33
Dip Switch S2
•
Set the S2-1 and S2-2 dip switches for the
Cooling and Heating CFM/Ton.
S2
1
1
12
34
5
12
34
5
HP
2 (Compressor)
2 (Stages)
AC (System)
}
OUTDOOR
Capacity (Tons)
OUTDOOR
}
Torque
CFM/Ton
Cool Off Delay
}
INDOOR
CFM
+12V
R13
R14
R1
R4
1
U1
R NET 1
S1
on
on
S2
R NET 2
R
6
C2
2
C1
9
C
15
C
12
C1
8
C2
1
C10
D9
L1
R22
Airflow Control (AFC)
INDOOR
MODEL
S2
‐
1
S2
‐
2
COOLING
CFM/TON
HEATING
CFM/TON
OFF
OFF
400
430
OFF
ON
360
390
ON
OFF
380
410
ON
ON
420
450
OFF
OFF
400
430
OFF
ON
360
390
ON
OFF
380
410
ON
ON
420
450
OFF
OFF
370
420
OFF
ON
350
400
ON
OFF
390
440
ON
ON
410
450
OFF
OFF
370
400
OFF
ON
330
360
ON
OFF
350
380
ON
ON
390
420
OFF
OFF
350
400
OFF
ON
330
380
ON
OFF
370
420
TAM7A0C42H31SB
TAM7A0C48H41SB
TAM7A0A24H21SB
TAM7A0B30H21SB
TAM7A0C36H31SB
ON
ON
390
440
OFF
OFF
370
400
OFF
ON
380
410
ON
OFF
390
420
ON
ON
400
430
TAM7A0C60H51SB
TAM7B0C60H51SA