IX. TROUBLESHOOTING GUIDE (cont’d)

PROBLEM

POSSIBLE CAUSE/REMEDY

6. Condensing unit runs but short cycles on...

1. Overload Protector - See #4 Above

2. Thermostat - Differential Set Too Close

3. High Pressure “Cut-Out” Due To:

a)  Insufficient Air or Water Supply - Check Air or Water

Supply To Condenser, Correct

b)  Overcharge - Reduce Refrigerant Charge

c)  Air In System - Purge

4. Low Pressure “Cut-Out” Due To:

a)  Liquid Line Solenoid Leaking - Replace e

b)  Compressor Valve Leak - Replace

c)  Undercharge - Fix Leak, Add Refrigerant

d)  Restriction In Expansion Device - Replace Device

7. Condensing unit operates for prolonged 

1. Shortage Of Refrigerant - Fix Leak, Add Charge

periods or continuously.

2. Control Contacts Stuck or Frozen Closed - Clean Contacts or

Replace Control

3. Excessive Heat Load Placed Into Cabinet - Allow Unit

Sufficient Time For Removal Of Latent Heat

4. Prolonged or Too Frequent Door Openings - Plan or

Organize Schedule To Correct Condition

5. Evaporator Coil Iced - Defrost

6. Restriction In Refrigeration System - Determine Locations &

Remove

7. Dirty Condenser - Clean Condenser

8. Filter Dirty - Clean or Replace

9. Unit may need to be defrosted.

8. Start capacitor open or shorted or blown.

1. Relay Contacts Not Opening Properly - Clean Contacts or

Replace Relay If Necessary

2. Prolonged Operation On Start Cycle Due To:

a)  Low Voltage To Unit - Determine Reason & Correct

b)  Improper Relay - Replace

c)  Starting Load Too High - Correct By Using Pump Down

Arrangement If Necessary

3. Excessive Short Cycling - Determine Reason For Short

Cycling (see #5 above) And Correct

4. Improper Capacitor - Determine Correct Size

9. Run capacitor open, shorted or blown.

1. Improper Capacitor - Determine Correct Size & Replace

2. Excessively High Line Voltage (110% of rated max) -

Determine Reason & Correct

10. Relay defective or burned out.

1. Incorrect Relay - Check & Replace

2. Incorrect Mounting Angle - Remount Relay In Correct

Position

3. Line Voltage Too High or Too Low - Determine Reason &

Correct

4. Excessive Short Cycling - Determine Reason (see #5 above)

& Correct

5. Relay Being Influenced By Loose Vibrating Mounting -

Remount Rigidly

6. Incorrect Run Capacitor - Replace With Proper Capacitor

-8-

Summary of Contents for RAC37

Page 1: ...ns you may have please refer to the model and serial number found on the name tag affixed to the unit Should you need service however call us on our toll free number 800 825 8220 between 7 30 am and 4...

Page 2: ...DE REFRIGERANT AMOUNT VOLTS AMPS WATTS HZ CODE UL UL C LISTED 17YO FOR SERVICE 815 459 7500 4401 Blue Mound Road Fort WorthTX 76106 COMMERCIAL REFRIGERATION AND OR FREEZER READING THE SERIAL TAG Seria...

Page 3: ...to avoid scratching the unit when lifting off the 2 III INSTALLATION con t crate Remove the wooden pallet and strapping material and the unit should be rolled off the skid Avoid laying the unit on it...

Page 4: ...V d PRODUCT UNLOADING When unloading product from the Air Curtain refrigerator it is recommend that this be done from the top down Empty trays can be removed or left in the unit after unloading their...

Page 5: ...light will remain illuminated until the cabinet has reached the SET POINT temperature and will go OFF at that time VI e TEMP RECALL This feature displays either the actual internal cabinet air temper...

Page 6: ...hold STANDARD TEMP Arrow UP or COLDER TEMP Arrow DOWN for 5 seconds TO CHANGE TEMPERATURE Press UP Arrow or DOWN Arrow TEMP RECALL Press To Display Either Actual or Set Point Temperature ON DEMAND DEF...

Page 7: ...o 1 pint water ratio VII c CLEANING THE INTERIOR For cleaning stainless steel interiors the use of baking soda as described in section VII b is recommended Use on breaker strips as well as door gasket...

Page 8: ...frosted or has tripped off due to overload Wait 30 minutes Unit will self reset 4 Condensing unit starts but fails to switch 1 Improperly Wired Check Wiring Against Diagram off of start winding 2 Low...

Page 9: ...Restriction In Refrigeration System Determine Locations Remove 7 Dirty Condenser Clean Condenser 8 Filter Dirty Clean or Replace 9 Unit may need to be defrosted 8 Start capacitor open or shorted or bl...

Page 10: ...t 12 Liquid line frosted or sweating 1 Restriction In Dehydrator or Strainer Replace Part 2 Liquid Shut Off king valve Partially Closed Open Valve Fully 13 Noisy condensing unit 1 Loose Parts or Mount...

Page 11: ...10 X WIRING DIAGRAM V 15 0 2 Stage V 15 0...

Page 12: ...OPERATION OR USE AND TRAULSEN NEITHER ASSUMES NOR AUTHORIZES ANYONE ELSE TO ASSUME FOR IT ANY OBLIGATION OR LIABILITY IN CONNECTION WITH THE EQUIPMENT OR ITS SALE OPERATION OR USE OTHER THAN AS STATE...

Page 13: ...minutes and an automatic defrost cycle begins 90 minutes If the unit is operating with door open and the door is closed after End is displayed the open door session will be terminated Cycle controller...

Page 14: ...Fort Worth TX 76106 Phone 800 825 8220 Fax Svce 817 740 6757 Website www traulsen com Quality Refrigeration HOURS OF OPERATION Monday thru Friday 7 30 am 4 30 pm CST EXTENDED WARRANTY SERVICE HOURS Mo...

Reviews: