AD05-24, -230, AD10-24, -230
Data Sheet
PRODUCT IDENTIFICATION SYSTEM
AD 0 5 -2 4
Actuator Damper
05 = 5 Nm
10 = 10 Nm
24 = 24 V fl ON/OFF
230 = 230 V ON/OFF
Fig. 1. Product Identification System
MODELS
order no.
supply voltage end switches
torque
AD05-24 --
5
Nm
AD10-24
24 Vac/dc
-- 10
Nm
AD05-230 5
Nm
AD10-230
230 Vac
--
10 Nm
BASIC FEATURES
Dir
Rev
Service/Off
AD05-24
1
3
5
6
4
2
7
Fig. 2. Setting units and control elements
Legend for Fig. 2:
1) Universal shaft adapter
2) Mechanical end limits (manually adjustable)
3) Declutch button
4) Function selection switch
5) Removable access cover
6) Anti-rotation bracket
7) M20 cable gland
Contents of Package
The delivery package includes the actuator and parts 1
through 7 (see Fig. 2).
RUN MODES
The function selection switch (see Fig. 3) can be used to
place the actuator into either of two different modes:
•
Service/Off;
or
•
the floating/2-position run mode ("Dir" for CCW-closing
dampers or "Rev" for CW-closing dampers).
Service/Off
Dir
Rev
Service/Off
Dir
Rev
floating/2-position
Service / Off
Fig. 3. Function selection switch
Power-Off Behavior
If power is removed, the shaft adapter remains in position.
Service/Off
If the function selection switch is set to the "Service/Off"
position, then all rotary movement is cancelled, and all control
signals are ignored, thus allowing the actuator to be manually
operated safely.
Floating/2-Position Run Mode
If the function selection switch has been set to one of the two
floating/2-position control settings – and if the actuator is
wired correspondingly (see Fig. 7, Fig. 8, and Fig. 9) – then
as soon as operating power is applied, the shaft adapter will
run according to the control signals applied.
Table 1 describes the behavior ("stops," rotates "CCW," or
rotates "CW") of the AD05-24/AD10-24 in dependence upon
the control signals (switch "open" or "24 Vac/dc") applied to
terminals 3 and 4, the function selection switch setting, and
the manner in which the actuator is wired (either for floating
mode: see Fig. 7; or for 2-position mode: see Fig. 8).
Table 1. Behavior of AD05-24/AD10-24
control signal at
switch setting
wiring
term. 3
term. 4
Dir
Service/Off
Rev
open open
stops stops stops
open 24Vac/dc
CCW stops
CW
float.
24Vac/dc
open CW stops CCW
24Vac/dc
open CW stops CCW
2-pos.
24Vac/dc
24Vac/dc
CCW stops CW
Table 2 describes the behavior ("stops," rotates "CCW," or
rotates "CW") of the AD05-230/AD10-230 in dependence
upon the control signals (switch "open" or "230 Vac") applied
to terminals 1 and 3 and the function
selection switch setting;
only one manner of wiring is permitted (see Fig. 9).
2
AD05-24, -230, AD10-24, -230 Data Sheet TA200853 Issue 1/B 12/04/07
EN0B-0477GE51 R0407