Pre-Installation

This section provides the following pre-installation information:

Mounting location

Transformer considerations

Recommended configurations

Mounting Location

Important:

The power supply module must be mounted onto a DIN rail inside an enclosure that

meets all local electrical codes.

Observe the following:

The enclosure must allow for the minimum 1.8 in. (4.6 cm) vent clearance around the top and

bottom of the power supply vents.

The mounting location must meet the temperature and humidity specifications of the power

supply as outlined in

Table 3, p. 9

.

Do not mount the power supply module on a flat surface, such as on a floor or on top of a table.
Mount in an upright position with the front facing outward.

Transformer Considerations

Follow these guidelines when using transformers:

Transformers must be class 2 rated.

Non-class 2 transformers must be fused appropriately.

Fully loaded power supply modules require 75 VA transformers.

The transformer size can be reduced for smaller loads on the power supply module; however,

transformers less than 20 VA should not be used.

Table 3

shows the recommended transformer VA

based on the PM014 output current.

Table 3.

Transformer recommendations

PM014 output current

Less than or equal to 0.7 Adc

Greater than 0.7

Transformer VA (minimum)

40

75

Summary of Contents for PM014

Page 1: ...dge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the litera...

Page 2: ...de could result in death or serious injury WARNING Personal Protective Equipment PPE Required Installing servicing this unit could result in exposure to electrical mechanical and chemical hazards Befo...

Page 3: ...ication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks referenced in this document are the trademarks of th...

Page 4: ...Recommended Configuration 10 Installing the Power Supply Module 11 Repositioning or Removing the Power Supply Module 12 Power and Field Wiring 13 Installing Power Input Wire 13 Grounding the Power Su...

Page 5: ...dule and other equipment The PM014 uses a full wave rectifier It is designed to safely share power with a device that uses half wave rectification within the transformer limits The power supply module...

Page 6: ...es 24 24 VAC VAC XFMR XFMR OUT OUT 24 24 VAC VAC 2 4 in 6 14 cm 2 4 in 6 1 cm 1 8 in 4 5 cm 4 0 in 10 2 cm 2 4 in 6 1 cm 1 2 in 3 1 cm 0 6 in 1 5 cm 2 0 in 5 0 cm 2 0 in 5 0 cm PM014 24 VAC XFMR OUT 2...

Page 7: ...Codes and standards Listing Description UL C UL IEC60950 1 UL recognized under Information Technology Equipment Safety Part 1 General Requirements UL916 Open listing CE Conformity The European Union...

Page 8: ...PM014 Specifications Enclosure IP20 NEMA 1 DIN rail DIN 50022 35 mm x 7 5 mm Environmental Parameters Storage temperature 67 F 55 C minimum 203 F 95 C maximum Operating temperature 40 F 40 C minimum...

Page 9: ...as outlined in Table 3 p 9 Do not mount the power supply module on a flat surface such as on a floor or on top of a table Mount in an upright position with the front facing outward Transformer Conside...

Page 10: ...ustrated in Figure 2 Place DIN rail end stops at each end of the configuration to prevent shifting of modules Figure 2 Correct horizontal mounting PM014 24 VAC XFMR OUT 24 VAC DIN rail end stop DIN ra...

Page 11: ...rm the lockout tagout procedures for line voltage power to the electrical cabinet 2 Do not use excessive force Excessive force could cause equipment damage 3 Hook the power supply module DIN rail groo...

Page 12: ...ver to disengage the clip Do not use excessive force Excessive force could cause equipment damage 3 While holding tension on the DIN rail latch lift the module upward to remove or reposition 4 If repo...

Page 13: ...verify that the wire cannot be easily pulled out by lightly tugging on each wire For reference the screw terminals should be tightened to 0 5 to 0 6 N m 71 85 Ozf in 4 4 5 3 Lbf in Table 4 Recommende...

Page 14: ...onnection if daisy chaining unit control modules to the power supply module The current drawn through this connection should not exceed 3 Aac Figure 6 Grounding the Power Supply Module 24 VAC 24 VAC O...

Page 15: ...wer supplies Recommended method for separating the IMC bus Note This method preserves the power supply module warranty 3 Perform lockout tagout procedures for line voltage power to the cabinet 4 Using...

Page 16: ...start up the power supply module 1 Ensure that input voltage is 24 Vac 2 Remove the lockout tagout from line voltage power to the electrical cabinet 3 Apply power Note Initially the power supply modul...

Page 17: ...recommendations reveal no problems you may need to replace the power supply module Remove the power supply as instructed in Repositioning or Removing the Power Supply Module p 12 Table 6 Status LED A...

Page 18: ...ge across the 24 Vdc output termination Compare to expected value based on request from PM014 specification see Table 2 p 8 Figure 10 PM014 24 Vac Output AC measurement VAC ADC VDC IMC IMC IMC 24 DC I...