Trane RAUT 250 Installation Operation & Maintenance Download Page 9

RAUT-IOM-R410A

9

Installation

When hooking a vacuum pump to a refrigeration system,
it is important to connect the pump to both the high and
low side of the system.
Follow the pump manufacturer’s directions as to the
proper  methods  of   using  the  vacuum  pump  .
The lines used to connect the pump to the system should
be copper and of the largest diameter that can pratically
be  used.  Using  larger  line  sizes  with  minimum  flow
resistance  can  significantly  reduce  evacuation  time.
Rubber or synthetic hoses are not acceptable for unit
evacuation  because  they  have  moisture  absorbing
characteristics  which  result  in  excessive  rates  of
outgassing and pressure rise during standing vacuum
test. This makes it impossible to determine if the unit has
a leak.
An electronic thermopile vacuum gauge should be installed
in the common line ahead of the vacuum pump shutoff
valve as shown in Figure 2 . Close Valve B and open
Valve A. After several minutes, the gauge reading will
indicate the minimum blank-off  pressure the pump is
capable of pulling . Rotary pump should produce vacuum
of less than 100 microns.
Open Valve B and evacuate the system to a pressure of
500 microns  or less. Valve A must be closed when taking
this reading. Once 500 microns or less is obtained, with
Valve A closed, a time versus pressure rise should be
performed. The maximum allowable rise over a 15 minute
period is 200 microns. If  pressure rise is greater than
200 microns but levels off to a constant value, excessive
moisture is present. If the pressure steadily continues to
rise, a leak is indicated.

Figure 2
Vacuum pump connection.

Electrical Connections

Wiring diagrams are furnished with the units, but extra
copies may be obtained from the local Trane sales office.
The installing contractor is to provide and install fused
disconnect switches and the wiring up to the unit control
panel. Check all wiring connections and trace the circuits
to make sure that they agree with the wiring diagrams.

Caution :

1.  All  wiring  should  comply  with  local  and  national
      codes.  Type  and  location  of   disconnect  switches
    should comply with local and national codes. Install
    disconnect switch near unit, within sight, for safety.
2. Use copper conductors only for installation wiring.
    Unit terminals are not designed to accept other type
      of   wiring.  The  use  of   aluminium  wire  may  cause
    galvanic  corrosion  and/or  overheating  at  the
   connection points with resultant equipment failure.

Unit Start-Up

Preparation for start-up

Before starting the unit, use the following procedures
to ensure that the unit is completely and
properly installed and ready for start-up.
The installer must make sure that the following points
are checked before the initial start-up.
1. Inspect all wiring connections. Connections should
    be clean and tight. Trace circuits to ensure that wiring
    agrees with wiring diagrams provided with the unit.
    Information in the title block of the wiring diagram
    should match the data that appears on the unit
    nameplate.
2. Close the unit power fused disconnect switch and
    the manual disconnect switch.
3. Check the unit supply voltage to ensure that the
     voltage is within the utilization range.
4. Check the compressor oil level.
5. Check with a phase-meter the direction of rotation
    of scroll Trane compressors or check the good
    operation of the discharge and suction pressures.
6. As the various motors of the system are started,
    check the direction of rotation and make sure that
    the driven equipment is operating satisfactorily.
7. Ensure sufficient cooling load available at day of
    start-up (minimum of 50% of design load).

Preparation

Before putting the system into operation, perform these
service and check-out procedures :
1. Before making any electrical power connections make
    sure that the insulation resistance of all power terminal
    to earth is in accordance with the international electrical
    codes. Measure the insulation of all electrical motors
    using a 500 V DC tester and refer to the manufacturer’s
    specifications.

Warning :

No motor should be started if the insulation resistance

is less than 2 mega ohms. Under no circumstances
should any voltage be applied to a motor while it is
under vacuum.

2. Check the unit supply voltage to ensure that the voltage
    is within the utilization range.

Caution :

Phase unbalance must not exceed 2% . Supply for all
motors is to be within plus or minus 5% of the voltages
specified on the compressor nameplate.

3. Place all refrigerant circuit valves in operating position.
4. Reset all controls equipped with a manual reset function.

High side

Valve A

Vacuum
pump

Summary of Contents for RAUT 250

Page 1: ...n be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equi...

Page 2: ...No 11 Minor Major Design Sequence Comp Motor A Modular RAUT Design Digit No 12 Factory Installed 0 No Option A Corrosion Resistant Coated Fin Blue Fin B Hydrophobic Coating Fin C Copper Fin and Coppe...

Page 3: ...Contents Model Nomenclature System Precaution General Information General Data Installation Operation Maintenance Maintenance Compressor Trouble Analysis Dimensional Data Electrical Wiring 2 4 5 6 7 1...

Page 4: ...ing leakage of water etc Be sure to cut off the main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electri shock Any presence of foreign substan...

Page 5: ...mail Notify the local Trane Sales Office Concealed damage must be reported within 15 days delivery Check the unit nameplate to confirm that the proper unit was shipped Available power supply must be c...

Page 6: ...00 26 100 29 000 49 500 29 000 49 500 Vendor Motor Type 710W 710W 900W 1800W 1800W Qty 2 2 2 2 2 Speed RPM 920 920 920 720 720 V ph Hz 380 3 50 380 3 50 380 3 50 380 3 50 380 3 50 RLA LRA each A 3 22...

Page 7: ...le of handling the weight of the unit Table 1 Clearances Provide sufficient clearance around the unit for performance of service and maintenance Caution unit operation is a function of the air tempera...

Page 8: ...t and dry nitrogen for leak testing a violent explosion may result 3 Always use a pressure regulator valves and gauges to control drum and line pressures when pressure testing the system Excessive pre...

Page 9: ...ety 2 Use copper conductors only for installation wiring Unit terminals are not designed to accept other type of wiring The use of aluminium wire may cause galvanic corrosion and or overheating at the...

Page 10: ...er full load in the compressor oil level sight glass The unit was charged with the proper amount of oil before shipping Under normal operation compressor oil is always expected to return to compressor...

Page 11: ...e 3B EXPANSION VALVE CAPILLARY TUBES SIGHT GLASS STRAINER LIQUID LINE FROM RECEIVER EXPANSION VALVE SOLENOID LIQUID VALVE EXPANSION VALVE EXPANSION VALVE THERMAL BULBS EXPANSION VALVE EQUALIZER LINES...

Page 12: ...recommended procedures The following procedures should be carried out by a qualified service technician as part of a maintenance contract The first and last visit will include the seasonal shut down...

Page 13: ...ction filter is required install it a minimum of 18 upstream of the compressor manifold piping See Figure 4 Caution Altering the original manifold piping may cause oil compressor failure This sequence...

Page 14: ...line but not on motor side or fuse Voltmeter does not read proper voltage Motor starter holding coil is not energized Compressor will not operate Open contact on high pressure switch Discharge pressu...

Page 15: ...obable cause Insufficient oil charge Clogged filter drier Liquid flooding back to compressor Recommended action All oil Replace Readjust superheat setting and verify correct bulb mounting F Compressor...

Page 16: ...Expansion valve opens too far a Adjust superheat and check flood back to compressor bulb attachment b Expansion valve stuck in open b Repair or replace position L Discharge pressure too high Problems...

Page 17: ...00 1693 0 222 2 208 0 67 4 146 7 SUCTION CONNECTION 1 5 8 1786 0 LIQUID CONNECTION 5 8 99 5 1588 0 99 5 RECOMMANDED CLEARANCE 1070 821 0 RECOMMANDED CLEARANCE 1524 RECOMMANDED CLEARANCE 1524 RECOMMAND...

Page 18: ...273 0 273 0 2206 0 1156 0 2380 3 RECOMMANDED CLEARANCE 1070 RECOMMANDED CLEARANCE 1524 464 0 183 0 578 0 297 1 128 0 SUCTION CONNECTION SIZE 1 5 8 LIQUID CONNECTION SIZE 5 8 RECOMMANDED CLEARANCE 152...

Page 19: ...RAUT IOM R410A 19 Electrical Wiring RAUT250 400 Micro P 1 2...

Page 20: ...20 RAUT IOM R410A Electrical Wiring RAUT250 400 Micro P 2 2...

Page 21: ...RAUT IOM R410A 21 Electrical Wiring RAUT500 600 Micro P 1 2...

Page 22: ...22 RAUT IOM R410A Electrical Wiring RAUT500 600 Micro P 2 2...

Page 23: ...RAUT IOM R410A 23 Electrical Wiring RAUT250 400 with Carel pCO5 1 2...

Page 24: ...t 1 ID10 J7 2 Low Pressure Switch Circuit 2 ID11 J7 3 High Pressure Switch Circuit 2 ID12 J7 4 Compressor 1 Overload Circuit 2 IDC9 J7 5 Common DI 9 12 ID13h J8 1 Not used ID13 J8 2 Compressor 2 Overl...

Page 25: ...RAUT IOM R410A 25 Electrical Wiring RAUT500 600 with Carel pCO5 1 2...

Page 26: ...t 1 ID10 J7 2 Low Pressure Switch Circuit 2 ID11 J7 3 High Pressure Switch Circuit 2 ID12 J7 4 Compressor 1 Overload Circuit 2 IDC9 J7 5 Common DI 9 12 ID13h J8 1 Not used ID13 J8 2 Compressor 2 Overl...

Page 27: ...RAUT IOM R410A 27 Note...

Page 28: ...ations without notice We are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor env...

Reviews: