T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015. 5
Installation Instructions
T/PI
5
Remove lid
6
Remove Connector
7
Insert Cable
8
Wire to Controller
2 InSTallaTIon
(continued)
Either:
use M20 fl exible conduit
Or:
use M16 cable gland
IQ controller
polarity independent
Sensor
24 Vdc
IN
Terminate screen at IQ end only
Analogue input channel
confi gured for current
(
I
)
IQ system TP/I/22/HF/200-600V (Belden 8761) cable
recommended.
Terminal size 0.5 to 2.5 mm
2
(20 to 14 AWG)
Note: if connecting to an IQ22x controller (including /ADL or /
OC), do not connect directly to C (+24V), instead connect to
AUX+ (+24V).
Caution: This unit contains static sensitive devices.
Suitable anti-static precautions should be taken
throughtout the operation to prevent damage to
the units. BS EN100015/1 Basic Specifi cation:
protection of electrostatic sensitive devices.