background image

54

 CLCH-SVX009A-EN

Routine Maintenance

WARNING

Hazardous Service Procedures!

The maintenance and troubleshooting procedures 
recommended in this manual could result in exposure 
to electrical, mechanical or other potential safety 
hazards. Always refer to the safety warnings provided 
throughout this manual concerning these procedures. 
Unless specified otherwise, disconnect all electrical 
power including remote disconnect and discharge all 
energy storing devices such as capacitors before 
servicing. Follow proper lockout/tagout procedures to 
ensure the power can not be inadvertently energized. 
When necessary to work with live electrical 
components, have a qualified licensed electrician or 
other individual who has been trained in handling live 
electrical components perform these tasks. Failure to 
follow all of the recommended safety warnings 
provided, could result in death or serious injury.

WARNING

Rotating Components!

The following procedure involves working with 
rotating components. Disconnect all electric power, 
including remote disconnects before servicing. Follow 
proper lockout/ tagout procedures to ensure the power 
can not be inadvertently energized. Secure rotor to 
ensure rotor cannot freewheel. Failure to secure rotor 
or disconnect power before servicing could result in 
rotating components cutting and slashing technician 
which could result in death or serious injury. 

Maintenance Checklist

Table 17.

Maintenance Checklist

After 48 hours of operation

For belt-drive fans, the belts have acquired their permanent set. Readjust but do not overtighten. See 

“Tension the Fan Belt,” page 51

 for more 

information.

Every week

Observe unit weekly for any change in running condition and unusual noise.

Every month

Clean or replace air filters if clogged or dirty; coat permanent filters with oil after cleaning; change bag filters when pressure drop is 1 in. wg. 
See 

“Air Filters” on page 55

 for more information.

Belt-drive fans - relubricate fan bearings if necessary. See 

“Fan Bearing Lubrication” on page 61

 for more information.

Belt-drive fans - check and adjust fan belt tension.See 

“Tension the Fan Belt,” page 51

 for more information.

Every three to six months

Belt-drive fans - check fan bearing grease line connections. Lines should be tight to the bearings.

Check motor bracket torque. See 

Table 18, page 61

 for torque requirements.

Belt-drive fans - check bearing bolt torque and bearing setscrew torque. See 

Table 18, page 61

 for torque requirements.

Belt-drive fans - align fan and motor sheaves. Tighten sheave set screws to the proper torque. See 

“Align Fan and Motor Sheaves,” page 53

 

for more information.

Inspect and clean drain pans. See 

“Coils” on page 55

 for more information.

Tighten electrical connections.

Inspect coils for dirt build-up. See 

“Coils” on page 55

 for more information.

Every year 

Inspect the unit casing for corrosion. If damage is found, clean and repaint. 

Clean the fan wheels and shaft. See 

“Coils” on page 55

 for more information.

Inspect and clean drain pans.

Check damper linkages, set screws, and blade adjustment. Clean, but do not lubricate, the nylon damper rod bushings.

Clean damper operators.

Inspect electrical components and insulation.

Inspect wiring for damage.

Rotate the fan wheel and check for obstructions. The wheel should not rub. Adjust the center if necessary.

Lubricate motor bearings in accordance with motor manufacturer’s recommendations (see 

“Motor Bearing Lubrication” on page 61

 for more 

information).

Check condition of gasketing and insulation around unit, door and dampers.

Examine flex connections for cracks or leaks. Repair or replace damaged material.

Summary of Contents for UCCA

Page 1: ...nd training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature...

Page 2: ...on some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the applicable laws and follow them ATTENTION Warnings Ca...

Page 3: ...High intensity C band ultraviolet light is known to severely damage polymer plastic materials and poses a personal safety risk to anyone exposed to the light without proper personal protective equipm...

Page 4: ...23 Joining at Shipping Splits 23 Fan Removal 24 Filter Placement 26 Duct Connections 27 Condensate Drain Connections 27 Fan Discharge Connections 28 Field Conversions 28 Fan Discharge Conversion 28 Ad...

Page 5: ...s 55 Coils 55 Steam and Water Coils 55 Refrigerant Coils 56 Coil Winterization 57 Moisture Purge Cycle 57 Drain Pans 58 Low Limit Switch 58 Fans 60 Inspecting and Cleaning Fans 60 Bearing Set Screw Al...

Page 6: ...tifies the type of section and functional components customer tagging information the unit serial number the unit order number the build section position for installation and the unit model number Not...

Page 7: ...rs with Class B insulation are acceptable for ambient temperatures up to 104 F while motors with Class F insulation can withstand ambient temperatures to 140 F 60 C Note Units with UL approval have a...

Page 8: ...d provided controls Various end device options including Low limit protection Condensate overflow switch Fan status switch Filter status switch Discharge air sensor Mixed air sensor Damper actuator Wi...

Page 9: ...n U 4 row DX 9 fins per in V 4 row DX 12 fins per in W 4 row DX 14 fins per in Y 6 row DX 9 fins per in Z 6 row DX 12 fins per in 1 6 row DX 14 fins per in S Special Digit 14 Coil 2 second in airstrea...

Page 10: ...xed 1300 1400 rpm variable T 1400 rpm fixed 1350 1450 rpm variable U 1450 rpm fixed 1400 1500 rpm variable V 1500 rpm fixed 1450 1550 rpm variable W 1550 rpm fixed 1500 1600 rpm variable Y 1600 rpm fi...

Page 11: ...S Special Digit 31 Controls options 2 0 None A Discharge air sensor B Discharge air sensor and mixed air sensor C Discharge air sensor mixed air sensor factory mounted n o mixing box actuator D Disch...

Page 12: ...d indoors When outdoor storage is necessary several things must be done to prevent damage Note Keep the equipment on the original skid for protection and ease of handling Select a well drained area pr...

Page 13: ...access see Service Clearances on page 14 Refer to submittals for specific minimums Allow room for supply and return piping ductwork electrical connections and coil removal Ensure there is adequate hei...

Page 14: ...56 00 D VFD 48 00 48 00 48 00 48 00 48 00 48 00 48 00 48 00 48 00 48 00 E Electric Heat 45 00 40 00 39 00 35 00 31 00 32 00 27 00 30 00 28 00 23 00 Notes At a minimum the above clearance dimensions a...

Page 15: ...n 23 00 36 00 40 00 52 00 59 00 59 00 67 00 67 00 69 00 82 00 Velocity fpm 537 533 524 504 488 488 522 516 522 527 Dry Weight lb 1 row hydronic 23 35 43 53 65 75 81 96 114 127 2 row hydronic 30 47 60...

Page 16: ...3 16 3 20 0 22 5 26 4 30 6 Nominal Velocity fpm 432 0 432 0 450 0 450 0 369 2 430 8 425 0 466 7 473 7 490 9 2 in Angle Filter 16 x 20 2 6 6 6 4 12 16 x 25 2 3 3 8 20 x 20 4 2 4 6 8 20 x 25 2 12 Area...

Page 17: ...64 44 17 133 09 172 89 21 155 81 290 14 25 168 83 304 07 30 208 34 317 00 Note Add motor weight to get total weight of fan Table 4 Motor weights pounds Motor HP Voltage Motor Weight Frame Size 1 208 2...

Page 18: ...Hz 3 PH 8 60 1800 15 20 15 22 00 27 460 V 60 Hz 3 PH 4 20 1800 4 80 12 11 00 20 575 V 60 Hz 3 PH 3 30 1800 3 90 20 9 00 25 5 208 V 60 Hz 3 PH 15 70 1800 22 00 22 42 00 31 230 V 60 Hz 3 PH 13 60 1800...

Page 19: ...FC Fan 3 10 1 Remove screws attaching shipping protection brackets from center of isolation base to casing mounting bracket 2 Remove shipping protection brackets through door Figure 3 Shipping tie do...

Page 20: ...injury and equipment damage Figure 9 Do not use skid tie down for lifting WARNING Heavy Objects Failure to follow instructions below or properly lift unit could result in unit dropping and possibly c...

Page 21: ...torage and transportation Remove the skids before placing the unit in its permanent location Forklifting Considerations To lift unit with forklift extend the forks under both ends of the unit as indic...

Page 22: ...provided frame can be mounted parallel to airflow or perpendicular to airflow For parallel to airflow channels size channels based on a four point load distribution For perpendicular to airflow channe...

Page 23: ...aking cabinet penetrations or mounting any components to the cabinet Joining at Shipping Splits 1 Bring sections close to each prior to connecting to each other 2 Remove the strap channels top and bot...

Page 24: ...to damage equipment panels 4 Remove screws Item 3 around parameter lip where second level is attached to first level 5 If unit is equipped with optional filter rack insert screws Item 3 in vertical fl...

Page 25: ...sconnected via quick connects in the control interface or VFD box respectively Electric heat wiring should be disconnected from switch in control interface box Any controls low voltage end devices loc...

Page 26: ...20 25 20 20 20 20 25 16 25 16 20 16 20 16 Size 25 26 40 ft 20 25 20 25 20 25 20 25 20 25 20 25 25 16 25 16 Size 30 30 60 ft 20 25 20 25 20 25 20 25 25 16 25 16 25 16 25 16 25 16 25 16 Size 17 20 00 f...

Page 27: ...ft open air can be drawn in through the opening This drawn in air can cause moisture carryover All drain lines Figure 21 Angle filter arrangement Size 3 5 60 ft Size 6 11 10 ft Size 8 12 50 ft Size 10...

Page 28: ...ews inside the cabinet along the top of the coil that secure the coil to the cabinet roof Remove the screws that attach the roof to the side walls and the front panel 4 Remove roof 5 If horizontal fro...

Page 29: ...roper operation height of the fan and motor isolation base Minimum required clearances are listed in Table 6 To determine the isolator clearances on all unit sizes measure between the top of the cabin...

Page 30: ...n for cleaning purposes only it does not need a trap however a cap or shutoff valve should be installed on the drain connection Only sections handling condensate such as a cooling coil section or mois...

Page 31: ...gative pressure L H J pipe diameter where H 1 inch for each inch of negative pressure plus 1 inch J 1 2 H Drain pan trapping for section under positive pressure L H J pipe diameter where H 1 2 inch mi...

Page 32: ...e of the trap 4 If installing coils in series airflow control each coil bank independently with an automatic steam control valve Size the traps for each coil using the capacity of the first coil in di...

Page 33: ...y is below these minimums vent the coil by one of the following methods 1 Install an air vent in the top pipe plug tapping of the return header 2 When the return line rises above the top of the coil v...

Page 34: ...tailed schematics of evaporator piping Figure 32 Example of placement for split system components Discharge line Manual ball valve Access port Filter Access port Access port Filter drier with access p...

Page 35: ...split systems with mircochannel heat exchanger condensers MCHE solenoid valves isolate the refrigerant from the evaporator during the off cycles Trim solenoids cannot be used with MCHE Note Trane con...

Page 36: ...installed after the system is cleaned up Access port The access port is used to determine suction pressure This port is usually a Schraeder valve with a core Frostat coil frost protection The Frostat...

Page 37: ...suitable for use with R 410A These same lines sized at 1 5 8 OD or 2 1 8 OD must use type K or thicker wall Expansion valves need to be reselected Expansion valves are refrigerant specific Any gasket...

Page 38: ...ader connection 4 Use the tube diameter recommended in the condensing unit application manual for a vertical rise Ensure that the top of the riser is higher than the evaporator coil 5 Pitch the suctio...

Page 39: ...Use the tube diameter recommended for a vertical rise as specified in the condensing unit application manual Assure the top of the riser is higher than the evaporator coil 7 Pitch the suction line sl...

Page 40: ...ameter recommended for a vertical rise as specified in the condensing unit application manual Ensure that the top of the riser is higher than the evaporator coil 7 Pitch the suction line slightly 1 in...

Page 41: ...or a vertical rise as specified in the condensing unit application manual 5 The top of the Circuit 2 suction riser must be higher than the top evaporator coil Use the tube diameter recommended for a v...

Page 42: ...as specified in the condensing unit application manual Ensure that the top of the riser is higher than the evaporator coil 7 Pitch the suction line slightly 1 inch 10 feet so that the refrigerant dra...

Page 43: ...hematic for specific wiring details and point to point wiring connections Dashed lines indicate field wiring on the unit wiring schematics All interconnection wiring must conform to NEC Class 2 wiring...

Page 44: ...50 14 50 17 50 20 47 20 41 230 V 60 Hz 3 PH 6 13 6 26 7 32 8 41 10 53 12 59 14 59 17 59 20 56 20 50 460 V 60 Hz 3 PH 6 13 6 24 7 32 8 44 10 53 12 63 14 75 17 95 20 95 20 120 575 V 60 Hz 3 PH 6 13 6 26...

Page 45: ...208 230 3 LP CC 25 CC 208 230 5 JJN 50 T 208 230 7 5 JJN 50 T 208 230 10 JJN 80 T 208 230 15 JJN 100 T 460 1 LP CC 10 CC 460 1 5 2 LP CC 10 CC 460 3 LP CC 15 CC 460 5 LP CC 15 CC 460 7 5 LP CC 25 CC...

Page 46: ...5 JJN 80 T 208 230 7 5 JJN 100 T 208 230 10 JJN 100 T 460 3 LP CC 25 CC 460 5 LP CC 25 CC 460 7 5 JJS 50 T 460 10 JJS 50 T 460 15 JJS 80 T 575 3 LP CC 20 CC 575 5 LP CC 20 CC 575 7 5 LP CC 30 CC 575...

Page 47: ...2 6T3 12B 15B 1Q1 L3 L2 L1 6A 6A 5A 5A 4A 4A BLK RED 1T1 24V 208V 1T1 24V 1T1 24V 1T1 24V 12A 15A 18A BLU YEL 1K3 1K3 1K3 4D D 5D D SPLICE SPLICE SPLICE DEVICE PREFIX LOCATION CODE AREA 1 MAIN CONTROL...

Page 48: ...ubrication if necessary See Fan Bearing Lubrication page 61 Coil Related Checks Ensure coil and condensate drain piping connections are complete Check the piping and valves for leaks Open or close the...

Page 49: ...ance is 2 percent Voltage imbalance is defined as 100 times the sum of the deviation of the three voltages from the average divided by twice the average voltage For example if the three measured volta...

Page 50: ...plate 1 22 Motor Voltage Depends on unit Set Based on Motor Nameplate 1 24 Motor Current Depends on unit Set Based on Motor Nameplate 1 25 Rated Motor Speed Depends on unit Set Based on Motor Nameplat...

Page 51: ...ee Figure 44 Determine actual deflection by depressing one belt with the belt tensiometer and measuring the deflection relative to the other belts or to belt line see Figure 45 Adjust the belt tension...

Page 52: ...4 8 5 12 6 2 501 4 000 6 0 8 9 7 3 10 9 C CX 7 0 9 0 500 1 740 11 5 17 0 14 7 21 8 1 741 3 000 9 4 13 8 11 9 17 5 9 5 16 0 500 1 740 14 1 21 0 15 9 23 5 1 741 3 000 12 5 18 5 14 6 21 6 D 12 0 16 0 200...

Page 53: ...are not parallel Realign as required After realignment tighten the belts again to the standard belt tensioning specifications If the force is still not the same for all belts the belts or sheaves are...

Page 54: ...and unusual noise Every month Clean or replace air filters if clogged or dirty coat permanent filters with oil after cleaning change bag filters when pressure drop is 1 in wg See Air Filters on page...

Page 55: ...o ensure rotor cannot freewheel Failure to secure rotor or disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious...

Page 56: ...9 Repeat steps 6 and 7 as necessary 10 Straighten any coil fins that may have been damaged during the cleaning process 11 Confirm the drain line is open following the cleaning process 12 Allow the un...

Page 57: ...e the heating season begins Note On many unit sizes there are multiple coils in the coil section Be sure to winterize all coils in a given coil section To winterize hydronic coils 1 Remove the vent an...

Page 58: ...to the mounting wall 4 Loosen the set screw in the wheel drive pulley using an Allen wrench and remove the pulley from the motor drive shaft 5 While supporting the weight of the drive motor in one han...

Page 59: ...for clarity Figure 50 Resetting low limit switch for vertical units Low limit freeze stat Note Fan access door removed for clarity only Figure 51 Resetting low limit switch for horizontal DDP fan unit...

Page 60: ...metal surfaces 6 Allow the unit to dry completely before putting it back into service 7 Be careful any contaminated material does not contact other areas of the unit or building Properly dispose of a...

Page 61: ...e Many different styles of motors come as standard selections so please obtain the motor IOM and use the manufacturer recommended grease Fan Motor Inspection Inspect fan motors periodically for excess...

Page 62: ...er company for adjustments Mechanical failure Check that motor and drive rotate freely Check bearing lubricant Motor stalls Open phase Check line for an open phase Overloaded motor Reduce load or repl...

Page 63: ...e see the Coils section on page 55 Do not use steam to clean refrigerant coils Fin frosting Verify defrost cycle operation Verify frostat operation Verify refrigerant charge Low steam coil capacity In...

Page 64: ...lio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and r...

Reviews: