8
CHS-SVN011C-EN
General Information
Model Number . . . . . . . . . . . . . . . . . . . . . . . PCC-1L-3210-4-7.5
Ambient Operating Conditions . . . . . . . . . . . . -20°F to 100°F
1
Airside Data
Discharge Air Configuration . . . . . . . . . . . . . . . . . . . . Horizontal
Flex Duct Connection Qty & Size . . . .(1) 36 in. round
2
(F0)
units (4) 20 in. round (F1) units
Nominal Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . 12,100
3
Discharge Static Pressure
@ Nominal Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5 in. ESP
Maximum Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . 24,500
Discharge Static Pressure
@ Maximum Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 in. ESP
Electrical Data
Supply Motor Size . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 hp/11 A
Heater Circuit . . . . . . . . . . . . . . . . . . . . . . . . . 37,730 W/47.35 A
Supply Motor Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . 1160 rpm
Fused Disconnect/Circuit Breaker . . . . . . . . . . . . . . . . . . . . . Yes
Number of Electrical Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Voltage 460V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-phase
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Hz
Minimum Circuit Ampacity (MCA) . . . . . . . . . . . . . . . . . .. 61 A
Maximum Over current Protection (MOP) . . . . . . . .. . . . . 80 A
For additional electrical information contact Trane Rental
Services.
Waterside Data
Water Connection Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 in.
Water Connection Type . . . . . . . . . . . . . . . . . . . . . . . . . . Grooved
Drain Pipe Size . . . . . . . . . . . . . . . . . . . . . . . . . 2.0 in. (F0 Units)
3/4 in. (F1 Units)
Drain Pipe Connection Type . . . . . Female Pipe Thread (F0
Units) Garden Hose (F1 Units)
NOTICE
Water Damage!
Connecting all drains to a common line with only one
trap could result in condensate retention and possible
water damage to the air handler or adjoining space.
When more than one module has a drain pain, trap
each module individually.
Table 1.
Coil Capacity
Coil Type
Entering/Leaving
Water Temp (°F)
Water Flow
(gpm)
Pressure Drop
(ft of H²O)
Entering/Leaving
Air Temp (°F)
Coil Capacity
(BTUH)
Chilled Water
0/3.4
70
16.17
14/6.8
105,077
0/3.9
90
17.39
16/9.7
158,567
0/3.1
120
27.9
16/9.4
166,583
Selection based on 50% propylene glycol/water solution.
Selection is required for actual AHU performance.
Contact Trane Rental Services for specific selection
information.
Maximum waterside pressure is 150 psi (2.31’ H
2
O = 1 psi)
1
For ambient conditions below 40°F, glycol is recommended.
2
With Long Throw Adapter
3
Actual airflow is dependent upon external static pressure requirement. Con-
tact Trane Rental Services for specific airflow and static pressure information.
Subject to change at any time without notice or liability.