22-1769-07
5
General
Data
Product Specifications
Model No.
1
2TTB3042A1000C 2TTB3048A1000C 2TTB3060A1000C
Electrical Data V/Ph/Hz
2
200/230/1/60
200/230/1/60 208/230/1/60
Min Cir Ampacity
21
25
33
Max Fuse Size (Amps)
35
40
50
Compressor
RECIP
RECIP
SCROLL
RL Amps - LR Amps
15.4 - 93.5
18.6 - 93.4
25.3 - 146
Outdoor Fan FL Amps
1.4
1.4
1.3
Fan HP
1/6
1/6
1/4
Fan Dia (inches)
27.6
27.6
27.6
Coil
Spine Fin™
Spine Fin™
Spine Fin™
Refrigerant R-22
(Not factory supplied) 6/13-LB/OZ
8/14-LB/OZ
8/11-LB/OZ
Line Size - (in.) O.D. Gas
3
7/8
1-1/8
1-1/8
Line Size - (in.) O.D. Liquid
3
3/8
3/8
3/8
Dimensions H x W x D (Crated)
38.4 x 35.1 x 38.7
46.4 x 35.1 x 38.7
46.4 x 35.1 x 38.7
Weight - Shipping
283
307
280
Weight - Net
249
271
244
Start Components
YES
YES
NO
Sound Enclosure
YES
NO
NO
Compressor Sump Heat
NO
NO
NO
Optional Accessories:
4
Anti-short Cycle Timer
TAYASCT501A
TAYASCT501A
TAYASCT501A
Evaporator Defrost Control A/C
AY28X079
AY28X079
AY28X079
Rubber Isolator Kit
BAYISLT101
BAYISLT101
BAYISLT101
Crank Case Heater Kit
BAYCCHT300
BAYCCHT300
BAYCCHT300
Hard Start Kit Scroll
BAYKSKT263
Extreme Condition Mounting Kit
BAYECMT001
BAYECMT001
BAYECMT001
Refrigerant Lineset
5
TAYREFLN3* TAYREFLN4* TAYREFLN4*
AHRI Standard Capacity Rating Conditions
AHRI STANDARD 210/240 RATING CONDITIONS —
(A) Cooling 80°F DB, 67°F WB air entering indoor coil,
95°F DB air entering outdoor coil.
(B) High Temperature Heating 47°F DB, 43°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(D) Rated indoor airflow for heating is the same as for cooling.
AHRI STANDARD 270 RATING CONDITIONS
— (Noise
rating numbers are determined with the unit in cooling opera
-
tion.) Standard Noise Rating number is at 95°F outdoor air.
Accessory Description and Usage
Anti-Short Cycle Timer
— Solid state timing device that
prevents compressor recycling until 5 minutes have elapsed
after satisfying call or power interruptions. Use in area with
questionable power delivery, commercial applications, long
lineset, etc.
Evaporator Defrost Control
— SPST Temperature actuated
switch that cycles the condenser off as indoor coil reaches
freeze-up conditions. Used for low ambient cooling to 30°F
with TXV.
Rubber Isolators
— 5 large rubber donuts to isolate con
-
densing unit from transmitting energy into mounting frame or
pad. Use on any application where sound transmission needs
to be minimized.
Hard Start kit
— Start capacitor and relay to assist compres
-
sor motor startup. Use in areas with marginal power supply,
on long linesets, low ambient conditions, etc.
Extreme Condition Mount Kit
— Bracket kits to securely
mount condensing unit to a frame or pad without removing
any panels. Use in areas with high winds, or on commercial
roof tops, etc.
Summary of Contents for XB 13
Page 1: ...Split System Cooling Product Performance Data XB 13 2TTB3018 060 1 5 Tons PUB NO 22 1769 07...
Page 7: ...22 1769 07 7 Electrical Data Schematic Diagrams SEE LEGEND 2TTB3018 024 030A...
Page 8: ...8 22 1769 07 Electrical Data 2TTB3036A1000C Schematic Diagrams SEE LEGEND...
Page 9: ...22 1769 07 9 Electrical Data 2TTB3042A1000C 2TTB3048A1000C Schematic Diagrams SEE LEGEND...
Page 10: ...10 22 1769 07 Electrical Data Schematic Diagrams SEE LEGEND 2TTB3060A1000C...