SXIH-SVX01C-EN
27
Maintenance
Maintenance Procedures
Before beginning any maintenance procedures heed all warnings and cautions.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Periodic Maintenance Checklist
–
Inspect coil surface for cleanliness. Clean as required. Refer to
under
“Maintenance Procedures,” p. 27
.
Annual Maintenance Checklist
–
Perform all monthly maintenance inspections.
–
Perform seasonal startup checks.
–
Leak test refrigerant circuits. Inspect contacts of fan motor contactors and relays. Replace
all worn contacts.
Table 11. Integral air-cooled general data
Nominal Tons
5
7.5
10
15
ARI capacity - btu/h
65,000
91,000
121,900
177,200
EER
11.20
10.36
10.38
9.76
Refrigerant type/circuit charge (lbs.)
R-410A/14.0 R-22/14.3
R-22/9.3 R-22/11.7
Shipping weight – lbs.
1087
1087
1495
1897
Operating weight – lbs.
1027
1027
1445
1767
Compressor, qty - hp
1
1 2 2
Circuits
1
1
2
2
Condenser
Face area, sq/ ft.
10.75
10.75
16.55 16.55
Rows / fpf
4/192
4/168
3/180
4/180
Fans, qty.
1
1
2
2
Fan size, in.
15x15
15x15
15x15
15x15
Motor hp
1.0
2.0 2.0 5.0
Evaporator
Face area, sq. ft
8.32 8.32 12.82
12.82
Rows / fpf
4/168
4/144
4/144
4/144
Filter qty. - size, in.
2- 23.7x25
2 - 23.7x25
3 - 23.7x25.6
3 - 23.7x25.6
Fans qty. - size, in
1- 12x12
1 - 12x12
2 - 12x12
2 - 12x12
Motor hp
1.0 1.5 2.0 3.0
Min. airflow
1800
2700
3600
5400
Max. airflow
2200
3300
4400
6600
Notes:
1.
Net cooling capacity is rated at 95°F ambient, 80°F entering dry bulb and 67°F entering wet bulb at scfm air condition.
2.
EER is rated at ARI conditions.