Frame-mounted Tracer™ AH541 Controller

Order Numbers: BMTA000CAB00

The frame-mounted Tracer AH541 controllers can be used to replace controllers in existing equipment or mounted in new 
equipment or custom enclosures.

NOTICE

Avoid Equipment Damage!

Install and use the controllers as specified by the manufacturer. Failure to do so may result in equipment damage.

Warnings, Cautions, and Notices

Warnings, cautions, and notices are provided in appropriate places throughout this document:

 

WARNING:

 Indicates a potentially hazardous situation which, if not avoided, could result in death or serious 

injury.

CAUTION:

 Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate 

injury. It may also be used to alert against unsafe practices.

NOTICE

:

 Indicates a situation that may result in equipment or property-damage only accidents.

Summary of Contents for Tracer AH541

Page 1: ...ed by the manufacturer Failure to do so may result in equipment damage Warnings Cautions and Notices Warnings cautions and notices are provided in appropriate places throughout this document WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or ...

Page 2: ...ion below 24 Vac dedicated power supply Compliance with National Electrical Code NEC and applicable local electrical codes for high voltage power wiring to the enclosure Figure 1 Minimum clearances Table 1 Specifications Temperature From 40 F to 158 F 40 C to 70 C Humidity 5 95 non condensing Power requirements 21 27 Vac 24 Vac nominal Altitude 6500 ft 2000 m Installation Category 3 Pollution Degr...

Page 3: ...late mark the location of the four mounting holes and the grounding screw on the mounting surface 3 Set aside the controller and then drill holes for 8 4 mm screws at the marked locations 4 Drill a 1 8 inch diameter pilot hole for the supplied grounding screw 5 Secure the controller to the mounting surface with the enclosed using 8 4 mm screws not supplied in the mounting holes Figure 2 Dimensions...

Page 4: ...e installed The board can be kept in the office and programmed while the enclosure is mounted and wired After programming has been completed connect the circuit board to the termination board To begin verify that the 24 Vac power cable is not connected to the termination board and then install the main circuit board as shown in Figure 3 p 5 ...

Page 5: ...th the mounting locks on the bottom frame and then push the two frames together in the direction indicated by the arrows Note You will hear a click when the frames connect For controllers with an operator display connect the operator display cable to the circuit board 4 Install the supplied grounding screw 6 32 x 2 inch thread rolling screws into the assembly and turn it into the sheet metal backi...

Page 6: ...ul MN 55110 USA Product name Tracer AH541modular configurable controller Model numbers BMTA000BAB00 BMTA000BAB01 BMTA000CAB00 Electromagnetic emission by Council directive 89 336 EEC EN61000 6 4 2001 Radiated EN61000 3 2 Conducted EN61000 3 3 Amendment A14 2000 1995 Class B limit 1995 Class B limit Electromagnetic immunity by Council directive 89 336 EEC EN61000 6 2 1999 IEC 1000 4 2 1995 EN61000 ...