Freeze Protection

 

Depending on the ambient temperature the unit may be 
exposed to freeze, there are multiple options for freeze 
protection. They are listed in order of highest ambient 
(least freeze protection) to the lowest ambient (most 
freeze protection).

For all chiller running with water under cold ambient 
temperature (below 0°C), it is extremely important to 
keep full water fl ow in the evaporator for an extended 
time after last compressor stops. This will protect 
evaporator tube from freezing by refrigerant migration. 
This is why evaporator water pump output relay must 
be used to control the chilled water pump. This is not 
mandatory if glycol is used with protection down to 
lowest ambient expected.

1. Water pump and heaters

a. Heaters are factory installed on water boxes and 

evaporator shell. They will protect it from freezing 
in ambient temperatures down to -20°C.Heaters are 
installed on the water piping and on the pumps of 
units equipped with hydraulic module. 

b. Install heat tape on all water piping, pumps, and other 

components that may be damaged if exposed to 
freezing temperatures. Heat tape must be designed 
for low ambient temperature applications. Heat tape 
selection should be based on the lowest expected 
ambient temperature. 

c. Tracer™ UC800 controller can start the pump(s) when 

freezing conditions are detected. For this option the 
pumps must be controlled by the RTAF unit and this 
function validated on the chiller controller. 

d. Water circuit valves need to stay open at all times.

Note: 

Water pump control and heater combination will 

protect the evaporator down to any ambient temperature 
provided power is available to the pump and the UC800 
controller. This option will NOT protect the evaporator 
in the event of power failure to the chiller unless backup 
power is supplied to the necessary components.

Note: 

When no chiller operation is possible and the pump 

is already off, UC800 pump control function for freeze 
protection will command the pump to turn on:

• ON if the average of the evaporator entering water 
temperature, evaporator leaving temperature, and the 
evaporator refrigerant pool temperature is less than 
Low Evaporator Refrigerant Temperature Cutout (LERTC) 
+ 2.2°C for a period of time

• OFF again if the evaporator refrigerant pool temperature 
rise above LERTC + 3.3°C for a period of time

Note: 

The period of time referenced for ON and OFF 

conditions above described is dependent on past running 
conditions and present temperature measured. 

• ON if entering OR leaving water temperature < LWTC 
for 16.2°C-sec

• OFF again if water temperature > LWTC for 30 min

OR

2. Freeze inhibitor 

a. Freeze protection can be accomplished by adding 

suffi cient glycol to protect against freezing down to the 
lowest ambient expected.

b. See “evaporator glycol requirement” section for 

guidance on determining the glycol concentration.

Note: 

Use of glycol type antifreeze reduces the cooling 

capacity of the unit and must be considered in the design 
of the system specifi cations.

OR

3. Drain water circuit 

For ambient temperatures below -20°C and for those 
installation not including either option 1 or 2 above 
described
a. Shut off power supply to unit and to all heaters.
b. Purge the water circuit
c. Blow out the evaporator to ensure that no liquid is left 

inside the evaporator and the water lines. Drain the 
pump.

CAUTION! Evaporator damage!

If insuffi cient concentration or no glycol is used, the 
evaporator water pumps must be controlled by the 
UC800 to avoid severe damage to the evaporator due 
to freezing. A power loss of 15 minutes during freezing 
can damage the evaporator. It is the responsibility of the 
installing contractor and/or the customer to ensure that a 
pump will start when called upon by the chiller controls.
Please consult the table named “Recommended Low 
Evaporator Refrigerant Cutout (LRTC) and % Glycol for 
RTAF chillers”.
With factory-fi tted disconnect switch option, evaporator 
trace heating is taken from the live side of the isolator. 
As a consequence, the heaters are energized as long as 
the main switch is closed. Supply voltage to the heating 
tapes is 400V.
Avoid the use of very low or near minimum chilled fl uid 
fl ow rates through the chiller. Higher velocity chilled fl uid 
fl ow reduces freeze risk in all situations.
 Flow rates belowpublished limits have increased 
freeze potential and have not been considered by freeze 
protection algorithms.
•  Avoid applications and situations that result in a 

requirement for rapid cycling or repeated starting and 
stopping of the chiller. Keep in mind that chiller control 
algorithms may prevent a rapid compressor restart 
after shutting down when the evaporator has been 
operating near or below the LERTC limit.

•  

Maintain refrigerant charge at appropriate levels. If 
charge is in question, contactTrane service. A reduced 
or low level of charge can increase the likelihood of 
freezing conditions in the evaporator and/or LERTC 
diagnostic shutdowns.

The warranty will be void, in case of freezing due to the 
lack of use of either of these protections.

Evaporator Waterside

Summary of Contents for Sintesis RTAF HE

Page 1: ...kW July 2020 Confidential and proprietary Trane information Original instructions Sintesis chillers are part of theTraneTechnologies EcoWise portfolio of products that are designed to lower their envi...

Page 2: ...er to the general sales conditions of your localTRANE sales office Note Unit inspection in France Delay to send registered letter in case of visible and concealed damage is only 72 hours Loose Parts I...

Page 3: ...e shipment Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur after delivery Noti...

Page 4: ...n relays and wiring Water piping Flow switch Taps for thermometers and gauges Thermometers Water flow pressure gauges Isolation and balancing valves in water piping Vents and drain Waterside pressure...

Page 5: ...sonal Short XSS Digit 13 Agency listing C CE Marking Digit 14 Pressure vessel code 2 PED Pressure equipment directive D Australian code Digit 15 Acoustic level X Standard noise SN L Low noise LN A AC...

Page 6: ...stant delta P T Variable Speed Pump Constant deltaT Digit 38 Open for future use X Digit 39 Open for future use X Digit 40 Power socket X None P Included 230V 100W Digit 41 Factory tests X No final pe...

Page 7: ...ssor nameplate is located on each compressor Unit Nameplate The unit nameplate provides the following information Unit model and size description Unit serial number Identifies unit electrical requirem...

Page 8: ...ed for operation maintenance panel access and airflow NO OBSTRUCTIONS ABOVE UNIT 2 For installations with obstructions or multiple units refer toTrane office for Close Spacing and Restricted Airflow a...

Page 9: ...ting bolts at this time See the isolators submittals for isolators location maximum weights and isolators diagrams 2 Align the mounting holes in the base of the unit with the threaded positioning pins...

Page 10: ...l freeze To avoid free cooling coil damage If the building loop needs to be charged with water for testing purposes isolate free cooling coils by closing free cooling service shut off valve and modula...

Page 11: ...eliminators Shutoff isolation valves Thermometers if desired temperature readings available on chiller controller display Clean out tees Pipe strainer Pi Pressure gauge FT Water Flow Switch T1 Evapor...

Page 12: ...terbox prevents vacuum by removing air from evaporator for complete drainage Drain connections and vents are also provided on header pipes for use when free cooling option Evaporator configuration var...

Page 13: ...essure Relief Valves Install a water pressure relief valve in the evaporator inlet piping between evaporator and the inlet shutoff valve Water vessels with close coupled shutoff valves have high poten...

Page 14: ...valve Temperature sensor Note A pressure switch device to detect lack of water is not included in the pump package Installation of this type of device is highly recommended to avoid sealing damage due...

Page 15: ...conditions It may vary from 30 C to 61 C For details performance consult Order Write Up Flow switch The flow switch is fitted on water line to monitor a to low water flow through theTotal Heat Recover...

Page 16: ...e cooling will be enabled whenever the outdoor temperature is below the evaporator entering water temperature The operating logic is described below The free cooling system operates combined with the...

Page 17: ...ree Cooling Figure 8 Flow chart Free Cooling Direct free cooling version Note glycol free cooling chilled water setpoint should be in the range of 4 C 20 C Water Glycol mixture is filled on the free c...

Page 18: ...e Cooling offset is an adjustable parameter to make free cooling active If free cooling function is enabled free cooling becomes the 1st stage of cooling Free cooling is the first stage to engage for...

Page 19: ...the customer and installed at the unit inlet Unit is shipped without glycol content on the free cooling circuit Free cooling loop venting must be performed by using Manual override mode to run the fre...

Page 20: ...Direct Free Cooling option Glycol percentage should be based on freeze avoidance requirements The glycol solution requires an inhibitor package to be carefully chosen with the aid of a qualified water...

Page 21: ...during monthly maintenance operation when free cooling is continuously OFF to avoid possible glycol cristalization Pump Override function is located inTD7 via Button Settings Manual Control Settings...

Page 22: ...endent on past running conditions and present temperature measured ON if entering OR leaving water temperature LWTC for 16 2 C sec OFF again if water temperature LWTC for 30 min OR 2 Freeze inhibitor...

Page 23: ...see Adaptive Frequency Drive AFD3 Capacitor Discharge and BAS SVX19B E4 Hazardous Voltage Pressurized Burning Fluid Before removing compressor terminal box cover for servicing or servicing power side...

Page 24: ...mps Starting Amps of the largest compr RLA of 2nd compr RLA of all fans control Compressor Power factor Disconnect switch size A Short Circuit Rating for all sizes 35 kA For the control of every unit...

Page 25: ...Supply The evaporator shell is insulated from ambient air and protected from freezing for temperature down to 20 C by two thermostatically controlled immersion heaters combined with evaporator pumps a...

Page 26: ...Installer Supplied Components Alarm and Status Relay Outputs Programmable Relays See RTAF User Guide for alarm and status relay outputs EDLS and ECWS Analog Input Signal Wiring Details See RTAF User G...

Page 27: ...e service valve 9 Liquid shut off valve 10 Filter drier 11 Electronic expansion valve 12 Sight glass 13 Relief valve 14 Service valve 15 Oil line solenoid valve 16 Oil filter 17 Suction service valve...

Page 28: ...ndensed inside the microchannel states 2b to 3b Refrigerant flow through the system is balanced by an electronic expansion valve states 3b to 4 Refrigerant Cycle with Economizer Liquid refrigerant eit...

Page 29: ...crochannel tubes and two refrigerant manifolds Coils can be cleaned with high pressure water see Condenser Coils MCHE maintenance for instructions The condenser coil has an integral subcooling circuit...

Page 30: ...s specific information you need on a day to day basis like setpoints limits diagnostic information and reports Day to day operational information is presented at the display Logically organized groups...

Page 31: ...air temperature based on wind speed lower than 2m s Maximum ambient operation is for unit at 12 C 7 C operating conditions It is not possible to have a unit operating low and high ambient For specifi...

Page 32: ...n 10 Reapply power to complete the procedures 11 Prove all Interlock and Interconnecting Wiring Interlock and External as described in the Electrical Installation section 12 Check and set as required...

Page 33: ...is will damage the shaft seal Always fill the system with diluted solution Maximum concentration of glycol is 45 for unit with pump package If the chiller is installed in a humid environment or a loca...

Page 34: ...user guide for instruction on settings CAUTION To prevent compressor damage do not operate the unit until all refrigerant valves and oil line service valves are opened IMPORTANT A clear sight glass a...

Page 35: ...that is stuck open A restriction in the line can sometimes be identified by a noticeable temperature differential between the two sides of the restriction Frost will often form on the line at this poi...

Page 36: ...ot contain glycol to prevent any risk of evaporator freeze up Refer to charts 1 and 2 Extended Shutdown Procedure The following procedure is to be followed if the system is to be taken out of service...

Page 37: ...llowing recommendedTrane operation maintenance and service procedures with specific attention to the following 1 Refrigerant used in any type of air conditioning or refrigerating equipment should be r...

Page 38: ...peration water fl ow to be within allowed operating range A fully loaded chiller is highly recommended for a successful operation In case the technician is not able to ensure a 2 circuit fully loaded...

Page 39: ...see general data table 9 Install the new filter element in the filter housing 10 Inspect the flange gasket and replace it with a new one if damaged 11 Install the flange and torque the bolts to 19 22...

Page 40: ...the need for oil charge 1 Some services procedures may result in loss of small quantities of oil that must be replaced oil analysis compressor filter replacement re tubing the evaporator and so forth...

Page 41: ...the required amount of oil into the unit Note the compressor filter has an internal shutoff valve that will prevent oil from entering the compressor while the compressor is not running Therefore there...

Page 42: ...a service valve on the suction line and on the evaporator Use these valves to vacuum the compressor 10 Open the oil line shutoff valve Sever damage to the compressor can result if the oil line shutof...

Page 43: ...ing remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized Failure to disconnect power before servicing could result in death...

Page 44: ...r must be cleaned and checked regularly Lubrication The pump shaft seal does not require any special maintenance Visual leakage check are however required Distinctly visible leakage will require an ex...

Page 45: ...1A Running Status Starts Running Time Hr min Oil Pressure kPa Compressor 1B Running Status Starts Running Time Hr min Oil Pressure kPa Motor 1A Active Demand Limit Setpoint Average Motor Current Perc...

Page 46: ...x x x x xxx 7 x x x x x xxx 8 x x x x x xxx 9 x x x x x xxx 10 x x x x x xxx x over 10 every year every year every year 2 x every year 3 every year every 3 years 40 000 h This timetable is applicable...

Page 47: ...e period designated The inspections will be conducted at agreed upon intervals andTrane Service First will submit a written report to the customer after each inspection These reports will indicate any...

Page 48: ...n please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice We are...

Reviews: