Component air pressure drops
Table 9 - Pressure drop through accessories
Unit
size
Airflow
(m
3
/h)
Filter
EU2/G2
Filter
EU4/G4
Economizer
100%
outside air
Electric
heater
Hot water
coil
060
3060
31
50
38
17
49
3400
38
55
46
21
55
3740
46
61
55
25
62
4080
55
66
64
30
68
072
3670
13
37
27
7
46
4080
16
42
29
9
52
4490
19
46
31
11
58
4900
23
50
33
13
64
090
4590
19
47
33
12
66
5100
24
52
39
15
74
5610
29
57
45
20
83
6120
35
62
52
25
92
102
5200
16
42
40
8
64
5780
20
47
50
10
72
6360
25
52
62
12
81
6940
30
57
75
15
90
120
6120
22
50
52
11
84
6800
27
55
62
14
95
7480
33
61
73
17
106
8160
40
66
85
20
117