35
Fabricating Refrigeration Hoses
NOTE: Thermo King recommends adherence to all guidelines, including
EPA guidelines concerning the service of refrigerant systems.
Minimum Bend Radii
CAUTION: TK 2000 Speedy Clip System components should not
be reused. Failure to follow these instructions and/or the use of
TK 2000 Speedy Clip System hose with fittings supplied by other
manufactures could result in sudden or unintended escape of
refrigerant gases. Personal injury and/or violations of EPA
regulations may occur as a consequence.
Improperly Installed Clip
Properly Installed Clip
All hoses must be routed as to maintain the
minimum bend radii given in the table below.
Hose
Size
Minimum
Bend
Radius
#6
2.00 in.
#8
2.50 in.
#10
3.00 in.
#12
4.00 in.
#16
7.00 in.