Binary outputs for 2-heat/2-cool applications
CNT-SVX12C-EN
13
Binary outputs for 2-heat/2-cool
applications
This configuration supports rooftop units and split systems applications
that have the following components:
•
Economizer
•
Supply fan
•
Cool 1
•
Cool 2
•
Heat 1
•
Heat 2
•
Exhaust
The Tracer ZN517 controller has eight binary outputs. Each binary out-
put is a relay with a rating of 12 VA. Table 5 describes the function of
each output for 2-heat/2-cool applications.
Binary output 5
Use the Rover service tool to configure binary output 5 (5NO/5COM/5NC)
in one of the following ways. It is the only output that can be configured
as a generic binary output.
•
Not used.
•
Exhaust fan: Will energize when the economizer outside air damper
position is greater than the user-defined control point.
•
Occupancy: Will energize when the Tracer ZN517 is in the occupied
mode.
•
Generic: Can be monitored only by a BAS and has no direct effect on
Tracer ZN517 operation.
Table 5. Binary outputs for 2-heat/2-cool applications
Binary output terminal label
Function
OPN
Economizer, drive open
CLS
Economizer, drive closed
G
Supply fan
1 (Y1)
Cool stage 1
2 (Y2)
Cool stage 2
3 (W1)
Heat stage 1
4 (W2)
Heat stage 2
5NO/5COM/5NC (binary output 5)
Exhaust fan/occupancy/generic
Summary of Contents for Tracer ZN517
Page 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Page 2: ......
Page 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Page 4: ......
Page 12: ...Table of contents vi CNT SVX12C EN...
Page 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Page 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Page 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Page 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Page 110: ...Index 98 CNT SVX12C EN...