![Trane WDS Installation, Operation And Maintenance Manual Download Page 45](http://html1.mh-extra.com/html/trane/wds/wds_installation-operation-and-maintenance-manual_1148940045.webp)
BAS-SVX04C-EN •
Wireless Sensors
45
Maintenance and Troubleshooting
Note: The output circuits are not electrically powered; consequently, resistance can
be measured without risk of damage to the volt-ohm meter.
Table 8. Receiver resistance table for all models
Zone or setpoint
temperature
Nominal zone temperature
output resistance
Nominal setpoint and
heating setpoint output
resistance
55°F (12.8°C)
17.47 k
Ω
792
Ω
60°F (15.6°C)
15.3 k
Ω
695
Ω
65°F (18.3°C)
13.49 k
Ω
597
Ω
70°F (21.1°C)
11.9 k
Ω
500
Ω
75°F (23.9°C)
10.5 k
Ω
403
Ω
80°F (26.7°C
9.3 k
Ω
305
Ω
85°F (29.4°C)
8.25 k
Ω
208
Ω
Table 9. Receiver resistance table for model WDS
Fan command
System command
Nominal output
resistance
Auto or invalid
Emergency heat
35,000
Ω
Auto or invalid
Heat
19,480
Ω
Auto or invalid
Auto
7680
Ω
Auto or invalid
Off
2320
Ω
Auto or invalid
Cool
4870
Ω
On
Emergency heat
43,450
Ω
On
Heat
27,930
Ω
On
Auto
16,130
Ω
On
Off
10,770
Ω
On
Cool
13,320
Ω
High
Invalid
16,130
Ω
Med
Invalid
13,320
Ω
Low
Invalid
10,770
Ω
Auto
Invalid
2320
Ω
Off
Invalid
4870
Ω
Valid
Valid
7680
Ω
Invalid
Valid
7680
Ω
Valid
Invalid
2320
Ω
Invalid
Invalid
—
Summary of Contents for WDS
Page 5: ...BAS SVX04C EN Wireless Sensors 5 Contents Appendix B Agency Compliance 50 ...