19
System Settings
Î
Changing these settings will affect the operation of the heating/cooling system.
To view and edit these settings:
1. Press the
MENU
button.
2. Press and hold the two middle buttons simultaneously until the
Installer Settings
menu is displayed.
3. Scroll to System Settings and press the
Select
button.
4. Scroll to the setting you want to change. Press the plus (
+
) or minus (
-
) button to adjust the setting.
5. Press the
Done
button when you are finished.
Î
Note on Delta Settings: The Delta T Setting is the delta, or difference between, the setpoint and current temp for
determining when a heat or cool call comes on. The “delta” is the number of degrees away from setpoint.
Setting
Range
Default
Description
Schedule
Enable
Y or N
N
When enabled, the local thermostats scheduler function is enabled.
Recovery
Enable
Y or N
N
See Thermostat Recovery Operation below.
H/C Delta
3 - 15
degrees
3
Sets the minimum separation between heating and cooling
setpoints. Attempts to lower the cooling below the heating setpoint
by this amount will PUSH the heating setpoint down to maintain
this separation. Same for setting the heating setpoint above the
cooling setpoint, it will PUSH the cooling setpoint up to maintain this
separation.
Heating Delta
Stage 1 ON
1 to 8
degrees
1
Sets the delta from setpoint that stage 1 heating starts.
Heating Delta
Stage 1 OFF
0 to 8
degrees
0
Sets the delta from setpoint that stage 1 heating stops. Stage 1
turns off at setpoint minus (-) Delta Stage 1.
Heating Delta
Stage 2 ON
1 to 8
degrees
2
Sets the delta from setpoint that stage 2 heating starts.
Heating Delta
Stage 2 OFF
0 to 8
degrees
0
Sets the delta from setpoint that stage 2 heating stops. Stage 2
turns off at setpoint minus (-) Delta Stage 2.
Heating Delta
Stage 3 ON
1 to 8
degrees
3
Sets the delta from setpoint that stage 3 heating starts.
Heating Delta
Stage 3 OFF
0 to 8
degrees
0
Sets the delta from setpoint that stage 1 heating stops. Stage 3
turns off at setpoint minus (-) Delta Stage 3.
Cooling Delta
Stage 1 ON
1 to 8
degrees
1
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Delta
Stage 1 OFF
0 to 8
degrees
0
Sets the delta from setpoint that stage 1 Cooling stops. Stage 1
turns off at setpoint plus (+) Delta Stage 1.
Cooling Delta
Stage 2 ON
1 to 8
degrees
2
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Delta
Stage 2 OFF
0 to 8
degrees
0
Sets the delta from setpoint that stage 2 Cooling stops. Stage 2
turns off at setpoint plus (+) Delta Stage 2.
Thermostat Recovery Operation
The Recover feature is active only when “Schedule” is enabled and the schedule mode is set to “RUN”
Recovery operation, when enabled, will start the cooling or heating system so that the desired comfort temperature is reached by the
next scheduled set point time. The advance start time calculation is a learned process that is recalculated and adjusted each day until
the room temperature is at the target temperature at the schedule time. When the thermostat is in Recovery mode the display will show
“Recov”.
Recovery works for all scheduled periods (1-4) and in HEAT, COOL or AUTO modes. While in Recovery the Aux-Heat stage will not
engage.
The maximum Recovery time is one hour.