CPSMC0100-200 / CPSMC0100-205

Installation 

-- Continued

Grounding the Media Converter

The single-slot chassis comes equipped with grounding lugs located on the
back panel.  They require a grounding conductor wire terminated with a 

two-

hole, compression-type, grounding connector

.  The grounding wire -- which

must be a copper conductor -- is not included with the chassis and 

must be

provided by the customer/installer

.   

The electrical conducting path from the single-slot chassis must:

Flow via the grounding lugs to the common bonding network (CBN) for
telecom installations, or to an alternative approved grounding system (if
required) for non-telecom installations.

Be of sufficiently low impedance to conduct fault currents likely to be
imposed on the media converter, and 

Enable proper operation of any over-current protection devices.  

The conductor must be fastened to the grounding lugs with the enclosed anti-
rotation star-washers and lug-nut fasteners.  The applied torque required to the
connector lug-nut fasteners is specified by the connector’s manufacturer.  

To properly ground the single-slot chassis:

1.

Obtain one (1) grounding conductor (12 AWG copper wire gauge or
larger) with a two-hole, compression-type, grounding connector.   

2.

Attach the grounding conductor to the converter by placing the two-hole
connector onto the grounding lugs and fasten with the enclosed lock-
washers / lug-nuts at the proper torque (per the manufacturer’s
specification).

3.

Attach the opposite end of the
grounding conductor to the
common bonding network
(CBN) for telecom, or to earth
ground (if required) for non-
telecom installations.

grounding lugs

earth ground

grounding

connector

and wire

3/4-inch

spacing

Grounding lugs

(6-32, 1/8" diam.)

12 AWG copper wire

(not included)

Star washer (included)

Lug nuts (included)

Two-hole, compression-type

grounding connector

(not included)

[email protected]

-- Click the 

“Transition Now”

link for a live Web chat.

5

Technical Specifications

For use with Transition Networks Model CPSMC0100-20x or equivalent.

NOTE:

The CPSMC0100-20x single-slot chassis is Class B compliant ONLY if

Class B compliant media converters are installed.  Installation of a Class A
compliant media converter reduces the chassis to Class A compliance.

Compliance

EN55022; Class A&B; CE Mark 

Dimensions

3.875 x 5.5 x 1.0 in (98 x 140 x 25 mm) 

Weight 

13 oz. (369 g.) (approximate) 

MTBF 

CPSMC0100

-200:

22,394,241 hours (MIL217F2 V5.0) (MIL-HDBK-217F)
233,811,224 hours (Bellcore7 V5.0)

CPSMC0100

-205:

49,888 hours (MIL217F2 V5.0) (MIL-HDBK-217F)
133,257 hours (Bellcore7 V5.0)

Maximum power delivery capacity:

CPSMC0100

-200:

6 Watts

CPSMC0100

-205:

12 Watts

Power Supply 

CPSMC0100

-200: 

12VDC, 0.8 A (N. America, Europe, Japan, Latin Am.)
12VDC, 1.25 A (UK, Australia, South Africa)

CPSMC0100

-205: 

12VDC, 1.25 A (all regions)

Environment

Tmra*:

0 to 50°C (32 to 122° F )

Storage Temp:   -20 to 85°C
Humidity:

10 to 90%, non condensing 

Altitude:

0 to 10,000 feet

Warranty

Lifetime

*Manufacturer’s rated ambient temperature.  