Trane TTA200FD Series Installation Operation & Maintenance Download Page 17

TTA-SVN03A-EN

17

Unit Start-Up

Once the unit is properly installed and 
pre-start procedures are complete, 
start the unit by turning the System 
Switch on the indoor thermostat to 
either HEAT, COOL or AUTO. The 
system should operate normally.

CAUTION

Ensure the disconnect for the indoor 
air handler is closed before operating 
the system. Operating the indoor unit 
without the indoor fan energized, can 
cause unit trip-out on high pressure 
control and/or liquid flood back to the 
compressor.

Sequence of Operation

ReliaTel

TM

 Control 

Unit Model Number Digits 9 and 
10 = 0R, 0T, OU or OW

The ReliaTel Controls is a 
microelectronic control feature, which 
provides operating functions that are 
significantly different than 
conventional Electromechanical units. 
The ReliaTel Refrigeration Module 

(RTRM)

 uses Proportional/Integral 

control algorithms to perform specific 
unit functions that govern the unit 
operation in response to application 
conditions.

The RTRM provides compressor anti-
short cycle timing functions through 
minimum 

“Off”

 and 

“On”

 timing to 

increase reliability, performance and 
to maximize unit efficiency. Upon 
power initialization, the RTRM 
performs self-diagnostic checks to 
insure that all internal controls are 
functioning. It checks the 
configuration parameters against the 
components connected to the system. 
The Light Port LED located on the 
RTRM module is turned 

“On”

 within 

one second after power-up if all 
internal operations are okay.

ReliaTel Control Cooling Mode

When the system switch is set to the 

COOL

 position and the zone 

temperature rises above the cooling 
setpoint, the RTRM energizes the 
compressor relay coil located on the 
RTRM. When the compressor relay 
contacts close, the compressor 
contactor coil is energized provided 
the low and high pressure controls 
are closed. When the compressor 
contacts close, the compressor and 
the outdoor fan motor start to 
maintain the zone temperature to 
within ± 2 F of the sensor setpoint at 
the sensed location.

On units with dual circuits, the second 
stage of cooling is initiated as a result 
of the Proportional/Integral control 
algorithms calling for additional 
cooling.

For Thermostat Control:

When the room thermostat system 
switch is positioned at 

COOL 

and the 

fan switch is at 

AUTO

, the RTRM 

energizes the compressor relay coil 
located on the RTRM during a call for 
cooling. When the compressor relay 
contacts close, the compressor 
contactor coil is energized provided 
the low and high pressure controls 
are closed. When the contacts of the 
compressor contactor close, 
operation of the compressor and 
condenser fan begins. The evaporator 
fan contactor also energizes on a call 
for cooling and initiates evaporator 
fan operation.

On units with dual circuits, the second 
stage of cooling is initiated as a result 
of the 2-stage thermostat calling for 
additional cooling.

Note:

Irregular unit operation may 
occur when the unit is 
controlled with a triac-
switching thermostat. Please 
review the approved 
thermostat vendor list for all 
recommended relay-switching 
thermostats.

ReliaTel Control Evaporator Fan 
Operation

When the fan selection switch is set to 
the 

AUTO

 position, the RTRM 

energizes the evaporator fan relay coil 
approximately 1 second after 
energizing the compressor contactor 
coil in the cooling mode. In the 
heating mode, the RTRM energizes 
the evaporator fan

 

relay coil 

approximately 1 second before 
energizing the electric heat 
contactors. The RTRM de-energizes 
the evaporator fan relay coil 
approximately 60 seconds after the 
cooling requirement has been 
satisfied to enhance unit efficiency. 
When the heating cycle is terminated, 
the evaporator fan relay coil is de-
energized at the same time as the 
heater contactors. When the fan 
selection switch is set to the 

ON

 

position, the RTRM keeps the 
evaporator fan relay coil energized for 
continuous fan motor operation.

ReliaTel Control Heating 
Operation

When the system switch is set to the 

HEAT

 position and heating is 

required, the RTRM energizes the Heat 
1 relay coil. When the Heat 1 relay 
contacts close, the first stage electric 
heat contactor is energized. If the first 
stage of electric heat cannot satisfy 
the heating requirement, the RTRM 
energizes the Heat 2

 

relay coil. When 

the Heat 2

 

relay contacts close, the 

second stage electric heat contactor is 
energized. The first and second stages 
of heat are cycled 

“On”

 and 

“Off”

 as 

required to maintain the zone.

System Start Procedure
ReliaTel™ Controls

Summary of Contents for TTA200FD Series

Page 1: ...TTA SVN03A EN June 2006 Installation Operation Maintenance Split System Cooling Condensers 20 Ton Model 60 Hz TTA240F A Model 50 Hz TTA200FD A...

Page 2: ...n must conform with National Electric Code ANSI NFPA NO 70 LATEST REVISION Note Do Not release refrigerant to the atmosphere If adding or removing refrigerant is required the service technician must c...

Page 3: ...ce and Cautions and Warnings 2 Model Number Description 4 Electrical Data 6 Installation 7 System Prestart Procedure 15 System Test Mode ReliaTel 18 Troubleshooting ReliaTel 19 Maintenance 22 Warranty...

Page 4: ...CT TYPE TTA Split System Cooling DIGITS 4 6 NOMINAL GROSS COOLING CAPACITY MBh 200 200 MBh 240 240 MBh DIGIT 7 REFRIGERATION CIRCUIT A 1 Refrigerant Circuit R22 B 2 Refrigerant Circuit R22 C Manifold...

Page 5: ...imensional Data Connection Location Clearances Corner Weights APPROXIMATE CORNER WEIGHT MASS TOTAL UNIT WEIGHT TOTAL SHIPPING WEIGHT MODEL NO 1 2 3 4 TTA240F A 292 lbs 181 lbs 222 lbs 140 lbs 835 lbs...

Page 6: ...Circuit Fuse Amps Amps Number Characteristics Range Ampacity Size Qty RLA LRA Qty HP FLA LRA TTA240F3 208 230 60 3 187 254 89 4 110 2 35 3 239 0 2 1 5 0 14 4 TTA240F4 460 60 3 414 506 46 6 60 2 18 5 1...

Page 7: ...it is stored and as soon as possible after delivery Concealed damage must be reported within 15 days If concealed damage is discovered stop unpacking the shipment Do not remove damaged material from t...

Page 8: ...allation maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation Glass wool fibers may a...

Page 9: ...fold valve for the line that is connected to the suction line service valve Disconnect the line from the gauge port on the valve Figure 4 Refrigerant Piping Procedure Indoor Unit Once liquid and sucti...

Page 10: ...removed and power is applied to the unit Failure to observe all safety precautions could result in severe personal injury or death 2 Turn on power to the unit Allow the system to run for five to ten...

Page 11: ...storing components provided by Trane or others refer to the appropriate manufacturer s literature for allowable waiting periods for discharge of capacitors Verify with an appropriate voltmeter that al...

Page 12: ...or 10 wires maximum 24 volts of wires are dependent upon zone sensor selection F NSB Panel 8 wires 24 volts Figure 6 Typical Field Wiring ReliaTel Control Note 1 Wiring shown with dashed lines is to b...

Page 13: ...TTA SVN03A EN 13 Installation Figure 7 Night Setback Panel Field Wiring Figure 8 Zone Sensor Field Wiring Figure 9 Thermostat Field Wiring...

Page 14: ...14 TTA SVN03A EN Installation Figure 10 TTA240F TWE240E Refrigerant Circuit...

Page 15: ...s returned to normal the compressor will cycle back on Internal Overload Protector IOL This device is a thermal actuated snap disc imbedded in the compressor It will shut off the compressor if the dis...

Page 16: ...ON AUTO switch on the room thermostat With the switch positioned at AUTO and the system operating in the cooling mode fan operation coincides with the cooling run cycles If the system is equipped with...

Page 17: ...ditional cooling For Thermostat Control When the room thermostat system switch is positioned at COOL and the fan switch is at AUTO the RTRM energizes the compressor relay coil located on the RTRM duri...

Page 18: ...Mode will be ignored if a short is present across Test 1 and Test 2 at start up 2 Resistance Test Mode This method can be used for start up providing a decade box for variable resistance outputs is a...

Page 19: ...n to start the unit This procedure will allow you to check all of the RTRM outputs and all of the external controls relays contactors etc that the RTRM outputs energize for each respective mode Procee...

Page 20: ...use LED s for quick status information at the unit purchase a BAYSENS010B ZSM and connect wires with alligator clamps to terminals 6 through 10 Connected each respective terminal wire 6 through 10 fr...

Page 21: ...forward direction If high resistance in both directions LED is open If low in both directions LED is shorted Method 3 To test LED s with ZSM connected to unit test voltages at LED terminals on ZSM A m...

Page 22: ...ation 1 Perform all of the monthly maintenance inspections 2 With the unit operating check unit superheat and record the reading in the Maintenance Log 3 Remove any accumulation of dust and or dirt fr...

Page 23: ...Log Date Ambient Temp F Evaporator Entering Air Compressor Superheat Circuit 1 F Subcooling Circuit 1 F Dry Bulb Wet Bulb Suction Pressure Discharge Pressure Perform each inspection once per month du...

Page 24: ...hall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective THE WARRANTY AND LIABI...

Page 25: ...conforming to this warranty Warrantor shall not be obligated to pay for the cost of lost refrigerant No liability whatever shall attach to Warrantor until said products have been paid for and then sa...

Page 26: ...26 TTA SVN03A EN...

Page 27: ...TTA SVN03A EN 27...

Page 28: ...nuous product and data improvement and reserves the right to change design and specifications without notice Literature Order Number TTA SVN03A EN File Number SV UN TTA SVN03A EN 06 06 Supersedes New...

Reviews: