MULTISTAGE ELECTRONIC THERMOSTAT

Pub. No. 18-HD28D1-1

TROUBLESHOOTING GUIDE

Available on select models.

(continued)

Symptom

Possible Cause

Action

Display does not
come on.

Thermostat is not being
powered.

Check that B terminal is connected to the system
transformer.

Check for 24 Vac between B and R terminals.

If missing 24 Vac:

Check if the circuit breaker is tripped—reset the
circuit breaker.

Check if the system fuse is blown—replace the fuse.   

Check if the power switch on the HVAC equipment is
in the Off position—set to the On position.

Check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Temperature
display is incorrect.

Room temperature display was
reconfigured.

Enter Installer Setup Number 37 and reconfigure the display.

Thermostat is configured for 

°

F

or 

°

C display.

a

Enter Installer Setup Number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Temperature
settings will not
change. (Example:
Cannot set the   

The upper or lower temperature
limits were reached.   

Check the temperature setpoints:

Heating limits are 55 to 85

°

F (13 to 29

°

C)

Cooling limits are 65 to 99

°

F (18 to 37

°

C).

heating higher or
the cooling lower.)

The setpoint temperature range
stops were configured.

Check Installer Setup mode numbers 34 and 35 and
reconfigure the setpoint stops.

Heating does not
come on.

No power to the thermostat.

Check that B terminal is connected to the system
transformer.

Check for 24 Vac between B and R terminals.

If missing 24 Vac:

Check if the circuit breaker is tripped—reset the
circuit breaker.

Check if the system fuse is blown—replace the fuse.   

Check if the system switch at the equipment is in the
Off position—set to the On position.

Check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Heating does not
come on.

Thermostat minimum off time is
activated.

Wait up to five minutes for the system to respond.

System selection is not set to
Heat.

Set system selection to Heat.

Heating setpoint is below room
temperature.

Check heating setpoint. Set heating setpoint to desired
temperature.

Summary of Contents for TAYSTAT 375

Page 1: ...e product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTIO...

Page 2: ...the mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 for typical hookups A letter code is located near each terminal for identification CAUTION E...

Page 3: ...NFORMATION KEY i DECREASE TEMPERATURE SETTING INCREASE TEMPERATURE SETTING Fig 6 Thermostat key locations and descriptions SETTINGS System and Fan Settings System settings control the thermostat opera...

Page 4: ...ded off periods by providing air circulation to prevent stagnation and improved moisture removal due to increased run time Cooling Droop is most effective in mild weather conditions and during nightti...

Page 5: ...e 2 cooling cycle rate 10 03 3 3 cph recommended 2 or 5 cph not recommended 02 or 05 02 2 cph 05 5 cph System setting adjustment 12 00 Automatic changeover 01 or 02 01 Manual changeover 02 Auto Only D...

Page 6: ...4 85 Highest heating sepoint setting 55 to 85 Temperature range 1 F increments of heating stpoint setting Temperature range stops in cooling 35 65 Lowest cooling sepoint setting 65 to 99 Temperature r...

Page 7: ...cool turns off 30 Stage one cool and system fan turn off Fan Equipment System Test i 40 Change from cooling to fan equipment system test 41 Fan comes on 40 Fan turns off Key Operation System Test IMP...

Page 8: ...here Applicable Allow the outdoor temperature sensor to absorb the outdoor air for a minimum of five minutes before taking a reading With an accurate thermometer 1 F 0 5 C measure the temperature at t...

Page 9: ...ings will not change Example Cannot set the The upper or lower temperature limits were reached Check the temperature setpoints Heating limits are 55 to 85 F 13 to 29 C Cooling limits are 65 to 99 F 18...

Page 10: ...e room temperature Check cooling setpoint Set cooling setpoint to desired temperature Heating or cooling comes on momentarily and shuts off Heat or cool circuit is opening up or becoming high impedanc...

Page 11: ......

Page 12: ...Tyler TX 75711 9010 CUSTOMERASSISTANCE If after reading this guide you have any questions concerning the operation of your thermostat please call the Thermostat Customer Assistance Helpline at 1 877 8...

Reviews: