Trane RTHC-SVN02C-EN Installation Manual Download Page 9

RTHC-SVN02C-EN

9

Wiring

Wiring can be completed once all of the components are installed.

 

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing.  
Follow proper lockout/tagout procedures to ensure the power can not be 
inadvertently energized. Failure to disconnect power before servicing could 
result in death or serious injury.

Connecting Supply Voltage to the 4U1

The controller requires 24 VAC to operate. 

Note: If the module is factory installed, the power supply wiring will already be 
connected.

1.

To connect the power to the module, use four-lead conductor wire, (X1906-0094-
010).

2.

Connect the red lead to the J2-4 on the 1U2 starter module.

3.

Connect the black lead to the J2-3 on the 1U2 starter module.

4.

Connect the other end of red lead to ACC in the 4U1 controller.

5.

Connect the other end of the black lead to AC in the 4U1 controller.

NOTE: Conduit is not required. Four-lead conductor wire is to be used X1906-
0094-010. Trim the two additional wires.

Wiring the Pressure Transducers to the 4U1 Module

1.

The transducer ships from the supplier with a four-wire cable and a ground. Only 
2 wires and the ground will be used. Install a fork connector to the black lead, 
red lead and the ground. The white and green leads are not used and can be cut 
back out of the way.

2.

Prepare the wire leads for both transducers.

3.

Feed the leads through the lower bushing strain reliefs installed in the sheet 
metal box.

4.

Connect the black lead of the transducer installed on the condenser to S1 - 4U1.

5.

Connect the red lead of the transducer installed on the condenser to TX1 - 4U1.

6.

Connect the ground of the transducer installed on the condenser to GND - 4U1.

7.

Connect the black lead of the transducer installed on the evaporator to S2 - 4U1.

8.

Connect the red lead of the transducer installed on the evaporator to TX2 - 4U1.

9.

Connect the ground of the transducer installed on the evaporator to GND - 4U1.

Connect the 4U1 Output to the Water Valve

The wiring between the 4U1 controller and the water valve is customer supplied. It is 
class 2 wiring. It should not be run in conduit with higher voltage wire.

Important: 

To avoid erratic control of the valve, do not run the signal wire between 

the 4U1 controller and the water valve in conduit with voltages higher than 30 volts.

Summary of Contents for RTHC-SVN02C-EN

Page 1: ...o or greater than the evaporator leaving water temperature The system also must achieve a leaving condenser water temperature 25 F higher than the evaporator leaving water temperature within 2 minutes...

Page 2: ...ance Instructions for UL Approved Valves found on the internet at http www cranevalve com Water Valve Rating Confirm that the correct valve was shipped by referring to the Center Line nameplate attach...

Page 3: ...e certain the waterway is free of all debris 5 Almost close the valve prior to installing to avoid damage to the disc or seat of the valve Refer to Figure 1 6 The valve can be installed at any angle t...

Page 4: ...Size inches Bolt Length inches Required Torque ft lbs 6 200 8 3 4 10 2 25 100 8 200 8 3 4 10 2 25 100 6 300 12 3 4 10 2 1 2 25 100 8 300 12 7 8 9 2 3 4 50 200 NOTE Bolting and Torquing recommendations...

Page 5: ...e The actuator is intended for indoor use Special precautions must be taken if the actuator will be exposed to rainwater or direct sunlight Failure to adequately protect actuator may result in equipme...

Page 6: ...factory set to allow the valve to operate with the largest allowable number of steps If the valve appears to sluggish the sensitivity may need to be decreased CAUTION Equipment Damage Valve should be...

Page 7: ...If the controller is not factory installed use the procedure below to mount the controller Installation 1 Locate the factory mounted pressure differential switch for detecting low system differential...

Page 8: ...e service valve on the evaporator and condenser where the transducers will be installed 5 Install one of the transmitters to condenser service valve located on the top of the shell NOTE Install a schr...

Page 9: ...le 1 The transducer ships from the supplier with a four wire cable and a ground Only 2 wires and the ground will be used Install a fork connector to the black lead red lead and the ground The white an...

Page 10: ...r and Input on the actuator 3 Connect the second lead to Output 4U1 controller Input on the actuator Note If the water valve and actuator were not ordered the signal can also be used by a BAS system C...

Page 11: ...ucer 4R1 connected to condenser pressure and arrange so transducer 4R2 can be connected to either atmospheric or above 70 psi Apply 24 VAC to 4U1 and line power to valve Stroke valve open and closed b...

Page 12: ...fied licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed...

Page 13: ...re the voltage across S1 and S for the condenser transducer Measure across S2 and S for the evaporator transducer 3 Compare the voltage reading to the graph in figure 7 The converted pressure should b...

Page 14: ...ve actuator incorrect signal sent by 4U1 ASM module failure of one or both of the pressure transducers incorrect power supply loose connections Valve opening unstable noise on signal line potentiomete...

Page 15: ...00906 144 inches Conductor cable UNN00040 2 1 4 flare union internal BRK02884 1 Bracket NUT00148 4 10 32 nut SCR01557 4 10 32 x 1 screw Table 5 List of Water Regulating Valves one required Trane Part...

Page 16: ...re Order Number RTHC SVN02C EN File Number SL RF RLC RTHC SVN02C EN 0503 Supersedes RTHC SVN02B EN Stocking Location Inland Trane A business of American Standard Companies www trane com For more infor...

Reviews: