PKGP-PRC004-EN
23
Performance
Data
Table PD-10 — Belt Drive Evaporator Fan Performance WSC060AD,T Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
1.12 Nom kW Standard Motor & Drive
2720
692
0.25
761
0.30
823
0.36
884
0.41
941
0.47
990
0.52
1034
0.58
1077
0.64
1119 0.70
1158 0.75
3060
761
0.35
825
0.40
882
0.46
937
0.52
992
0.58
1043
0.65
1088
0.71
1130
0.77
1169 0.83
1207 0.90
3400
831
0.46
891
0.52
945
0.58
995
0.65
1045
0.72
1094
0.79
1141
0.86
1185
0.93
1224 1.00
1260 1.07
3740
901
0.60
958
0.67
1009
0.73
1057
0.80
1101
0.88
1146
0.95
1192
1.03
1235
1.11
1277 1.18
1314 1.26
4080
972.8
0.76
1026
0.84
1075
0.91
1120
0.98
1163
1.06
1204
1.14
1245
1.23
—
—
—
—
—
—
1.12 Nom kW Standard Motor &
Hi Static Drive
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose
Motors, Specifically Designed And Tested To Operate Reliably And
Continuously At All Cataloged Conditions. Using The Full Horsepower
Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In
Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
External Static Pressure (Pascals)
275
300
325
350
375
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor
1.12 Nom kW Standard Motor &
& Drive
Hi Static Drive
2720
1196
0.82
1231
0.88
1265
0.94
1298
1.00
1330
1.07
3060
1244
0.96
1280
1.03
1314
1.10
1346
1.16
1380
1.24
3400
1295
1.14
1330
1.21
1363
1.28
—
—
—
—
3740
—
—
—
—
—
—
—
—
—
—
4080
—
—
—
—
—
—
—
—
—
—
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Table PD-10a — Belt Drive Evaporator Fan Performance WSC060AD,T Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor & Drive
1600
692
0.34
761
0.41
823
0.48
884
0.55
941
0.63
990
0.70
1034
0.78
1077
0.85
1119 0.93
1158 1.01
1800
761
0.47
825
0.54
882
0.62
937
0.70
992
0.78
1043
0.87
1088
0.95
1130
1.03
1169 1.12
1207 1.21
2000
831
0.62
891
0.70
945
0.78
995
0.87
1045
0.97
1094
1.06
1141
1.15
1185
1.25
1224 1.34
1260 1.43
2200
901
0.80
958
0.90
1009
0.98
1057
1.08
1101
1.18
1146
1.28
1192
1.38
1235
1.49
1277 1.59
1314 1.69
2400
972.8
1.02
1026
1.13
1075
1.22
1120
1.32
1163
1.42
1204
1.53
1245
1.65
—
—
—
—
—
—
1-1/2 HP Standard Motor & Drive
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Std Motor & Drive
1-1/2 HP Standard Motor & Hi Static Drive
1600
1196
1.09
1231
1.17
1265
1.26
1298
1.35
1330
1.44
1800
1244
1.29
1280
1.38
1314
1.47
1346
1.56
1380
1.66
2000
1295
1.52
1330
1.62
1363
1.72
—
—
—
—
2200
—
—
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
—
—
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
Factory Supplied Motors, In Commercial Equipment,
Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions.
Using The Full Horsepower Range Of Our Fan Motors As Shown In
Our Tabular Data Will Not Result In Nuisance Tripping Or Premature
Motor Failure. Our Product’s Warranty Will Not Be Affected.
1-1/2 HP Standard Motor & Hi Static Drive