98
SS-SVX11K-EN
Figure 69.
W7100A discharge air controller
SETPOINT °F
RESET °F
CONTROL
BAND °F
Test Plug Socket
(Remove red dust cover)
ECONO
24 VAC
CHANGE
OVER
# STAGES
SENSOR
RESET
REMOTE
SETPOINT
SATELLITE
COOL
COOL
COOL
COOL
COOL
COOL
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
6
5
4
3
2
1
GND
TR
TR
W
R
B
Y
10
9
T
T1
8
7
6
P
P1
5
4
3
2
1
Discharge Air Sensor Checkout
(Honeywell Sensor)
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
1. Verify that the main power disconnect switch and
the control circuit switch 1S2, in the unit control
panel, is “OFF”.
2. At the Discharge Air Controller, in the unit control
panel, disconnect the wire connected to Terminal
T1. Use a digital ohmmeter to measure the
resistance across Terminal T and the wire removed
from Terminal T1.
3. Use the conversion chart in
to
convert the measured resistance to an equivalent
temperature.
4. Measure the actual temperature at the sensor
location. If the measured resistance in step 2 is not
within ± 10.0 ohms of the actual temperature, the
sensor is out of range; replace it.
N
No
otte
e:: Before condemning the sensor, verify that
the connecting cable resistance is not
excessive. Refer to the “Field Installed
Control Wiring” section.
5. Make all necessary repairs and reconnect the duct
sensor lead to terminal T1 on the controller.
6. Restore power to the system and turn all control
switches to the “ON” position.
Figure 70.
Discharge duct sensor 6RT2 & 6RT3 “temperature vs resistance” curve
3000
3200
3400
3600
3800
4000
4200
20
(-6.7)
40
(4.4)
60
(15.6)
80
(26.7)
100
(37.8)
120
(48.9)
140
(60.0)
160
(71.1)
180
(82.2)
200
(93.3)
220
(104.4)
R
e
s
is
ta
n
c
e
(O
h
m
s
)
Temperature °F (°C)
3483±10 ohms
77°F (25°C)
Economizer Actuator Checkout
((U
Usse
ed
d w
wiitth
h “
“Z
Zo
on
ne
e”
” o
orr “
“D
Diisscch
ha
arrg
ge
e A
Aiirr”
” T
Te
em
mp
p
C
Co
on
nttrro
olllle
err))
The following procedures should be used to verify that
the field provided economizer actuator(s) function
properly. These procedures are based on using a
typical Honeywell actuator. If another type actuator is