40
UH-SVX01A-EN
Motor Data
*Optional variable speed switch is available.
**These motors are without thermal overload protection.
†230/1/60 unit has 115/1/60 motor supplied with field installed stepdown transformer.
†230/1/60 unit has 115/1/60 motor supplied with field installed stepdown transformer.
Table 18. Totally Enclosed Motor Type
Unit Model No.
AMP
MCA
MOP
HP
RPM
115/1/60
18, 24, A08, A18
0.8
1
1.8
16W*
1550
A36
1.4
1.8
3.2
1/20*
1000
36, A25
1.2
1.5
2.7
25W*
1550
48, 60, 72
1.4
1.8
3.2
1/20*
1000
84, 96, 108
2.2
2.8
5.0
1/12*
1000
120, 132, 144, 156, 180, 204, 240
4.5
5.6
10.1
1/3
1140
280, 300, 360
5.4
6.8
12.2
1/2
1100
230/1/60
18, 24, A08, A18
0.4
0.5
0.9
16W
1550
A36
1.4
1.8
3.2
1/20†
1000
36, A25
0.6
0.8
1.4
25W
1550
48, 60, 72
1.4
1.8
3.2
1/20†
1000
84, 96, 108
2.2
2.8
5.0
1/12†
1000
120, 132, 144, 156, 180, 204, 240
4.5
5.6
10.1
1/3†
1140
280, 300, 360
5.4
6.8
12.2
1/2†
1100
208-230/460/3/60
48, 60, 72, 84, 96, 108, 120, 132, 144, 156, 180, 204,
240, 280, 300, 360
2.6-2.6/1.3
3.3-3.3/1.6
5.9-5.9/2.9
1/2**
1140
Table 19. Explosion Proof with Thermal Overload Motor Type
Unit Model No.
AMP
MCA
MOP
HP
RPM
AMP
MCA
MOP
HP
RPM
115-230/1/60
230/460/3/60
48, 60, 72, 84, 96, 108, 120, 132
3.7
4.6
8.3
1/6†
1140
-
-
-
-
-
144, 156, 180, 204
5.4
6.8
12.2
1/4†
1140
2.2/1.1
2.8/1.4
5.0/2.5
1/3
1140
240, 280, 300
7.4-3.7
9.3-4.7
16.7-8.3
1/3***
1140
2.2/1.1
2.8/1.4
5.0/2.5
1/3
1140
360
7.4-3.7
9.3-4.7
16.7-8.3
1/2***
1140
2.2/1.1
2.8/1.4
5.0/2.5
1/3
1140