background image

5

 3270 3403 D

Frame-mounted Tracer™ AH541 Controller

Figure 3.

Installing the main circuit boards

G

BO5

BO4

BO3

BO2

BO1

BO6

24VAC

AO4

AO3

AO6

AO5

AO2

IN3

IN2

IN1

AO1

IN6

IN7

IN5

IN11
IN12

IN10

IN9

IN8

IN4

BO1

BO3

BO5

BO2

BO4

BO6

SER

VICE

COMM

FA

N

EX

FA

N

TEST

ST

AT

US

BO5

BO4

BO3

BO2

BO1

BO6

24VAC

AO4

AO3

AO6

AO5

AO2

IN3

IN2

IN1

AO1

IN6

IN7

IN5

IN11
IN12

IN10

IN9

IN8

IN4

BO1

BO3

BO5

BO2

BO4

BO6

SER

VICE

COMM

FA

N

EX

FA

N

TEST

ST

AT

US

H

I

1.

Hold the top frame 

(A)

 at a 90° angle to the bottom frame 

(B)

.

2. Connect the 60-pin cable 

(C)

 to the 60-pin cable ejector slot 

(D)

 by pressing down firmly on the cable until the ejector 

tabs collapse and snap over the ends of the cable. Then, connect the 20-pin cable 

(E)

 to the 20-pin slot 

(F)

.

3. Align the snaps on the top frame 

(G)

 with the mounting locks on the bottom frame and then push the two frames 

together in the direction indicated by the arrows. 

Note:

You will hear a click when the frames connect. For controllers with an operator display, connect the operator-
display cable to the circuit board.

4. Install the supplied grounding screw (6-32 x 2 inch, thread-rolling screws) into the assembly and turn it into the 

sheet metal backing.

Grounding
screw

Important:

The 60-pin cable ejector is designed to eject the 60-pin cable when disconnecting (refer to the lower right inset above).

B

A

C

D

E

F

Ensure that the slot keys are 
aligned when connecting the 
60-pin cable to the 60-pin 
cable ejector.

Grounding screw

5. Locate the 24 Vac power 

connector on the termination 
board. Remove the mating plug 
with screw terminals.

6. Attach the 24 Vac power-supply 

cable to the screw terminals on 
the mating plug.

7.

Connect the 24 Vac power cable to 
the termination board 

(H)

. The 

green status LED will light 

(I)

.

Summary of Contents for Tracer AH541

Page 1: ...ed by the manufacturer Failure to do so may result in equipment damage Warnings Cautions and Notices Warnings cautions and notices are provided in appropriate places throughout this document WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or ...

Page 2: ...ion below 24 Vac dedicated power supply Compliance with National Electrical Code NEC and applicable local electrical codes for high voltage power wiring to the enclosure Figure 1 Minimum clearances Table 1 Specifications Temperature From 40 F to 158 F 40 C to 70 C Humidity 5 95 non condensing Power requirements 21 27 Vac 24 Vac nominal Altitude 6500 ft 2000 m Installation Category 3 Pollution Degr...

Page 3: ...late mark the location of the four mounting holes and the grounding screw on the mounting surface 3 Set aside the controller and then drill holes for 8 4 mm screws at the marked locations 4 Drill a 1 8 inch diameter pilot hole for the supplied grounding screw 5 Secure the controller to the mounting surface with the enclosed using 8 4 mm screws not supplied in the mounting holes Figure 2 Dimensions...

Page 4: ...e installed The board can be kept in the office and programmed while the enclosure is mounted and wired After programming has been completed connect the circuit board to the termination board To begin verify that the 24 Vac power cable is not connected to the termination board and then install the main circuit board as shown in Figure 3 p 5 ...

Page 5: ...th the mounting locks on the bottom frame and then push the two frames together in the direction indicated by the arrows Note You will hear a click when the frames connect For controllers with an operator display connect the operator display cable to the circuit board 4 Install the supplied grounding screw 6 32 x 2 inch thread rolling screws into the assembly and turn it into the sheet metal backi...

Page 6: ...ul MN 55110 USA Product name Tracer AH541modular configurable controller Model numbers BMTA000BAB00 BMTA000BAB01 BMTA000CAB00 Electromagnetic emission by Council directive 89 336 EEC EN61000 6 4 2001 Radiated EN61000 3 2 Conducted EN61000 3 3 Amendment A14 2000 1995 Class B limit 1995 Class B limit Electromagnetic immunity by Council directive 89 336 EEC EN61000 6 2 1999 IEC 1000 4 2 1995 EN61000 ...