezing in the drain line Electric heating cable or electric tape by others is used for this purpose The drain line heater should be connected for continuous operatio...

Page 11: ...ers and heater clips 3 Motors are permanently lubricated type and require no further lubrication THP 60Hz System Model Number Date of Start Up Serial Number Service Contractor Refrigerant Phone Electr...

Page 12: ...the manufacturer s policy of continuous product improvement we reserve the right to make changes without notice NATIONAL REFRIGERATION AIR CONDITIONING CANADA CORP 159 Roy Blvd Brantford Ontario Canad...

Reviews: