background image

SS-SVF15A-EN

7

Sequence of Operation

NOTICE

Equipment Damage!

Ensure the disconnect for the indoor air handler is closed before operating the system. 
Operating the outdoor unit without the indoor fan energized can cause unit trip-out on high 
pressure control and/or liquid flood back to the compressor.

Electromechanical Controls 

General

Operation of the system cooling (and optional heating) cycles is controlled by the position of the 
system switch on the room thermostat. Once the system switch is placed in either the 

HEAT 

or 

COOL 

position, unit operation is automatic. The optional automatic changeover thermostat, when 

in the 

AUTO 

position, automatically changes to heat or cool with sufficient room temperature 

change.

Evaporator Fan (Indoor Supply Air)

The evaporator fan is controlled by an 

ON/AUTO 

switch on the room thermostat. With the switch 

positioned at 

AUTO 

and the system operating in the cooling mode, fan operation coincides with 

the cooling run cycles. If the system is equipped with heat and is operating in the heating mode 
while the fan switch is at 

AUTO

, fan operation coincides with the heating run cycles. When the fan 

switch is positioned at 

ON, 

fan operation is continuous.

Cooling Mode

With the disconnect switch in the 

ON 

position, current is supplied to the compressor sump 

heater(s), phase monitor and control transformer. The sump heater(s) supplies heat to the 
compressor(s) during the 

“Off” 

cycle. The phase monitor looks at the incoming power to verify 

that there is no reversed phase, no phase imbalance, and no loss of phase. If the phase monitor 
detects any of these three conditions, it will shut off control voltage. The transformer steps down 
the line voltage to 24V for the low voltage control circuit. When the room thermostat system switch 
is positioned at 

COOL 

and the fan switch is at 

AUTO

, the compressor contactor energizes on a call 

for cooling. When the contacts of the compressor contactor close, operation of the compressor and 
condenser fan begins. The evaporator fan contactor also energizes on a call for cooling and initiates 
evaporator fan operation.

On units with dual circuits, the second stage of cooling is initiated as a result of the 2-stage 
thermostat calling for additional cooling.

ReliaTel™ Controls 

The ReliaTel™ Controls is a microelectronic control feature, which provides operating functions 
that are significantly different than conventional Electromechanical units. The ReliaTel™ 
Refrigeration Module 

(RTRM)

 uses Proportional/Integral control algorithms to perform specific 

unit functions that govern the unit operation in response to application conditions.

The RTRM provides compressor anti-short cycle timing functions through minimum 

“Off”

 and 

“On”

 timing to increase reliability, performance and to maximize unit efficiency. Upon power 

initialization, the RTRM performs self-diagnostic checks to ensure that all internal controls are 
functioning. It checks the configuration parameters against the components connected to the 
system. The system LED located on the RTRM module is turned 

“On”

 within one second after 

power-up if all internal operations are okay.

Summary of Contents for TTA120D300AA

Page 1: ...0TAA TTA120DK0TAA TTA120D3HTAA TTA120DKHTAA TTA120D30UAA TTA120DK0UAA TTA120D3HUAA TTA120DKHUAA TTA120D30WAA TTA120DK0WAA TTA120D3HWAA TTA120DKHWAA TTA120D400AA TTA120DW00AA TTA120D4H0AA TTA120DWH0AA...

Page 2: ...y All technicians who handle refrigerants must be certified The Federal Clean Air Act Section 608 sets forth the requirements for handling reclaiming recovering and recycling of certain refrigerants a...

Page 3: ...ken ALWAYS refer to appropriate MSDS and OSHA guidelines for proper PPE When working with or around hazardous chemicals ALWAYS refer to appropriate MSDS and OSHA guidelines for information on allowabl...

Page 4: ...A TTA120D Rubber Isolator Kit BAYISLT023A TTA120D Steel Spring Isolator Kit Low Ambient BAYLOAMU02A TTA120D On Off Fan Control Mounted in Unit Control Box large cabinets BAYLOAM333A TTA120D3 Modulatin...

Page 5: ...DOOR COIL INDOOR COIL INDOOR COIL SERVICE SERVICE VALVE VALVE SERVICE SERVICE VALVE VALVE EXPANSION EXPANSION VALVE BULB VALVE BULB EQUALIZER EQUALIZER TUBE TUBE NOTE A NOTE A NOTE A NOTE A NOTE A NOT...

Page 6: ...0 Tons Single Compressor TTA120D3 D4 DW DK Cooling Performance Gross Cooling Capacity Matched Air Handler 124 000 Condensing Unit Only 112 000 ARI Net Cooling Capacity 120 000 Efficiency Matched Air H...

Page 7: ...ming power to verify that there is no reversed phase no phase imbalance and no loss of phase If the phase monitor detects any of these three conditions it will shut off control voltage The transformer...

Page 8: ...lay coil approximately 1 second after energizing the compressor contactor coil in the cooling mode In the heating mode the RTRM energizes the evaporator fan relay coil approximately 1 second before en...

Page 9: ...000 1050 1100 1150 13 18 24 29 35 41 46 52 Ambient DB Degree C S uction Pres s ure kPa 20 14 DB WB 23 17 DB WB 27 19 DB WB 30 22 DB WB Discharge Pressure at 400 CFM Ton 200 250 300 350 400 450 500 550...

Page 10: ...TTA120D TTA120D Charging Curve 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 650 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 Liquid Temperature Leaving OD...

Page 11: ...UNDERCHARGE REFRIGERANT OVERCHARGE EXCESSIVE EVAP LOAD NONCONDENSABLES RESTRICTED O D AIRFLOW O D AIR RECIRCULATION TXV STUCK OPEN SUPERHEAT RESTRICTED I D AIRFLOW REF CIRCUIT RESTRICTIONS REFRIGERAN...

Reviews: