PART-SVN234B-EN
17
General Information
Table 2.
Torque values
Item
Torque
Rotolock equalizer nut
1-3/4 and 2-1/4
133 ± 10 N·m; 98 ± 7 ft·lb
Terminal screws #10-32 X 0.5 in
2.75 ± 0.25 N·m; 25 ± 2 in·lb
Terminal stud
2.75 ± 0.25 N·m; 30 ± 2 in·lb
Terminal stud nut
3.4 ± 0.25 N·m; 30 ± 2 in·lb
Ground screw
1.90 ± 0.25 N·m; 17 ± 2 in·lb
Terminal box cover
2.15 ± 0.25 N·m; 19 ± 2 in·lb
Note:
With Rotolock fittings, always use two wrenches:
one to back-up on the sleeve and one to tighten the
nut. Proper torquing of the Rotolock nut is
important to ensure a leak-free joint.
POE Oil
Table 3.
Factory oil charge
Nominal Capacity
Pints
Liters
Part Number
090
6.3
3.0
OIL00078, OIL00080
109–156
7.0
3.3
OIL00078, OIL00080
181
7.6
3.6
OIL00078, OIL00080
182–301
14.2
6.7
OIL00078, OIL00080
360–361
15.2
7.2
OIL00078, OIL00080
Notes:
1.
OIL00078—1 quart container
2.
OIL00080—1 gallon container
3.
Oil amount and type is also printed on the nameplate.
Oil Handling
POE oil is very hygroscopic, which means it absorbs
moisture very readily. Therefore, it is important to
properly handle the oil.
POE Oil handling guidelines
•
Always use the smallest container size required for the
job requirements.
•
Always leave the oil container tightly sealed until time
of use.
•
Do not reuse oil that has been opened.
Oil Level
Figure 10.
Compressor oil label
The oil should be visible through the oil sightglass both
during operation and when the compressor(s) is off. Oil
level slightly below the sightglass, but still visible is
acceptable.
Single compressor.
The oil level should be stable in the
sightglass.
Tandem and trio compressors.
•
Operation
—
The oil
level will vary depending on the operating condition.
•
Unloaded condition
—
The running compressor will
have a higher oil level than the off compressor(s).
•
Loaded condition
—
Oil should be visible through all
of the compressor sight glasses. Some may have a
higher level than others, but this is not abnormal.
•
Off
—
After several minutes, the oil levels should be the
same in each compressor and should be visible in the
sightglass. This is the best method to determine if the
system has sufficient oil.
Units overcharged with oil will operate with degraded
performance and could lead to compressor damage.
Operating Envelope
The compressor must be operated within the published
operating envelope.