Important - Suction Line Routing and P-Trap Formation
Best Practices That Must Be Followed (Refer to the illustration on following page)
1. All hose bends must maintain at least minimum bend radii with no kinks. See “Minimum Bend Radii” on page 35.
2. Suction line should have a slight (if possible) downhill angle from the unit towards the compressor. Horizontal angle is acceptable - uphill angle is not.
3. Hoses should be secured adequately to prevent rubbing or chafing against hot, sharp or moving components.
4. P-Trap to be formed immediately before vertical run upwards to compressor while maintaining minimum bend radius with no kinks. It should be a
minimum of 2” below the lowest point of the horizontal run hose as shown.
5. After vertical run, the suction line must be horizontal or downwards to the compressor and cannot have any sag or droop.
Summary of Contents for Thermo King ES300
Page 12: ...11 Required Tools ...
Page 18: ...17 Dimensions Condenser Module Mounting Holes ...
Page 19: ...18 Dimensions HMI A 140 mm 5 50 in B 46 mm 1 80 in C 12 mm 50 in ...
Page 20: ...19 BLANK PAGE ...
Page 38: ...37 Important Suction Line Routing and P Trap Formation NOT ACCEPTABLE From Unit ...
Page 40: ...39 Installation Refrigeration Tubes to Compressor ...
Page 46: ...45 System Leak Check and Evacuation ...
Page 48: ...47 Installation Electrical Connections ...
Page 50: ...49 Electrical Connections Evaporator s ...
Page 52: ...51 Installation Standby Power Receptacle ...
Page 54: ...53 Installation Drain Hoses REMOTE Evaporator HOST Evaporator Defrost Heater Wires ...
Page 56: ...55 Installation HMI ...
Page 62: ...61 System Charging AMOUNT OF REFRIGERANT PER MODEL Model 50 5 00 lbs ...