BAS-SVX10C-EN
31
Maintenance and Troubleshooting
Table 1.
Resistance measurements for zone temperature and setpoints
Zone or setpoint temperature
Nominal zone temperature
output resistance
Nominal setpoint and heating
setpoint output resistance
**
NA
938
Ω
55°F (12.8°C)
17.47 k
Ω
792
Ω
60°F (15.6°C)
15.3 k
Ω
695
Ω
65°F (18.3°C)
13.5 k
Ω
597
Ω
70°F (21.1°C)
11.9 k
Ω
500
Ω
75°F (23.9°C)
10.5 k
Ω
403
Ω
80°F (26.7°C
9.3 k
Ω
305
Ω
85°F (29.4°C)
8.25 k
Ω
208
Ω
*
NA
49
Ω
Notes:
1. Sensors are calibrated at 70°F (21.1ºC).
2. Single setpoint systems: Varies ±28
Ω
at 70°F
(21.1ºC); varies ±128
Ω
at endpoints of scale 55ºF (12.8ºC) and 85ºF
(29.4ºC). Dual setpoint systems: Cooling setpoint varies ±10
Ω
at 70ºF (21.1ºC); varies at ±110
Ω
at endpoints of
scale. Heating setpoint varies ±20
Ω
at 70ºF (21.1ºC); varies at ±120
Ω
at endpoints of scale.
Table 2.
Resistance measurements for fan and system modes
Fan mode
System mode
Nominal output resistance
Auto or invalid
Emergency heat
35,000
Ω
Auto or invalid
Heat
19,480
Ω
Auto or invalid
Auto
7680
Ω
Auto or invalid
Off
2320
Ω
Auto or invalid
Cool
4870
Ω
On
Emergency heat
43,450
Ω
On
Heat
27,930
Ω
On
Auto
16,130
Ω
On
Off
10,770
Ω
On
Cool
13,320
Ω
High
Invalid (fan control only)
16,130
Ω
Med
Invalid (fan control only)
13,320
Ω
Low
Invalid (fan control only)
10,770
Ω
Auto
Invalid (fan control only)
2320
Ω
Off
Invalid (fan control only)
4870
Ω