BAS-SVX17B-EN
15
Configuration
13
Display zone
temperature
0 = No
1 = Yes
1
If the sensor is in a normal running state or in temporary
occupancy (timed override), the zone temperature
appears.
14
Keypad lockout
0 = Disabled
1 = Enabled
1
If enabled, the keypad can be locked out.
15
Default temporary
override timer setting
1, 2, 3, 4, 5 (hours)
3
Sets the default temporary override time in hours.
16
Zone temperature
calibration
Displays current temperature
reading with any offsets:
• 1 = –9.9ºF (–5.5ºC)
• 100 = 0.0ºF (0.0ºC)
• 199 = 9.9ºF (9.9ºC)
100
(0
offset)
Allows for field calibration in 0.1ºF (0.6ºC) increments of
either the internal sensor on the sensor, or the remote
sensor if used.
Important:
Apply power to the sensor for 60 minutes before
calibrating.
17
Baud rate
0 = 1024 baud
1=1200 baud
1
Set to 0 for 3–25 ton Voyager units built before January 1,
1996, that have the original UCP.
18
Default cooling setpoint
45–98ºF (7.2–36.7ºC)
74
If no setpoint has been programmed or the program is lost,
the value that is set becomes the operation setpoint.
19
Default heating setpoint
43–96ºF (6.1–35.6ºC)
68
If no setpoint has been programmed or the program is lost,
the value that is set becomes the operation setpoint.
20
Minimum cooling
setpoint
45–98ºF (7.2–36.7ºC)
45
Sets the minimum programmable cooling temperature
setpoint.
21
Maximum heating
setpoint
43–96ºF (6.1–35.6ºC))
96
Sets the maximum programmable heating temperature
setpoint.
22
Minimum setpoint
deadband
0 = 2ºF (1ºC)
1 = 4ºF (2ºC)
2 = 5ºF (3ºC)
3 = 7ºF (4ºC)
4 = 8ºF (5ºC)
5 = 10ºF (6ºC)
0
Sets the minimum difference between the heating and
cooling setpoints.
Table 3.
Configuration options for sensors used with
constant-volume (CV)
or
heat pump (HP)
units (continued)
Option
number
Function
Option value
Default Description