SS-SVN03B-EN
5
General
Data
General
This “Installation Manual” describes
information for condensing units TTK
509 to TTK 536, with horizontal air
discharge, cooling-only, from 9,000 to
36,000 Btu/h.
After unpacking the unit, inspect the
unit for any damage incurred in transit.
Immediately notify the carrier.
Compare the power supply
characteristics with the unit nameplate
data. The power supply must comply
with the unit nameplate data.
All stages of this installation should
comply with local, state and national
codes.
These installation instructions should
be carefully read prior to the air
conditioning system installation.
These instructions are not intended for
all system variations, nor advise
against all situations that may occur
during an installation. If more
information is required, or problems
that avoid client satisfaction arise,
contact your nearest Trane sales office
or Trane.
Unit Location and Preparation
1. The unit should be installed on a
leveled and reinforced concrete
foundation. The minimum height of
the concrete foundation should be
50 mm (1.97”). Unit shall be fixed to
the foundation with bolts (not
supplied).
2. The concrete foundation must be
positioned at least 250 mm (9.84”)
away from any existing wall or
shrubbery.
3. The minimum clearance on the air
inlet sides of the unit should be
250 mm (9.84”), and on the air
discharge side, 1200 mm (47.24”).
4. When the unit is mounted on a roof,
be sure the roof will support the unit
weight. Proper vibration isolation is
recommended in order to prevent
transmissions to the building
structure.
5. Minimum clearances between the
unit and other objects should be
observed in order to assure proper
ventilation.
WARNING!
!
Figure 01 - Recommended installation clearances
Rear
Side
Side
Front
Recommended installation and maintenance clearances
Obstacle (wall)
Distance for air inlet
250 mm (9.84”) (minimum)
Obstacle (wall)
Distance for air inlet
250 mm (9.84”) (minimum)
Obstacle (wall)
Distance for maintenance
300 mm (11.81”) (minimum)
Obstacle (wall)
Distance for air discharge
1200 mm (47.24”) (minimum)
600 mm (23.62”) (minimum)
Note: All dimensions are in mm( inches)