background image

Installation - Controls

SRV-SVX04C-EN

13 

c. Press 

ENTER

 again to edit the password. 

d. Once the last character has been located press 

ENTER

. Do not press any arrow.

e.

OK

 will display a dotted box. Press 

ENTER

 to accept, 

and the screen will return to make the selection without 
security restriction.

4. Run Time Meter

a. Press the 

Down Arrow

 once to navigate to this screen 

(

Figure 8

).

Figure 8.

Runtime meter

b. The Run Time Meter screen displays the amount of 

time in hours the equipment has been operating. There 
is an indication for DH displaying the amount of time 
dehumidification has been requested and operating. 
These values, shown in hours, may vary dependent on 
the configuration of the equipment.

5. Control Group Selection 1* 

a. Press 

F1 (PID)

 to navigate to this screen (

Figure 9

). 

b. The OP73 Display may prompt the operator for 

Username and Password

 (

Figure 10

). 

Enter

 this to 

proceed. See section 834 for information regarding 
Username and Password. The Control Group Selection 
1 screen displays the various system loops available on 
the equipment.

Table 7.

 System loops

Alarms

1.

Press 

F2 (ALM)

 to navigate to this screen (

Figure 9

). 

2.

The Alarm screen displays the 

Faults and Warnings

 the system encountered during operation. The triangle with exclamation 

point will indicate to the operator when an alarm condition exists. 

3.

Press the 

ACK

 button to clear the current alarm message without clearing the history.

Note:

The Alarm Screen displays and records information on triggered alarms. Each time an alarm is triggered, it is added to the Alarm History 
list 

Figure 10

, and the last alarm is displayed.

F4 Reset

1.

The operator must press the 

F4

 button to reset a fault in the PLC. This will clear all system faults and enable the equipment to 

be restarted by cycling the selector switch. 

2.

The selector switch may also be used as the system reset by turning it to the 

OFF

 position and return it to the 

AUTO

 or 

MANUAL

 

position.

3.

Press the 

acknowledge button (ACK)

 to clear the message and alarm symbol indication. 

4.

The system screen will display 

READY

 after a fault has been reset.

F1 CLEAR History

1.

The alarm history (see 

Figure 10

) can be viewed by pressing the 

Down Arrow 

first and both 

Up and Down Arrows

 to scroll the 

alarms stored. 

2.

To clear the alarm history, press 

F1

3.

Enter the 

Username and Password 

to clear the history.

Figure 9.

Alarm

Figure 10. Alarm history list

Summary of Contents for SRV-SVX04C-EN

Page 1: ...e equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Page 3: ...cal regulations Introduction SRV SVX04C EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without written permissio...

Page 4: ...uxiliary Dry Contacts Operational System States 9 Start up 9 Main Power Initialization Sequence 9 Normal Start up 9 Shutdown 9 Faults and Warnings 10 Alarm Indication 10 List of System and DH Warnings...

Page 5: ...ectrical power required The DHUs can be used in free blow or ducted applications Each unit has a single horizontal supply air connection single return air connection and is equipped with a post coolin...

Page 6: ...pm P ft Post Cool 4750 366 1 58 10 10 12 57 24 5 Table 3 Dimensions and weights Length Width Height Weight 15 ft 2 in 6 ft 2 in 6 ft 5 in 4175 lb Rigging DHUs are equipped with fork pockets on two sid...

Page 7: ...ess of 180 F Do not position unit where reactivation outlet air could come into contact with sensitive materials and cause equipment and property damage 3 Connect power cable from unit to the power so...

Page 8: ...lectrical cable Below is a list of electrical data for these units If additional information is needed contact Trane Rental Services Table 4 Electrical data RSDH5000 Fused Disconnect Yes Unit Power 46...

Page 9: ...evices such as capacitors before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized When necessary to work with live electrical components have a...

Page 10: ...ad go to the ALARM screen and press the F4 RESET key which resets the PLC To restart the system 1 Move the selector switch SS01 to the OFF position 2 Move the SS01 back to the AUTO or MANUAL position...

Page 11: ...ot opened once every 600 seconds a timer in PLC1 times out the system is faulted The system goes into the shutdown sequence See Normal shutdown sequence of operation p 9 and Auxiliary Dry Contacts Ope...

Page 12: ...e no faults and the interlocks are made RUNNING The DH is running and process control loops are running if enabled FAULTED The DH has faulted PURGING The DH is going through a shutdown sequence and is...

Page 13: ...LM to navigate to this screen Figure 9 2 The Alarm screen displays the Faults and Warnings the system encountered during operation The triangle with exclamation point will indicate to the operator whe...

Page 14: ...14 SRV SVX04C EN Fan Curve Figure 11 Fan curve...

Page 15: ...nently lubricated and require no maintenance The desiccant wheel is belt driven The drive belt should be examined periodically for wear and correct tension Each unit is provided with disposable filter...

Page 16: ...16 SRV SVX04C EN Wiring Diagrams Figure 12 Figure 13...

Page 17: ...Figure 14 Figure 15 Wiring Diagrams SRV SVX04C EN 17...

Page 18: ...Figure 16 Figure 17 Wiring Diagrams 18 SRV SVX04C EN...

Page 19: ...Figure 18 Figure 19 Wiring Diagrams SRV SVX04C EN 19...

Page 20: ...Figure 20 Figure 21 Wiring Diagrams 20 SRV SVX04C EN...

Page 21: ...Notes SRV SVX04C EN 21...

Page 22: ...Notes 22 SRV SVX04C EN...

Page 23: ...Notes SRV SVX04C EN 23...

Page 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: