TSP-BCM12
Power Supply Type
TSP power supply
[I
out Nom
]
Jumper position
J6
BCM Module Input Current Limitation
[I
in Limit
]
TSP 140-112
12.00A
1
10.50A
TSP 070-112
6.00A
2
5.20A
3
2.60A
TSP-BCM24
Power Supply Type
TSP power supply
[I
out Nom
]
Jumper position
J6
BCM Module Input Current Limitation
[I
in Limit
]
TSP 360-124
15.00A
1
12.80A
TSP 180-124
7.50A
2
6.40A (factory setting)
TSP 090-124
3.75A
3
3.20A
TSP-BCM24A
Power Supply Type
TSP power supply
[I
out Nom
]
Jumper position
J6
BCM Module Input Current Limitation
[I
in Limit
]
TSP 600-124
25.00A
1
21.40A
2
10.70A (factory setting)
3
5.40A
TSP-BCM48
Power Supply Type
TSP power supply
[I
out Nom
]
Jumper position
J6
BCM Module Input Current Limitation
[I
in Limit
]
TSP 360-148
7.5A
1
6.4 A
TSP 180-148
4.0A
2
3.2 A (factory setting)
TSP 090-148
2.0A
3
1.6 A
TSP-BCM48A
Power Supply Type
TSP power supply
[I
out Nom
]
Jumper position
J6
BCM Module Input Current Limitation
[I
in Limit
]
TSP 600-148
12.5A
1
11.0A
2
6.4A (factory setting)
3
3.2A
Please note: Total maximum input current is shared by load and battery!
4. Fusing
Model
Ratings
Marking
CAUTION:
For continued protection against risk of fire replace with
same type and rating of fuse!
Only authorized and trained
personnel should change this fuse.
TSP-BCM12
12.0 A / 60V
F1
12A
TSP-BCM24 15.0 A / 60V
F1
15A
TSP-BCM24A 30.0 A / 60V
F1
30A
TSP-BCM48 7.5 A / 60V
F1
7.5A
TSP-BCM48A 15.0 A / 60V
F1
15A