28
CNT-SVX08F-EN
Sequence of Operations for Generic Mode
Sequence of Operations for Generic Mode
Configuring the MP501 in generic mode will control a variety of applications. The MP501 controls
a process based on an input that is one of the following:
•
Temperature
•
Percent
•
Pressure
•
Flow
•
Parts per million (ppm)
Note:
The generic mode applications do not follow a LonMark profile.
Power-up Sequence
When 24 Vac power is initially applied to the MP501, the following sequence occurs:
10. The Status LED goes on.
11. All the outputs are turned off.
12. The controller reads all the inputs to determine their initial values.
13. A user-adjustable (power-up control wait) delay timer begins. If set to less than 10 seconds, a
10-second wait will be applied.
14. The Status LED goes off.
15. The delay timer expires.
16. The Status LED goes on.
17. If a hardwired input (4–20 mA) is not detected and no value has been communicated, the
actuator output is overridden to closed and generates a
Process Input Failure
diagnostic.
18. Normal operation begins if no diagnostics have been generated.
Loop Enable/Disable
The proportional, integral, derivative (PID) control loop in the controller can be enabled by either
the binary input (BI1) on the board or by a communicated signal. The communicated signal has
priority over the hardware input. The PID loop is enabled if the communicated signal is invalid and
nothing is connected to the hardware input (refer to
).
Table 6.
Loop enable summary
Communicated Signal
(nviLoopEnable)
Hardware Input (BI1)
The PID Loop Is…
Enable
Does not matter
Enabled
Disable
Does not matter
Disabled
Not valid
Enable
Enabled
Not valid
Disable
Disabled
Not valid
Invalid
Enabled
If the PID loop is enabled, the controller compares the input to its setpoint and calculates an output
between 0% and 100%. The controller takes that PID output value and controls the outputs
appropriately. If the PID loop is disabled, the outputs go to predefined positions. Refer to the
section,