background image

Note: Some options are dependent on the system settings and may not appear during setup.

Installation Options (see configure on front side of page) 

0210

Temperature 

sensor selection

0

0

Internal for H/C; display can showonly local temperature 

and setpoint.

1

Internal for H/C, remote (connected to S1 & S2) for display; display 

can show local and remote temperature, and setpoint.

2

Internal for H/C, remote (connected to S1 & S2) for compressor and 

auxiliary lockout; display can show local and remote temperature, 

and setpoint. (Disabled for conventional systems.)

3

Remote (connected to S1 & S2) for H/C, internal disabled; display 

can show remote indoor temperature and setpoint.

0220

Heat pump 

compressor 

lockout point

0

0

None

15 15° F (–9.5° C)

20 20° F (–6.5° C)

25 25° F (–4.0° C)

30 30° F (–1.0° C)

35 35° F (1.5° C)

40 40° F (4.5° C)

45 45° F (7.0° C)

Only available for heat pump systems with more heat than cool stages and 

remote outdoor sensor. A 5 °F (2.5 °C) dead band between options #0220 

and #0221 will be enforced automatically.

0221

Heat pump aux 

lockout point

0

0

None

40 40° F (4.5° C)

45 45° F (7.0° C)

50 50° F (10.0° C)

55 55° F (13.0° C)

60 60° F (15.5° C)

0230

Temp occupied 

duration limit

3

0

0 hours

1

1 hour

2

2 hours

3

3 hours

4

4 hours

For TOV override. When Setting 0 Hours, TOV Function Still Available.

0231

Number of periods

2

2

Two scheduling periods 

per day

4

Four scheduling periods 

per day

0232

Period occupied/ 

unoccupied 

definitions

4

If option #0231 is set to 2

Day

Night

0

UnOcc

UnOcc

1

UnOcc

Occ

2

UnOcc

UnOcc

3

UnOcc

Occ

4

Occ

UnOcc

5

Occ

Occ

6

Occ

UnOcc

7

Occ

Occ

8

UnOcc

UnOcc

9

UnOcc

Occ

10 UnOcc

UnOcc

11 UnOcc

Occ

12 Occ

UnOcc

13 Occ

Occ

14 Occ

UnOcc

15 Occ

Occ

If option #0231 is set to 4

Morn, Day, Evening, Night

0

UnOcc, UnOcc, UnOcc, Unocc

1

UnOcc, UnOcc, Unocc, Occ

2

UnOcc, UnOcc, Occ, UnOcc

3

UnOcc, Unocc, Occ, Occ

4

UnOcc, Occ, UnOcc, UnOcc

5

UnOcc, Occ, UnOcc, Occ

6

UnOcc, Occ, Occ, UnOcc

7

UnOcc, Occ, Occ, Occ

8

Occ, UnOcc, UnOcc, UnOcc

9

Occ, UnOcc, UnOcc, Occ

10 Occ, UnOcc, Occ, UnOcc

11 Occ, UnOcc, Occ, Occ

12 Occ, Occ, UnOcc, UnOcc

13 Occ, Occ, UnOcc, Occ

14 Occ, Occ, Occ, UnOcc

15 Occ, Occ, Occ, Occ

0233

Scheduling mode 

day options

0

0

1 day. Mo-Su all days share the same schedule.

1

5+1+1 days. Mo-Fr share a schedule. Sa and Su each have an 

independent schedule.

2

5+2 days. Mo-Fr share a schedule. Sa-Su share a schedule.

3

7 days. Each day has an independent schedule.

0240

Heat temperature 

range stops

90

40 - 90

40° F to 90° F

4 - 32

4° C to 32° C

(Only applies to systems with 

heat stages)

0241

Cool temperature 

range stops

50

50 - 99

40° F to 90° F

10 - 37

4° C to 32° C

(Only applies to systems with cool 

stages)

0260

Temperature 

display offset

0

–3 –3° F (–1.5° C)

–2 –2° F (–1.0° C)

–1 –1° F (–0.5° C)

0

None

1

1° F (0.5° C)

2

2° F (1.0° C)

3

3° F (1.5° C)

Applies only to control temperature and display temperature for internal 

and indoor remote sensor. Does not apply to outdoor temperature for 

display.

0270

Extended fan-on 

time heat

0

0

Off

90 90 seconds

(Only available when option #0151 

is set to 1)

0271

Extended fan-on 

time cool

0

0

Off

40 40 seconds

(Only available on systems with 

cool stages, see option #0130)

0300

Restore factory 

defaults

0

0

No - do not restore

1

Yes - reset all installer options to default except calendar, and system 

selection. (Options 0120, 0121, 0122, 0130 do not reset.)

No.

Name

Default Values/Descriptions

No.

Name

Default Values/Descriptions

0100

Temperature 

indication/ 

resolution

0

0

°F, 1 degree resolution

°F, 0.5 degree resolution

2

°C, 1 degree resolution

3

°C with 0.5 degree resolution

4

°C with 0.1 degree resolution

0110

Clock format

12

12 12 hour clock

09

09-99 2009-2099

24 24 hour clock

0121

Month

1

1 - 12

0122 

Day

1

1 - 31

0125

Daylight savings

2

0

Disabled

1

US (1987), changeover 

at 2:00am

2

US (2007), changeover 

at 2:00am

3

Europe, changeover at 

1:00am

4

Manual, changeover at 

2:00am

0126

0127

0128

0129

Spring month

Spring day

Fall month

Fall day

03

08

11

08

01-12 

01-31 

01-12 

01-31 

Spring and fall daylight savings 

months and days. 

(These options are available if 

option #0125 is set to 4).

0130

System selection

8

1

1H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)

2

1H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G)

3

1H (Conv) 1st Stage Heat (W), without fan

4

1H (Conv) 1st Stage Heat (W), Fan (G)

5

1C (Conv) 1st Stage Comp (Y), Fan (G)

6

2H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat 

(W1), Fan (G)

7

2H/2C (Conv) 1st & 2nd Stage Heat (W,W2), 1st & 2nd Stage 

Comp (Y,Y2), Fan (G)

8

2H/1C (Conv) 1st & 2nd Stage Heat (W,W2), 1st Stage Comp (Y), Fan 

(G)

9

1H/2C (Conv) 1st Stage Heat (W), 1st & 2nd Stage Comp (Y,Y2), Fan 

(G)

10 2H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Fan (G)

11 3H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), 

Auxiliary Heat (W1), Fan (G)

0140

Schedule options

1

0

Non-programmable

1

Programmable

0150

TOD/Economizer 

output (terminal A)

0

0

Unused

1

TOD energizes terminal A during occupied period, not during 

unoccupied period.

Economizer energizes terminal A during a call for cool.

0151

Heat fan operation

0

0

System controls fan

Thermostat controls fan

0153

Reversing value O/

B

0

0

O/B terminal energized in 

cooling

1

O/B terminal energized in 

heating

0160

CPH 1st stage 

compressor

3

1-5

Cycles per hour for 1st stage compressor. Only for 

systems with cool or heat pump stage. Also changes 

2nd stage cool default CPH.

0161

CPH 2nd stage 

compressor

3

1-5

Cycles per hour for 2nd stage compressor. Only for

systems with 2 cool or heat pump stages.

0162

CPH 1st stage 

conventional heat

5

1-10

Cycles per hour for 1st stage conventional heat. Only for

systems with heat stages. Changes 2nd stage heat 

default CPH.

0163

CPH 2nd stage 

conventional heat

9

1-10

Cycles per hour for 2nd stage conventional heat. Only for

systems with two conventional heat stages.

0164

CPH for auxiliary 

heat

9

1-10 

Cycles per hour for auxiliary heat. Only for heat pump 

systems with more heat than cool stages.

0165

CPH for emergency 

heat

9

1-10 

Cycles per hour for emergency heat.  Only for heat pump

systems with more heat than cool stages.

0170

Continuous 

backlight

0

0

Backlight turns off after 8 

seconds.

1

Backlight does not turn off

0180

Changeover

1

0

Manual changeover

0

0

60Hz

1

Automatic changeover

0181

Deadband

3

2

2° F (1° C)

3

3° F (1.5° C)

4

4° F (2.0° C)

5

5° F (2.5° C)

6

6° F (3.0° C)

7

7° F (3.5° C)

8

8° F (4.0° C)

9

9° F (4.5° C)

0182

Minimum comp off 

time (for systems 

with cool stage)

5

0

Off (no minimum)

1

1 minute

2

2 minutes

3

3 minutes

4

4 minutes

5

5 minutes

1

50Hz

0190

Power supply 

frequency

0120

Year

© 2012 Trane.  All rights reserved.
X39641161-01B 19 Mar 2012
Supersedes X39641161-01A  03 Dec 2009

Trane optimizes the performance  of homes and buildings around the world. A business of Ingersoll

Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane

offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and

parts.  For more information, visit www.Trane.com.

Tra ne  h as  a  pol icy  of  con tinu ous  pro duct  an d  prod uct  d ata  im prove ment  an d  reserves  the  rig ht  to   chang e

d esig n an d  sp ecificati ons  wi thou t  no tice.

We are co mmitted to using environmentally 
conscious print practices that reduce waste.

Reviews: