background image

Installer’s Guide

XR401

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

TCONT401AN21MA
2 Heat (Gas, Oil* or Elec) / 1 Cool / Heat Pump

(Factory set for 2H/1C gas applications)

Electronic Non-Programmable
3 - 9  Wire Hookup (2 for outdoor sensor)

Fan

Mode

Filter/OD

$

Introduction

TCONT401AN21MA

  

is a digital non-programmable 2Heat/1

Cool/Heat Pump/Heat-Cool wall mounted low voltage
(24VAC) Comfort Control with backlit LCD and keypad. It
maintains room temperature by controlling the operation of
heating, cooling and heat pump systems. The Comfort
Control is easily configured for heat pump or cooling only and
gas or electric  heat applications via the user friendly In-
staller Setup menu. The Comfort Control features include
separate heating and cooling setpoints, selectable auto or
manual changeover, adjustable energy saving mode, adjust-
able filter reminder, outdoor temperature sensing, LitePort
technology for extended system diagnostics and fault notifica-
tion. Setup selections and diagnostics are stored indefinitely
in the Comfort Controls nonvolatile memory eliminating the
need for battery backup.

Safety Considerations

Read the following manufacturer instructions carefully.
Follow all local codes during installation. All wiring must
conform to local and national electrical codes. Improper
wiring or installation may damage comfort control.
Recognize safety information. This is the safety alert symbol

!

. When you see this symbol on the equipment and in the

instruction manual, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING and
CAUTION. These words are used with the safety-alert
symbol. DANGER identifies the most serious hazards which

will 

result in severe personal injury or death. WARNING

signifies a hazard which 

could 

result in personal injury or

death. CAUTION is used to identify unsafe practices which

could

 result in minor personal injury or product and prop-

erty damage.

Note: Read the entire instruction manual before starting the
installation.

Application

FIG

Heat Pump or A/C
1 Stage Heat Pump**, 1 Stage Aux Heat.

Fig. 5

1 Stage Heat Pump**, 0 Stage Aux Heat.

Fig. 5

1 Stage Cool, 2 Stage Heat (Gas, Electric or Oil*).

Fig. 3

1 Stage Cool, 1 Stage Heat (Gas, Electric or Oil*).

Fig. 4

1 Stage Cool, 0 Stage Heat.

Fig. 4

0 Stage Cool, 2 Stage Heat (Gas, Electric or Oil*).

Fig. 3

0 Stage Cool, 1 Stage Heat (Gas, Electric or Oil*).

Fig. 4

* Requires external relay for oil furnace applications.

** External TAYPLUS103A required for dual fuel applica-
tions.

BAYSEN01ATEMPA required for outdoor temperature
sensing and display

SYSTEM MODE: Heat, Cool, Auto, Emergency Heat and Off

FAN MODE: Auto or On

Product Specifications

- Power Source: 20-30VAC, Class II, 50/60Hz.
- Cooling setpoint temperature range:  65F - 90F,

18.0C - 33.0C, 1F and 0.5C resolution.

- Heating setpoint temperature range:  40F- 85F,

5.0C - 30.0C, 1F and 0.5C resolution.

- Default set points:  68F, 20.0C Heat, 78F, 25.5C Cool
- Storage Range:  -40F to 140F, 5% - 90% RH non-

condensing.

- Operating Temperature range:  32F - 110F, 5 - 90% RH

non-condensing.

- Outdoor Temperature Display Range: -40F - 140F.

- Minimum Cycle Off Time Delay: Cooling - 5 minutes,

Heating - 1 minute.

- Use minimum 18 gauge NEC approved control

wiring.

Contents

Introduction ........................................................................ 1
Application .......................................................................... 1
Product Specifications ...................................................... 1
Installation .......................................................................... 2
Mounting and Wiring .......................................................... 2
SETUP ................................................................................. 3
Checkout ............................................................................. 4
Troubleshooting ................................................................. 6
Features .............................................................................. 7

18-HD29D2-4

Summary of Contents for TCONT401AN21MA Comfort Control

Page 1: ...e signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING sign...

Page 2: ...thermostat is being replaced a Remove existing thermostat from wall b Disconnect wires from existing thermostat one at a time Be careful not to allow wires to fall back into the wall c As each wire i...

Page 3: ...RT CONTROL TERMINAL BLOCK SINGLE STAGE OIL FURNACE SINGLE STAGE COOLING SINGLE STAGE AIR CONDITIONER FAN SOV COOLING HEATING 1st HEATING 2nd W2 X2 O SINGLE STAGE OIL FURNACE B C OD TEMP T R1 R1 Figure...

Page 4: ...STANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR 15 138 9 35 30 0 80 9 3 10 117 7 40 26 1 85 8 3 5 99 9 45 22 7 90 7 3 0 85 1 50 19 9 95 6 5 5 72 7 55 17 4 100 5 8 10 62...

Page 5: ...ee increments 50 Compressor Cooling Cycle Minimum On Time Minutes 3 2 4 CPH 1 15 Minutes 5 CPH 1 7 Minutes 6 CPH 1 5 Minutes 20 Exit User Setup Press Mode SA CA Cancel SA Save US Default User Settings...

Page 6: ...enough to prevent overshooting Set Control Response rate to Fast Step 33 Heating will not come on 1 System Mode not set to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or...

Page 7: ...n easily be determined by simply pressing the Filter OD keypad button once more Pressing and holding the Filter OD keypad button provides quick access to the filter timer value Keypad Lock Locking the...

Page 8: ...hich will be added to actual temperature The number can range between 5 and 5 degrees in 1 2 degree increments Factory default is 0 This adjusted value will be used and displayed as actual temperature...

Reviews: