62
SPR and CPR Adjustment Procedures
IMPORTANT: The following applicable procedures must be performed on all new unit installations.
Failure to do so may not allow the unit to operate at its maximum capacity.
NOTE: The following procedures are for initial settings. Sometimes
conditions such as high or low ambient temperatures may require that
the settings be fine-tuned for optimum performance.
Suction Pressure Regulator Valve
(Model 20 and 50 Only)
Model 20 and 50 units are equipped with a suction pressure regulator
(SPR) valve. The valve is used to limit the load on the standby compressor.
This also affects the current draw of the electric motor. Monitor the current
drawn of the electric motor when making this adjustment and keep it at
least 1.5 amps below the overload relay setting. Refer to the Maintenance
Manual for overload relay settings.
1. Install a gauge manifold set on the electric standby compressor. Attach
an additional compound gauge to the suction service port on the copper
tube directly before SPR valve (shown in illustration to monitor suction
pressure at the inlet to the suction pressure regulator.
2. Connect the unit power receptacle to an appropriate electric power
source.
3. Place a jumper wire between the 12 and CHB wires at the defrost
termination switch to ensure the unit will run in Defrost.
4. Start the unit and run it in Defrost on the electric standby compressor
until the pressure on the additional compound gauge attached to the
suction service port stabilizes at a pressure above 45 psig (310 kPa).
5. Check the suction pressure on the gauge attached to the suction service
port at the standby compressor. It should be 39.0 ± 4 psig (269 ± 28
kPa) for 230V 3 phase electric motor, and 24.0 ± 4 psig (165.5 ± 28
kPa) for 230V 1 phase electric motor. If the setting is incorrect, remove
the protective cap and adjust the suction pressure regulator valve to the
correct setting.
6. Remove the gauge manifold set, the additional compound gauge, and
the jumper wire when finished with the procedure.
Suction Pressure Regulator
Typical V-520 RT Refrigeration Module Components
Suction
Service Port
for Road
Compressor
Summary of Contents for Thermo King ES300
Page 12: ...11 Required Tools ...
Page 18: ...17 Dimensions Condenser Module Mounting Holes ...
Page 19: ...18 Dimensions HMI A 140 mm 5 50 in B 46 mm 1 80 in C 12 mm 50 in ...
Page 20: ...19 BLANK PAGE ...
Page 38: ...37 Important Suction Line Routing and P Trap Formation NOT ACCEPTABLE From Unit ...
Page 40: ...39 Installation Refrigeration Tubes to Compressor ...
Page 46: ...45 System Leak Check and Evacuation ...
Page 48: ...47 Installation Electrical Connections ...
Page 50: ...49 Electrical Connections Evaporator s ...
Page 52: ...51 Installation Standby Power Receptacle ...
Page 54: ...53 Installation Drain Hoses REMOTE Evaporator HOST Evaporator Defrost Heater Wires ...
Page 56: ...55 Installation HMI ...
Page 62: ...61 System Charging AMOUNT OF REFRIGERANT PER MODEL Model 50 5 00 lbs ...