Trane TTA240F Series Application Manual Download Page 8

2

 SS-APG008-EN

Overview

The origin of the requirements for equivalent line lengths of components, line pressure drop, and 
minimum and maximum refrigerant velocities is uncertain. It appears likely that at least some of 
the supporting data was derived from measurements and/or equations involving water. Some 
resource materials even 

show

 water components when illustrating refrigerant piping 

requirements.

Subsequent reviews of analytical and empirical data for refrigerant piping resulted in the 
publication of two research papers:

Pressure Losses in Tubing, Pipe, and Fittings

 by R.J.S. Pigott 

and 

Refrigerant Piping Systems—Refrigerants 12, 22, 500

 by the American Society of 

Refrigeration Engineers (ASRE). In his paper, Pigott described his use of refrigerant as the fluid 
and his direct measurement of pressure drops. His findings indicated that the pressure drop of 
many line components is small and difficult to measure. For these components, he used 
experimental data to derive a formula relating the geometry of the component to its pressure 
drop. Overall, his calculated pressure loss of the components was less than originally 
determined.

The conclusion of the ASRE research paper stated that the minimum required velocity to 
maintain oil entrainment in vertical risers and horizontal lines will vary with the diameter of the 
tube 

and with the saturation temperature of the suction gas

. In other words, the minimum 

required velocity for oil entrainment is not constant.

Updated Guidelines

Liquid Lines

Historically, liquid lines were sized to minimize the pressure losses within the piping circuit. Oil 
movement through the piping wasn’t a concern (nor is it today) because oil is miscible in liquid 
refrigerant at normal liquid-line temperatures. The historic and traditional 6 psid liquid line 
pressure drop had the unintended consequence of requiring line sizes with large internal 
refrigerant volumes. Since our objective is also to minimize the refrigerant charge to make the 
most reliable systems, we increased the allowable liquid pressure drop to 35 psid (R-22), which 
allows for the selection of a smaller liquid line while still maintaining refrigeration operation. 
With R-410A refrigerant and POE oil, this pressure drop can be as high as 50 psid. Within these 
guidelines, refrigeration operation is maintained while minimizing the refrigerant charge. It is 
still required to limit the liquid line velocity to 600 ft/min to help avoid issues with water hammer.

Suction Lines

R-410A is a high-pressure refrigerant and allows higher-pressure drops in the suction lines. With 
R-22, a 2°F loss in the suction line means a pressure drop of 3 psi. With R-410A refrigerant, that 
same 2°F loss is a 5 psi drop. Additional pressure drop may be tolerated in certain applications.

R-410A refrigerant suction lines must be sized to maintain oil-entrainment velocities in both the 
horizontal lines and vertical risers. Oil entrainment for R-410A is based on suction temperature as 
well as tube diameter. At the time of this writing, no known direct oil-entrainment tests have been 
published. Trane has used ASHRAE data to create equation-based formulas to predict the 
entrainment velocities of R-410A refrigerant and POE oil. These minimum velocities are reflected 
in the line sizes listed in the component selection summary tables (

Table 2, p. 20

, and 

Table 3, 

p. 21

).

Summary of Contents for TTA240F Series

Page 1: ...nd Component Selection for TTA and TWA Split Systems 6 20 Tons Using Refrigerant 410A Model Numbers TTA073D TTA090D TTA120D TTA120E TTA120F TTA150E TTA180E TTA180F TTA240E TTA240F TWA073D TWA120D TWA1...

Page 2: ......

Page 3: ...ent our customers and the air conditioning industry All technicians who handle refrigerants must be certified The Federal Clean Air Act Section 608 sets forth the requirements for handling reclaiming...

Page 4: ...e is a risk of arc or flash technicians MUST put on all necessary Personal Protective Equipment PPE in accordance with NFPA70E for arc flash protection PRIOR to servicing the unit Failure to follow re...

Page 5: ...f airflow and that provide no more than 45 percent ventilation outdoor air Prospective applications outside this operating envelope including low ambient process and 100 percent outdoor air applicatio...

Page 6: ...es 2 Equipment Placement 3 Line Sizing Routing and Component Selection 5 Liquid Lines 5 Line Sizing 5 Routing 5 Insulation 5 Components 5 Gas Line 7 Line Sizing 7 Routing 7 Insulation 8 Components 8 E...

Page 7: ...accumulated over years of observation demonstrates that the lower the refrigerant charge the more reliably a split air conditioning system performs Any amount of refrigerant in excess of the minimum...

Page 8: ...thin the piping circuit Oil movement through the piping wasn t a concern nor is it today because oil is miscible in liquid refrigerant at normal liquid line temperatures The historic and traditional 6...

Page 9: ...interconnecting refrigerant line by the shortest and most direct path so that line lengths and riser heights are no longer than absolutely necessary Use only horizontal and vertical piping configurati...

Page 10: ...iew Figure 2 Allowable elevation difference Cooling only TTA above indoor unit Figure 3 Allowable elevation difference TWA heat pump above indoor unit Figure 4 Allowable elevation difference TTA or TW...

Page 11: ...tion In fact heat loss from the liquid line improves system capacity because it provides additional subcooling If the liquid line is routed through a high temperature area such as an attic or mechanic...

Page 12: ...icating ability Use the Installation manual charging curves not the sightglass to determine proper charge levels Expansion Valve The expansion valve is the throttling device that meters the refrigeran...

Page 13: ...ard the indoor coil Do not install riser traps With field supplied air handler coils what appears to be a riser trap is located at the coil outlet see Figure 5 for an example This piping arrangement w...

Page 14: ...ngs and joints to verify that the system is leak free insulate the gas lines to prevent heat gain and unwanted condensation Components Adding a gas line filter is unnecessary provided that good refrig...

Page 15: ...ual distributors 10 2 5 Each TXV should be selected for 5 tons Example 2 10 ton coil one refrigerant circuit with two distributors and a 60 40 coil split 10 x 6 6 and 10 x 4 4 One TXV should be sized...

Page 16: ...r to the third party Simply stated this means that when a compressor turns on it shouldn t turn off until the expansion valve comes under control And once the compressor turns off it should be allowed...

Page 17: ...roblems Finally hot gas bypass uses excessive amounts of energy by preventing the compressors from cycling with fluctuating loads Trane now has several years of successful experience with Evaporator D...

Page 18: ...e for use with R 410A Suction lines 3 1 8 OD must use type K or thicker wall Discharge lines liquid lines heat pump vapor lines and hot gas bypass lines 1 3 8 OD and smaller of type L copper are suita...

Page 19: ...length of the liquid line exceeds 80 ft 24 m remove the liquid line filter drier from the TTA and install a new one Table 2 p 20 at the TWE air handler 1 If the total length of the liquid line exceeds...

Page 20: ...cal arrangement shown in cooling mode 1 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will start in the cooling mode remove the liquid line filter driers fr...

Page 21: ...s one thermal expansion valve TXV and one check valve See Table 3 and Table 4 p 21 for recommendations 2 For applications where the length of the liquid line exceeds 80 ft 24 m and the heat pump will...

Page 22: ...ble 3 p 21 2 Provide one expansion valve TXV per distributor TWA heat pumps only Provide one check valve for each expansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the...

Page 23: ...er 10 feet 1 cm per 3 m 4 Arrange the gas line so that suction gas leaving the coil flows downward past the lowest gas header outlet before turning upward Use a double elbow configuration on all lower...

Page 24: ...3 p 21 2 Provide one expansion valve TXV per distributor TWA heat pumps only Provide one check valve for each expansion valve 3 Pitch the gas line leaving the coil so that it slopes away from the coil...

Page 25: ...nch per 10 feet 1 cm per 3 m 4 Arrange the gas line so that suction gas leaving the coil flows downward past the lowest gas header outlet before turning upward Use a double elbow configuration on all...

Page 26: ...eder valve w core LIQUID LINE LIQUID LINE Tube diameter in 1 2 5 8 1 2 1 2 1 2 1 2 1 2 5 8 1 2 5 8 Filter drier DHY01123 DHY01232 DHY01123 DHY01123 DHY01123 DHY01123 DHY01123 DHY01131 DHY01123 DHY0113...

Page 27: ...6 3 8 VAL08459 1 2 VAL08460 5 8 VAL01722 Valve body VAL01483 valve core COR00006 valve cap CAP00072 The heat pump products require two filters and two check valves one set oriented for liquid in the...

Page 28: ...r Number SS APG008 EN Date October 2009 Supersedes New Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice O...

Reviews: