Note: Some options are dependent on the system settings and may not appear during setup.
Installation Options (see configure on front side of page)
0210
Temperature
sensor selection
0
0
Internal for H/C; display can showonly local temperature
and setpoint.
1
Internal for H/C, remote (connected to S1 & S2) for display; display
can show local and remote temperature, and setpoint.
2
Internal for H/C, remote (connected to S1 & S2) for compressor and
auxiliary lockout; display can show local and remote temperature,
and setpoint. (Disabled for conventional systems.)
3
Remote (connected to S1 & S2) for H/C, internal disabled; display
can show remote indoor temperature and setpoint.
0220
Heat pump
compressor
lockout point
0
0
None
15 15° F (–9.5° C)
20 20° F (–6.5° C)
25 25° F (–4.0° C)
30 30° F (–1.0° C)
35 35° F (1.5° C)
40 40° F (4.5° C)
45 45° F (7.0° C)
Only available for heat pump systems with more heat than cool stages and
remote outdoor sensor. A 5 °F (2.5 °C) dead band between options #0220
and #0221 will be enforced automatically.
0221
Heat pump aux
lockout point
0
0
None
40 40° F (4.5° C)
45 45° F (7.0° C)
50 50° F (10.0° C)
55 55° F (13.0° C)
60 60° F (15.5° C)
0230
Temp occupied
duration limit
3
0
0 hours
1
1 hour
2
2 hours
3
3 hours
4
4 hours
For TOV override. When Setting 0 Hours, TOV Function Still Available.
0231
Number of periods
2
2
Two scheduling periods
per day
4
Four scheduling periods
per day
0232
Period occupied/
unoccupied
definitions
4
If option #0231 is set to 2
Day
Night
0
UnOcc
UnOcc
1
UnOcc
Occ
2
UnOcc
UnOcc
3
UnOcc
Occ
4
Occ
UnOcc
5
Occ
Occ
6
Occ
UnOcc
7
Occ
Occ
8
UnOcc
UnOcc
9
UnOcc
Occ
10 UnOcc
UnOcc
11 UnOcc
Occ
12 Occ
UnOcc
13 Occ
Occ
14 Occ
UnOcc
15 Occ
Occ
If option #0231 is set to 4
Morn, Day, Evening, Night
0
UnOcc, UnOcc, UnOcc, Unocc
1
UnOcc, UnOcc, Unocc, Occ
2
UnOcc, UnOcc, Occ, UnOcc
3
UnOcc, Unocc, Occ, Occ
4
UnOcc, Occ, UnOcc, UnOcc
5
UnOcc, Occ, UnOcc, Occ
6
UnOcc, Occ, Occ, UnOcc
7
UnOcc, Occ, Occ, Occ
8
Occ, UnOcc, UnOcc, UnOcc
9
Occ, UnOcc, UnOcc, Occ
10 Occ, UnOcc, Occ, UnOcc
11 Occ, UnOcc, Occ, Occ
12 Occ, Occ, UnOcc, UnOcc
13 Occ, Occ, UnOcc, Occ
14 Occ, Occ, Occ, UnOcc
15 Occ, Occ, Occ, Occ
0233
Scheduling mode
day options
0
0
1 day. Mo-Su all days share the same schedule.
1
5+1+1 days. Mo-Fr share a schedule. Sa and Su each have an
independent schedule.
2
5+2 days. Mo-Fr share a schedule. Sa-Su share a schedule.
3
7 days. Each day has an independent schedule.
0240
Heat temperature
range stops
90
40 - 90
40° F to 90° F
4 - 32
4° C to 32° C
(Only applies to systems with
heat stages)
0241
Cool temperature
range stops
50
50 - 99
40° F to 90° F
10 - 37
4° C to 32° C
(Only applies to systems with cool
stages)
0260
Temperature
display offset
0
–3 –3° F (–1.5° C)
–2 –2° F (–1.0° C)
–1 –1° F (–0.5° C)
0
None
1
1° F (0.5° C)
2
2° F (1.0° C)
3
3° F (1.5° C)
Applies only to control temperature and display temperature for internal
and indoor remote sensor. Does not apply to outdoor temperature for
display.
0270
Extended fan-on
time heat
0
0
Off
90 90 seconds
(Only available when option #0151
is set to 1)
0271
Extended fan-on
time cool
0
0
Off
40 40 seconds
(Only available on systems with
cool stages, see option #0130)
0300
Restore factory
defaults
0
0
No - do not restore
1
Yes - reset all installer options to default except calendar, and system
selection. (Options 0120, 0121, 0122, 0130 do not reset.)
No.
Name
Default Values/Descriptions
No.
Name
Default Values/Descriptions
0100
Temperature
indication/
resolution
0
0
°F, 1 degree resolution
1
°F, 0.5 degree resolution
2
°C, 1 degree resolution
3
°C with 0.5 degree resolution
4
°C with 0.1 degree resolution
0110
Clock format
12
12 12 hour clock
09
09-99 2009-2099
24 24 hour clock
0121
Month
1
1 - 12
0122
Day
1
1 - 31
0125
Daylight savings
2
0
Disabled
1
US (1987), changeover
at 2:00am
2
US (2007), changeover
at 2:00am
3
Europe, changeover at
1:00am
4
Manual, changeover at
2:00am
0126
0127
0128
0129
Spring month
Spring day
Fall month
Fall day
03
08
11
08
01-12
01-31
01-12
01-31
Spring and fall daylight savings
months and days.
(These options are available if
option #0125 is set to 4).
0130
System selection
8
1
1H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)
2
1H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G)
3
1H (Conv) 1st Stage Heat (W), without fan
4
1H (Conv) 1st Stage Heat (W), Fan (G)
5
1C (Conv) 1st Stage Comp (Y), Fan (G)
6
2H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat
(W1), Fan (G)
7
2H/2C (Conv) 1st & 2nd Stage Heat (W,W2), 1st & 2nd Stage
Comp (Y,Y2), Fan (G)
8
2H/1C (Conv) 1st & 2nd Stage Heat (W,W2), 1st Stage Comp (Y), Fan
(G)
9
1H/2C (Conv) 1st Stage Heat (W), 1st & 2nd Stage Comp (Y,Y2), Fan
(G)
10 2H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Fan (G)
11 3H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B),
Auxiliary Heat (W1), Fan (G)
0140
Schedule options
1
0
Non-programmable
1
Programmable
0150
TOD/Economizer
output (terminal A)
0
0
Unused
1
TOD energizes terminal A during occupied period, not during
unoccupied period.
2
Economizer energizes terminal A during a call for cool.
0151
Heat fan operation
0
0
System controls fan
1
Thermostat controls fan
0153
Reversing value O/
B
0
0
O/B terminal energized in
cooling
1
O/B terminal energized in
heating
0160
CPH 1st stage
compressor
3
1-5
Cycles per hour for 1st stage compressor. Only for
systems with cool or heat pump stage. Also changes
2nd stage cool default CPH.
0161
CPH 2nd stage
compressor
3
1-5
Cycles per hour for 2nd stage compressor. Only for
systems with 2 cool or heat pump stages.
0162
CPH 1st stage
conventional heat
5
1-10
Cycles per hour for 1st stage conventional heat. Only for
systems with heat stages. Changes 2nd stage heat
default CPH.
0163
CPH 2nd stage
conventional heat
9
1-10
Cycles per hour for 2nd stage conventional heat. Only for
systems with two conventional heat stages.
0164
CPH for auxiliary
heat
9
1-10
Cycles per hour for auxiliary heat. Only for heat pump
systems with more heat than cool stages.
0165
CPH for emergency
heat
9
1-10
Cycles per hour for emergency heat. Only for heat pump
systems with more heat than cool stages.
0170
Continuous
backlight
0
0
Backlight turns off after 8
seconds.
1
Backlight does not turn off
0180
Changeover
1
0
Manual changeover
0
0
60Hz
1
Automatic changeover
0181
Deadband
3
2
2° F (1° C)
3
3° F (1.5° C)
4
4° F (2.0° C)
5
5° F (2.5° C)
6
6° F (3.0° C)
7
7° F (3.5° C)
8
8° F (4.0° C)
9
9° F (4.5° C)
0182
Minimum comp off
time (for systems
with cool stage)
5
0
Off (no minimum)
1
1 minute
2
2 minutes
3
3 minutes
4
4 minutes
5
5 minutes
1
50Hz
0190
Power supply
frequency
0120
Year
© 2012 Trane. All rights reserved.
X39641161-01B 19 Mar 2012
Supersedes X39641161-01A 03 Dec 2009
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll
Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane
offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and
parts. For more information, visit www.Trane.com.
Tra ne h as a pol icy of con tinu ous pro duct an d prod uct d ata im prove ment an d reserves the rig ht to chang e
d esig n an d sp ecificati ons wi thou t no tice.
We are co mmitted to using environmentally
conscious print practices that reduce waste.