32
18-GJ89D1-1D-EN
7.
Secure the sheathed wiring to the control pocket mounting plate using the factory supplied wire ties attached to the tabs as shown.
Distribution
Board
AHC
View A
J8 24 Volt Input
S2 (future use)
J10
Electrical
HT
J7 Motor
J1 EEV
J3 Sensors
J2 CAN
Connector
J5 CAN Connector
J14 External Switches
and Humidifier
J15 24 volt low voltage harness
J11 Supply Air Temperature
Sensor (SAT)
LED
J13 Sensors
J13 BLE
Button
J12
(future use)
8.
Mount Supply Air Temperature Sensor
The Supply Air Temperature (SAT) Sensor must be mounted a
minimum of 8” above the edge of the supply duct (additional distance
is preferred when possible). Locate the SAT Sensor in an area of the
discharge air duct where less air turbulence is expected. Avoid dead
air areas where representative discharge air temperatures may not
exist.
The plug on the SAT Sensor harness plugs directly onto the AHC
Board. Refer to the figure in Step 7, Table 14.
Note:
Supply Air Temp Sensor (SAT) is only used in Link
Communicating mode.
Note:
Supply Air Temp Sensor (SAT) ships with SC360 System
Controller.
Supply Air
Temperature
Sensor
8” Min.