AD05-24, -230, AD10-24, -230 

 

Data Sheet 

PRODUCT IDENTIFICATION SYSTEM 

AD 0 5 -2 4

Actuator Damper

05 = 5  Nm

10 = 10 Nm

 24 = 24 V fl ON/OFF

230 = 230 V ON/OFF

 

Fig. 1. Product Identification System 

 

MODELS 

order no. 

supply voltage  end switches 

torque 

AD05-24 -- 

Nm 

AD10-24 

24 Vac/dc 

-- 10 

Nm 

AD05-230 5 

Nm 

AD10-230 

230 Vac 

-- 

10 Nm 

 

BASIC FEATURES 

Dir

Rev

Service/Off

AD05-24

1

3

5

6

4

2

7

 

Fig. 2. Setting units and control elements 

 

Legend for Fig. 2:

 

1) Universal shaft adapter 
2) Mechanical end limits (manually adjustable) 
3) Declutch button 
4) Function selection switch 
5) Removable access cover 
6) Anti-rotation bracket 
7) M20 cable gland 

Contents of Package 

The delivery package includes the actuator and parts 1 
through 7 (see Fig. 2). 
 

RUN MODES 

The function selection switch (see Fig. 3) can be used to 
place the actuator into either of two different modes: 

 Service/Off; 

or 

  the floating/2-position run mode ("Dir" for CCW-closing 

dampers or "Rev" for CW-closing dampers). 

 

Service/Off

Dir

Rev

Service/Off

Dir

Rev

floating/2-position

Service / Off

 

Fig. 3. Function selection switch 

 

Power-Off Behavior 

If power is removed, the shaft adapter remains in position. 
 

Service/Off 

If the function selection switch is set to the "Service/Off" 
position, then all rotary movement is cancelled, and all control 
signals are ignored, thus allowing the actuator to be manually 
operated safely. 
 

Floating/2-Position Run Mode 

 

If the function selection switch has been set to one of the two 
floating/2-position control settings – and if the actuator is 
wired correspondingly (see Fig. 7, Fig. 8, and Fig. 9) – then 
as soon as operating power is applied, the shaft adapter will 
run according to the control signals applied. 
 
Table 1 describes the behavior ("stops," rotates "CCW," or 
rotates "CW") of the AD05-24/AD10-24 in dependence upon 
the control signals (switch "open" or "24 Vac/dc") applied to 
terminals 3 and 4, the function selection switch setting, and 
the manner in which the actuator is wired (either for floating 
mode: see Fig. 7; or for 2-position mode: see Fig. 8). 
 

Table 1. Behavior of AD05-24/AD10-24 

control signal at 

switch setting 

wiring

term. 3 

term. 4 

Dir 

Service/Off

Rev 

open open 

stops stops stops 

open 24Vac/dc

CCW  stops 

CW 

float. 

24Vac/dc

open CW  stops  CCW 

24Vac/dc

open CW  stops  CCW 

2-pos.

24Vac/dc

24Vac/dc

CCW stops  CW 

 
Table 2 describes the behavior ("stops," rotates "CCW," or 
rotates "CW") of the AD05-230/AD10-230 in dependence 
upon the control signals (switch "open" or "230 Vac") applied 
to terminals 1 and 3 and the function

 

selection switch setting; 

only one manner of wiring is permitted (see Fig. 9). 
 

 

AD05-24, -230, AD10-24, -230 Data Sheet TA200853 Issue 1/B 12/04/07

  