20
UV-SVN03D-EN
Modulating Water Valves
(Option)
The actuator on the valve is a 24V, 3-
point floating valve. The actuator can
be easily removed from the valve body
by pressing in on the locking tab and
rotating the actuator 45° counter-
clockwise (See
Figure 6a)
. The 2-way
valves are bi-directional flow. The 3-
way valves can be mixing or diverting
(See
Figure 6b
).
Note: The actuator must be removed if
soldering is being conducted near the
valve. High heat may cause damage to
the actuator’s plastic body/mecha-
nisms.
Figure 6a
: Remove modulating valve
actuator by pressing in tab (inset) and
turning actuator 45° counterclockwise.
Figure 6b
: Steam piping
On applications without the optional,
factory installed piping packages, it is
important to remove the cartridge as-
sembly from the valve body with the
provided tool (
Figure 7
).
Figure 7
: Cartridge removal tool
Closed
Open
A
B
A
B
AB<->B
AB
B
AB<->A
A
AB
2-way valve
3-way valve
Use the following steps to complete
cartridge assembly removal:
1
Remove valve actuator.
2
Remove the cartridge assembly
from the valve body with the en-
closed tool.
3
Solder the valve in accordance with
normal soldering practices.
4
Re-install the cartridge after solder-
ing by tightening until it bottoms
out. The top surface of the car-
tridge will be flush with the top
edge of the body casting.
Note: Do not overtighten. Maxi-
mum torque is 40 in-lb.
5
Replace valve actuator and wire in
accordance with instructions.
Plumbing the Valve
The valve may be plumbed in any an-
gle but preferably not with the actua-
tor below horizontal level of the body.
Make sure there is enough room
around the actuator for servicing or re-
placement.
For use in diverting applications, the
valve is installed with the flow water
entering through the bottom AB port
and diverting through end ports A or
B. In mixing applications the valve is
installed with inlet to A or B and outlet
through AB.
Mount directly to the tube or pipe. Do
not grip the actuator while making or
tightening plumbing connections. Ei-
ther hold valve body by hand or attach
an adjustable spanner (38mm/1-1/2”)
across the hexagonal or flat faces on
the valve body. See
Figure 8
.
Figure 8
: Proper plumbing technique
for modulating valves
Installation
Summary of Contents for VUV
Page 8: ...8 UV SVN03D EN Dimensions Standard Depth Unit ...
Page 9: ...UV SVN03D EN 9 Dimensions Falseback Unit ...
Page 10: ...10 UV SVN03D EN Dimensions Dynamic Air Barrier Unit ...
Page 11: ...UV SVN03D EN 11 Dimensions End Covers ...
Page 12: ...12 UV SVN03D EN Dimensions Wall Boxes ...
Page 33: ...UV SVN03D EN 33 Unit Wiring Field Installed Wiring 120V 1 PH 3 Speed ...
Page 34: ...34 UV SVN03D EN Unit Wiring End Device Controls 120V 1 PH 3 Speed DX Hot Water ...
Page 38: ...38 UV SVN03D EN Unit Wiring Tracer ZN520 120V 1 PH 3 Speed 4 Pipe Hot Water Chilled Water ...
Page 39: ...UV SVN03D EN 39 ...