background image

RT-SVX074A-EN

37

internal circuit breakers. If a circuit breaker trips, turn “Off”
all power to the unit before attempting to reset it.

WARNING

Hazardous Voltage!

Failure to disconnect power before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is
present with a voltmeter.

The transformers are located in the control panel. The
circuit breaker is located on the right side of the transformer
and can be reset by pressing in on the black reset button.

Controls using 24 VAC

Before installing any connecting wiring, refer to the
Dimensions and Weights chapter for the electrical access

locations provided on the unit and

Table 4, p. 39

for AC

conductor sizing guidelines, and;

1. Use copper conductors unless otherwise specified.

2. Ensure that the AC control wiring between the controls

and the unit’s termination point does not exceed 2.5
ohms/conductor for the length of the run

NOTICE

Component Failure!

Resistance in excess of two and a half (2.5) ohms per
conductor could result in component failure due to
insufficient AC voltage supply.
Do not exceed two and a half (2.5) ohms per
conductor for the length of the run.

Note:

Be sure to check all loads and conductors for

grounds, shorts, and mis-wiring.

3. Do not run the AC low voltage wiring in the same

conduit with the high voltage power wiring.

4. Route low voltage wiring per illustrations below.

Figure 46.

Low voltage wiring — B cabinet

Installation

Summary of Contents for Precedent THJ072

Page 1: ...installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags sticke...

Page 2: ...t is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the applic...

Page 3: ...than these policies those regulations supersede these policies Non Trane personnel should always follow local regulations Copyright This document and the information in it are the property of Trane a...

Page 4: ...nsor BAYSENS135 10 Touch Screen Programmable Zone Sensor BAYSENS800 11 Evaporator Frost Control 11 Discharge Line Temp Switch DLTS 11 Smoke Detector Sensor Optional 11 Phase Monitor 11 Pre Installatio...

Page 5: ...at 45 Final System Setup 45 Maintenance 47 Monthly Maintenance 47 Filters 47 Return Air Smoke Detector Maintenance 47 Condensate Overflow Switch 47 Cooling Season 47 Heating Season 47 Coil Cleaning 48...

Page 6: ...or 1 Optional Oversized High Static Motor 2 Single Zone Variable Air Volume with Standard Motor 3 Single Zone Variable Air Volume with Oversized High Static Motor 4 Multiple Zone Variable Air Volume w...

Page 7: ...7 Clogged Filter Switch Condensate Overflow Switch and Discharge Air Sensing Tube1 2 Digit 26 Not Used Digit 27 Hardware Enhancements 0 No Enhancements 1 Stainless Steel Drain Pan Digit 28 Short Circu...

Page 8: ...rage Take precautions to prevent condensate from forming inside the unit s electrical compartments and motors if The unit is stored before it is installed or The unit is set on the roof curb and tempo...

Page 9: ...lter switch has been closed for at least 2 minutes The system will continue to operate regardless of the status of the filter switch For further details refer to Installation Instructions ACC SVN238 E...

Page 10: ...ted Comfort building management system Integrated Comfort System BAYSENS074 This sensor features single setpoint capability and timed override with override cancellation It is used with a Trane Integr...

Page 11: ...e to follow these instructions will prevent the smoke detectors from performing its design function Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil...

Page 12: ...Precautionary Measures Avoid breathing fiberglass dust Use a NIOSH approved dust mist respirator Avoid contact with the skin or eyes Wear long sleeved loose fitting clothing gloves and eye protection...

Page 13: ...ORT ACCESS 1 3 8 35 MM DIA HOLE UNIT CONTROL WIRE 2 50 MM DIA HOLE EVAPORATOR SECTION ACCESS PANEL 15 1 4 388 27 5 8 700 88 1 8 2238 11 1 4 286 9 5 8 244 4 7 8 123 9 229 53 1 4 1352 50 7 8 1293 Figure...

Page 14: ...1 4 490 16 3 4 426 9 3 8 237 32 1 4 820 3 7 4 97 Figure 5 6 to 10 tons high efficiency unit clearance and roof opening CLEARANCE 36 914 MM CLEARANCE FROM TOP OF UNIT 72 TYPICAL ROOF OPENING CLEARANCE...

Page 15: ...6 3 8 1178 MM 34 3 8 873 MM 84 1 2 2146 MM 2 51 MM 34 3 8 873 MM 1 25 MM 49 7 8 1267 MM 50 3 8 1280 MM 2 51 MM 83 7 8 2130 MM 80 1 2 2045 MM 18 1 2 470 MM 1 25 MM 6 5 8 168 MM 18 1 4 470 MM 1 25 MM RE...

Page 16: ...E DRAIN CONNECTION 3 4 14 NPT DIA HOLE CONTROL BOX SECTION ACCESS PANEL UNIT POWER WIRE 1 3 8 35MM DIA HOLE 1 2 NPT CONNECTION 120 MBh 3 4 NPT GAS CONNECTION 150 MBh 200 MBh 250 MBh COMPRESSOR ACCESS...

Page 17: ...RICAL THROUGH THE BASE CONDENSATE 4 5 8 119 MM THROUGH THE BASE GAS 5 7 8 149 MM 27 5 8 701 MM 42 3 16 1072 MM 6 3 8 163 MM 2 3 4 71 MM 51 3 16 1316 MM 4 1 8 104 MM Figure 11 12 5 tons high efficiency...

Page 18: ...FROM TOP OF UNIT 72 63 3 16 1605 MM 46 1168 MM 46 1168 MM 99 11 16 2532 MM Figure 13 12 5 tons high efficiency roof curb 56 3 8 1432 MM 14 356 MM 1 3 4 44 MM 34 3 8 873 MM 18 1 2 470 MM 1 25 MM 6 5 8...

Page 19: ...1 279 35 890 21 3 4 554 Figure 15 6 to 12 5 tons high efficiency economizer manual or motorized fresh air damper DIMENSIONS EXTENDS TO 21 5 8 549MM WHEN POWERED EXHAUST IS COUPLED WITH LOW LEAK ECONOM...

Page 20: ...20 RT SVX074A EN Figure 16 6 to 12 5 tons high efficiency power exhaust ECONOMIZER HOOD 20 1 2 520 5 5 8 144 Dimensions and Weights...

Page 21: ...GAS CONNECTION 3 4 NPT 280 320 400 MBh EVAPORATOR SECTION ACCESS PANEL CONDENSATE DRAIN INDOOR TOP PANEL CONTROL BOX SECTION ACCESS PANEL UNIT CONTROL WIRE 2 50 MM DIA HOLE UNIT POWER WIRE 2 50 MM DI...

Page 22: ...8 3 8 212MM 48 1223MM 6 5 8 167 MM 55 0577 1398 467 55 2977 1404 563 8 205MM 55 3 8 1404MM THROUGH THE BASE ELECTRICAL THROUGH THE BASE GAS Y_J MODELS ONLY Figure 20 15 to 25 ton high efficiency hori...

Page 23: ...68 1727 MM 76 1 2 1943 MM 81 2057 MM ROOF OPENING CLEARANCE FORM TOP OF UNIT 72 MM 1829 MM Figure 22 15 to 25 tons high efficiency roof curb 117 3 16 2977 MM 7 1 2 191 MM 81 2057 MM 1 25 MM 1 25 MM 1...

Page 24: ...24 RT SVX074A EN Figure 23 15 to 25 ton high efficiency swing diameter for hinged door s option 32 809MM 30 754MM 36 907MM Dimensions and Weights...

Page 25: ...instead of base 2 Clearance is the same if any unit is rotated 180 degrees 4 0 1219 MM for D cabinet 5 0 1525 MM for D cabinet 5 8 for D cabinet 1727 MM Weights Table 1 Model weights corner weights lb...

Page 26: ...1 150 Low Leak Economizer Horizontal 180 Manual Outside Air Damper 26 26 15 Motorized Outside Air Damper 30 30 82 Oversized Motor 14 30 Powered Convenience Outlet 38 50 50 Powered Exhaust 80 80 110 Re...

Page 27: ...chains or slings may not be of the same length Adjust as necessary for even unit lift WARNING Improper Unit Lift Failure to properly lift unit in a LEVEL position could result in unit dropping and pos...

Page 28: ...s required anchor the unit to the slab using hold down bolts or isolators Isolators should be installed to minimize the transmission of vibrations into the building WARNING Risk of Roof Collapsing Fai...

Page 29: ...33 838 MM 4 1 8 104 MM 27 5 8 701 MM THROUGH THE BASE CONDENSATE 40 3 4 1035 MM THROUGH THE BASE ELECTRICAL 5 7 8 149 MM 5 127 MM 10 7 8 276 MM 3 3 4 95 MM 2 3 4 71 MM 6 1 2 165 MM Figure 32 12 5 ton...

Page 30: ...d catwalk around the unit is strongly recommended to provide easy access for unit maintenance and service Recommendations for installing the Supply Air and Return Air ductwork joining the roof curb ar...

Page 31: ...nd Weights chapter to protect the unit and to facilitate a uniform lift The minimum distance between the lifting hook and the top of the unit should be 7 feet 5 Test lift the unit to ensure it is prop...

Page 32: ...sion 3 ounce tube of high temperature RTV sealant 500 F 260 C similar to Dow Corning 736 Note Failure to use recommended sealant could result in unit performance loss If a unit is to be converted to a...

Page 33: ...flow duct opening Rotate the tube and bracket assembly 90 degrees ensuring that the holes on the aluminium sensing tube face away from the unit and face the return air ductwork Note Refer to horizonta...

Page 34: ...ect properly sized and protected power supply wiring to a field supplied installed disconnect switch and to the main power terminal block HTB1 in the unit control panel Install proper grounding wires...

Page 35: ...drain lines at least 1 2 inch for every 10 feet of horizontal run to assure proper condensate flow Do not allow the horizontal run to sag causing a possible double trap condition which could result i...

Page 36: ...ints The termination points depending on the customer option selected would be a factory mounted non fused disconnect switch UDC or circuit breaker UCB If neither a factory mounted non fused disconnec...

Page 37: ...cting wiring refer to the Dimensions and Weights chapter for the electrical access locations provided on the unit and Table 4 p 39 for AC conductor sizing guidelines and 1 Use copper conductors unless...

Page 38: ...38 RT SVX074A EN Figure 47 Low voltage wiring C cabinet Figure 48 Low voltage wiring D cabinet Installation...

Page 39: ...on the unit Table 5 p 39 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input output sign...

Page 40: ...of remote sensors is required Example 2 illustrates three sensors squared in a series parallel circuit Using BAYSENS077 two sensors are required to accomplish space temperature averaging Example 3 ill...

Page 41: ...56 5 15 0 74 65 10 12 2 63 80 15 9 4 54 66 20 6 7 46 94 25 3 8 40 40 30 1 1 34 85 35 1 7 30 18 40 4 4 26 22 Table 6 Temperature vs resistance continued Temperature Nominal Resistance kOhms Degrees F D...

Page 42: ...Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly Measure each leg phase to phase of the power supply Each reading must fall within the utiliz...

Page 43: ...Heaters Each compressor can be equipped with a crankcase heater On some units the crankcase heater comes standard The proper operation of the crankcase heater is important to maintain an elevated com...

Page 44: ...er will remain in any given state once initiated For detailed information on how each Service Test State is interpreted based on the equipment s configuration see ACC APG002 EN Symbio 700 for Preceden...

Page 45: ...ctromechanical test mode connections if applicable Hot Gas Reheat WARNING Live Electrical Components Failure to follow all electrical safety precautions when exposed to live electrical components coul...

Page 46: ...following tasks you MUST Follow all instructions in the unit s Installation Operation and Maintenance manual including warnings cautions and notices Perform all required tasks in any applicable Servi...

Page 47: ...ures refer to the appropriate section s of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit Condensate Overflow Switch During maintenance...

Page 48: ...oil Damage Failure to follow instructions below could result in coil damage DO NOT use any detergents with microchannel condenser coils Use pressurized water or air ONLY with pressure no greater than...

Page 49: ...RT SVX074A EN 49 3 For compressor replacements and or additional questions contact Technical Support Maintenance...

Page 50: ...ple maintenance log Date Current Ambient Temp F C Refrigerant Circuit 1 Refrigerant Circuit 2 Compr Oil Level Suct Press Psig kPa Disch Press Psig kPa Liquid Press Psig kPa Super heat F C Sub cool F C...

Page 51: ...RT SVX074A EN 51 Troubleshooting See ACC APG002 EN Application Guide Symbio 700 Controller with Precedent Packaged Rooftop Air Conditioners...

Page 52: ...12134343 SCHEMATIC SHEET 2 POWER SINGLE INDOOR FAN COOLING ONLY ELECTRIC HEAT HIGH SCCR Main Unit Symbio 700 230V 12134344 SCHEMATIC SHEET 2 POWER SINGLE INDOOR FAN 2 STAGE GAS HEAT 230V HIGH SCCR Ma...

Page 53: ...TIC SHEET 1 ELECTRIC HEAT 27 36 KW 240V Electric Heat Symbio 700 230V 12134303 SCHEMATIC SHEET 1 ELECTRIC HEAT 54 KW 240V Electric Heat Symbio 700 460V 575V 12134304 SCHEMATIC SHEET 1 ELECTRIC HEAT 9...

Page 54: ...OIL AIR SERVICE VALVE SUCTION LINE LIQUID LINE FITER DRIER TXV TXV BULB EQUALIZING LINE SERVICE VALVE AIR OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE COMPRESSOR 1A S D COMPRESSOR 1B DISCHARGE LIN...

Page 55: ...IL AIR SERVICE VALVE N O I T C U S LINE LIQUID LINE FILTER DRIER TXV TXV BULB EQUALIZING LINE SERVICE VALVE AIR OUTDOOR COIL LOW PRESSURE CONTROL COMPRESSOR 1A S D COMPRESSOR 1B DISCHARGE LINE THERMOS...

Page 56: ...UCTION LINE LIQUID LINE FITER DRIER TXV 1 EQUALIZING LINE SERVICE VALVE OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE DISCHARGE LINE THERMOSTAT HIGH PRESSURE CONTROL AIR AIR INDOOR COIL 1 INDOOR CO...

Page 57: ...EQUALIZING LINE SERVICE VALVE OUTDOOR COIL LOW PRESSURE CONTROL DISCHARGE LINE THERMOSTAT HIGH PRESSURE CONTROL AIR AIR INDOOR COIL 1 INDOOR COIL 2 TXV BULB 2 TXV BULB 1 TXV 2 EQUALIZING LINE DISCHAR...

Page 58: ...cts have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF...

Page 59: ...RT SVX074A EN 59 Notes...

Page 60: ...formation please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and spec...

Reviews: