T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015. 5

Installation Instructions 

T/PI

5

Remove lid

6

Remove Connector

7

Insert Cable

8

Wire to Controller

2 InSTallaTIon 

(continued)

Either:

 use M20 fl exible conduit

Or:

 use M16 cable gland

IQ controller

polarity independent

Sensor

24 Vdc
IN

Terminate screen at IQ end only

Analogue input channel 

confi gured  for  current 

(

I

)

IQ system TP/I/22/HF/200-600V (Belden 8761) cable

recommended.

Terminal size 0.5 to 2.5 mm

2

 (20 to 14 AWG)

Note: if connecting to an IQ22x controller (including /ADL or /

OC), do not connect directly to C (+24V), instead connect to 

AUX+ (+24V).

Caution:  This  unit  contains  static  sensitive  devices. 

Suitable  anti-static  precautions  should  be  taken 

throughtout the operation to prevent damage to 

the units. BS EN100015/1 Basic Specifi cation: 

protection of electrostatic sensitive devices.

Summary of Contents for T/PI

Page 1: ...ttps partners trendcontrols com 1 Dimensions 2 Installation 1 Box Contents T PI Installation Instructions TG200825 Pockets for use as immersion sensor Brass WB150 Stainless Steel WS150 6 mm 0 24 T PI...

Page 2: ...40 C 40 F 50 C 122 F 40 C 40 F 110 C 230 F to to Immersion Immersion Measurement range minimum distance from junctions 10xd 40 10 C 14 F 40 C 104 F 110 10 C 14 F 110 C 230 F 40 40 C 40 F 50 C 122 F 4...

Page 3: ...nto probe Adjust probe length Mount in pocket if pocket has grub screw discard spring and clip clip spring brass brush tighten use 2 mm hexagonal socket key pocket length clip engages in groove probe...

Page 4: ...No 6 3 4 s s self tapping screws integral foam gasket Or Use compression fitting compression fitting duct mounting flange Separate compression fitting Loosen nut Unscrew fitting Or for thinner materi...

Page 5: ...e screen at IQ end only Analogue input channel configured for current I IQ system TP I 22 HF 200 600V Belden 8761 cable recommended Terminal size 0 5 to 2 5 mm2 20 to 14 AWG Note if connecting to an I...

Page 6: ...ector 10 Replace lid 11 Con gure Controller 2 InSTallaTIon continued Note IP67 NEMA6 rating is only achieved if the sensor is correctly installed with cable or conduit connection fully tightened IQ IQ...

Page 7: ...40 T PI 40 C PRT I 14 104 F T PI 40 F PRT I 10 110 T PI 110 C PRT I 14 230 F T PI 110 F PRT I 40 50 T PI 40 C PRT I 40 122 F T PI 40 F Alternatively set scaling mode to 5 characterise and enter scalin...

Page 8: ...tzerland by its Authorized Representative Trend Control Systems Limited Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content he...

Reviews: