Technical Service Manual

TVR LX Systems

Low Static Pressure Duct Units with DC Fan Motor
220-240V/50-60Hz/1ph

August 2015

Summary of Contents for TVR LX 4TVL0024DF000AA

Page 1: ...Technical Service Manual TVR LX Systems Low Static Pressure Duct Units with DC Fan Motor 220 240V 50 60Hz 1ph August 2015...

Page 2: ...ic Pressure Duct with DC Fan Motor 1 Features 2 2 Specifications 3 3 Dimensions 7 4 Service Spaces 8 5 Piping Diagrams 9 6 Wiring Diagrams 10 7 Fan Performance 11 8 Capacity Tables 13 9 Electrical Cha...

Page 3: ...ling slab 1 4 The length of air duct can be 6m 1 5 Wide capacity range The capacity range is from 1 8kw to 7 1kw totally 7 models available 1 6 Convenient installation and maintenance 1 6 1 The EXV is...

Page 4: ...147 20 9 32 5 25 32 515 147 Number of circuits 3 3 Indoor air flow H M L m 3 h 590 520 415 590 520 415 CFM 347 306 244 347 306 244 Indoor external static pressure H Pa 10 10 30 10 10 30 Indoor noise...

Page 5: ...9 32 5 25 32 515 147 Number of circuits 3 3 Indoor air flow H M L m 3 h 590 520 415 655 560 465 CFM 347 306 244 386 330 274 Indoor external static pressure H Pa 10 10 30 10 10 30 Indoor noise level H...

Page 6: ...57 64 5 25 32 735 147 Number of circuits 6 6 Indoor air flow H M L m 3 h 856 740 600 905 740 580 CFM 504 436 353 533 436 341 Indoor external static pressure H Pa 10 10 30 10 10 30 Indoor noise level H...

Page 7: ...6 Indoor air flow H M L m 3 h 970 800 660 CFM 571 471 388 Indoor external static pressure H Pa 10 10 30 Indoor noise level H M L dB A 40 32 29 Indoor unit Dimension W H D mm 1180 210 470 Packing W H...

Page 8: ...Low Static Pressure Duct with DC Fan Motor 7 3 Dimensions...

Page 9: ...he ceiling is horizontal and its structure can endure the weight of the indoor unit The outlet and the inlet are not impeded and the influence of external air is the least The air flow can reach throu...

Page 10: ...Low Static Pressure Duct with DC Fan Motor 9 5 Piping Diagrams flare nut flare nut T2B gas side motor heat exchanger fan EXV liquid side T2 T1...

Page 11: ...Low Static Pressure Duct with DC Fan Motor 10 6 Wiring Diagrams...

Page 12: ...is and the fan in medium speed 2L means ENC2 is and the fan in low speed 1H 1M 1L indicate the testing diagram of the fan in high medium and low speed when ENC2 is 0H 0M 0L indicate the testing diagr...

Page 13: ...is the min airflow of this duct unit At this flow volume the fan achieves the max ESP and indoor evaporator may be protected by low temperature As well there s a limit airflow volume which is the max...

Page 14: ...1 8 1 2 1 8 1 2 1 9 1 1 1 9 1 1 46 0 1 2 1 1 1 5 1 2 1 7 1 2 1 8 1 2 1 8 1 2 1 9 1 1 1 9 1 1 2 2 10 0 1 5 1 3 1 8 1 4 2 1 1 5 2 2 1 5 2 3 1 6 2 6 1 6 2 9 1 5 12 0 1 5 1 3 1 8 1 4 2 1 1 5 2 2 1 5 2 3...

Page 15: ...1 0 2 5 1 9 2 9 2 1 3 4 2 3 3 6 2 4 3 8 2 5 4 2 2 6 4 1 2 2 33 0 2 5 1 9 2 9 2 1 3 4 2 3 3 6 2 4 3 8 2 5 4 2 2 6 3 9 2 1 35 0 2 5 1 9 2 9 2 1 3 4 2 3 3 6 2 4 3 8 2 5 4 2 2 6 3 9 2 1 37 0 2 5 1 9 2 9 2...

Page 16: ...6 3 4 5 7 3 4 5 8 3 2 6 0 3 1 46 0 3 9 2 7 4 6 3 0 5 3 3 3 5 6 3 4 5 7 3 7 5 8 3 2 6 0 3 1 7 1 10 0 4 9 3 6 5 8 4 0 6 7 4 3 7 1 4 5 7 5 4 4 8 4 4 5 9 2 4 6 12 0 4 9 3 6 5 8 4 0 6 7 4 3 7 1 4 5 7 5 4 4...

Page 17: ...2 42 2 38 2 20 2 13 2 02 1 85 13 70 15 00 2 49 2 38 2 20 2 13 2 02 1 85 2 2 20 19 8 1 46 1 46 1 46 1 46 1 46 1 46 19 18 8 1 56 1 56 1 56 1 56 1 56 1 56 17 16 7 1 64 1 64 1 64 1 64 1 64 1 64 15 14 7 1...

Page 18: ...6 2 20 3 00 3 76 3 76 3 76 3 76 3 68 3 36 4 10 5 00 3 88 3 88 3 88 3 88 3 68 3 36 6 00 7 00 4 00 4 00 4 00 3 88 3 68 3 36 7 90 9 00 4 12 4 12 4 00 3 88 3 68 3 36 9 80 11 00 4 24 4 24 4 00 3 88 3 68 3...

Page 19: ...0 6 30 6 11 5 80 5 29 13 70 15 00 7 12 6 80 6 30 6 11 5 80 5 29 7 1 20 19 8 4 48 4 48 4 48 4 48 4 48 4 48 19 18 8 4 80 4 80 4 80 4 80 4 80 4 80 17 16 7 5 04 5 04 5 04 5 04 5 04 5 04 15 14 7 5 20 5 20...

Page 20: ...187 264 0 375 15 0 016 0 3 4TVL0009DF000AA 50 60 220 240 187 264 0 375 15 0 016 0 3 4TVL0012DF000AA 50 60 220 240 187 264 0 375 15 0 021 0 3 4TVL0015DF000AA 50 60 220 240 187 264 0 5 15 0 032 0 4 4TV...

Page 21: ...t of ambient conditions 2 Semi anechoic chamber conversion value measured at a point which is 1 4m under the unit 10 2 Test value Model Sound Levels value dB A H M L 4TVL0006DF000AA 34 26 24 4TVL0007D...

Page 22: ...Low Static Pressure Duct with DC Fan Motor 21 4TVL0006DF000AA 4TVL0007DF000AA...

Page 23: ...Low Static Pressure Duct with DC Fan Motor 22 4TVL0009DF000AA 4TVL0012DF000AA...

Page 24: ...Low Static Pressure Duct with DC Fan Motor 23 4TVL0015DF000AA 4TVL0018DF000AA...

Page 25: ...Low Static Pressure Duct with DC Fan Motor 24 4TVL0024DF000AA...

Page 26: ...insulation Water outlet joint 1 For drainage Clasp 1 Chucking the joint which connect the drain hose and the outlet of indoor unit Copper nut 1 Use for pipe connection of engineering installation Sig...