Trane OXBOX JMM4A0A18S21SAA Installer'S Manual Download Page 7

Section 4. Wiring 

White 

AC  SYSTEMS 

W1 

B/C 

Brown

24 V AC HO T 

FA N 

24 V AC 

Common 

COOLING 

HEA T 

Thermostat 

Air Handler  Outdoor 

Unit 

3.11 Sequence of Operation 

Cooling (cooling only)

When  the  thermostat  calls  for  cooling,  the  circuit  from  R  to  G  is 
completed.  The  blower  motor  is  energized  directly  by  the  24VAC 
signal from the thermostat.

The circuit from R to Y is also completed, energizing the compressor 
contactor of the outdoor unit. The contactor will close and start the 
compressor and condenser fan motor.

Heating (electric heat only)

Note: The thermostat must be setup to bring the blower on when the 
electric heat is energized.

When  the  thermostat  calls  for  heating,  the  circuit  from  R  to  G  is 
completed and the blower motor is energized directly by the 24VAC 
signal  from  the  thermostat.  The  circuit  from  R  to  W  is  completed 
energizing the heating contactor(s).

3.12 Operational And Checkout Procedures

To obtain proper performance, all units must be operated and charge 
adjustments  made  in  accordance  with  procedures  found  in  the 
Service Facts document of the outdoor unit.

After  installation  has  been  completed,  it  is  recommended  that  the 
entire system be checked against the following list:
[  ] 1. Be sure unit suspension (if used) is secure and there are 
no tools or loose debris in, around or on top of the unit.
[  ] 2. Properly insulate suction lines and fittings.
[  ] 3. Properly secure and isolate all refrigerant lines.
[  ] 4. Verify that all electrical connections are tight.
[  ] 5. Check all duct outlets; they must be open and unrestricted.
[  ] 6. Check drain lines and be sure all joints are tight.
[  ] 7. Be sure the return air filter is installed.
[  ]  8.  Operate  complete  system  in  each  mode  to  verify  proper 
performance. Verify operation of supplementary electric heater.

7

3.13 Maintenance

The  system  air  filter(s)  should  be  inspected,  cleaned  or  replaced  at 
least monthly. Make certain that the access panels are replaced and 
secured  properly  before  placing  the  unit  back  in  operation.  This 
product  is  designed  for  dependable  service;  however,  periodic 
maintenance  should  be  scheduled  and  conducted  by  trained 
professional  service  personnel.  This  service  should  be  conducted  at 
least annually, and should include testing and inspection of electrical 
and  refrigerant  components.  The  heat  transfer  surface  should  be 
cleaned.  The  blower  motor  is  permanently  lubricated  for  normal 
operating conditions.

Table 1 Superheat Charging Chart

Outdoor 

Temp(oF)

Indoor Temperature(oF) Dry Bulb/Wet Bulb

95/79 

90/75 

85/71 

80/67 

75/63 

70/58 

Superheat (°F) 

115 

23 

16 

110 

24 

17 

105 

26 

19 

11 

100 

27 

21 

13 

95 

29 

23 

16 

90 

30 

25 

18 

12 

85 

32 

26 

20 

16 

80 

34 

28 

22 

17 

11 

75 

35 

30 

24 

19 

13 

70 

37 

32 

26 

21 

16 

10 

65 

38 

34 

29 

24 

19 

13 

60 

40 

36 

31 

27 

22 

17 

55 

41 

37 

33 

29 

25 

21 

Note: Chart is based on 400 CFM/Ton indoor airflow and 50% 
relative humidity. If indoor relative humidity is above 70% or 
below 20%. use indoor wet bulb temperature only. Airflow range 
is 375 to 425 CFM/Ton.

This air handler comes with a factory-installed piston metering 
device. A TXV may be required to achieve minimum efficiency 
ratings or for long refrigerant line set applications. Reference AHRI 
for system combination ratings.
Charge the system by superheat when using a piston. Reference the 
outdoor unit installation guide to charge the system by subcooling 
when using a TXV.

Summary of Contents for OXBOX JMM4A0A18S21SAA

Page 1: ...single phase 5 7 5 and 10 kW heaters All aluminum coil Factory installed piston style refrigerant control Field installed TXV kits available Blower and coil slide out easily for maintenance Factory sealed cabinet certified to achieve 2 or less air leakage rate at 1 0 inch water column Front or bottom return air Painted finish on galvanized steel Sturdy polycarbonate drain pans Air handler has fact...

Page 2: ... state electrical code on requirements for grounding Failure to follow this warning could result in property damage serious personal injury or death HAZARDOUS VAPORS Do not install an air handler with a non ducted return in the same closet alcove or utility room as a fossil fuel device Hazardous vapors can be distributed throughout the conditioned space and equipment damage can result Section 2 Sa...

Page 3: ...ins adhesives cleaning compounds and cement creates a corrosive condition which may cause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servicing Personal injury may result WARNING Make sure the blower motor support is tight 3 motor mount bolts then check ...

Page 4: ...mounting bracket and attach the unit to the installed bracket Reference Figure 3 1 4 Install the additional bottom plate for extra support for this type mounting see figure 3 1 Note The additional plate is shipped in the bottom of the shipping carton only for 30 36k unit 3 2 1 WALL MOUNT Fig 3 2 FRAME MOUNT The air handler comes with 8 clearance holes 4 on each side These holes are used to mount t...

Page 5: ...idential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Washington D C 20036 If duct system incorporates flexible air duct be sure pressure drop information straight length plus all turns shown in ACCA Manual D is accounted for in system Supply plenum is attached to the 3 4 duct flanges...

Page 6: ...HP or AC single stage heating cooling with electric heat The thermostat will energize the fan on a demand for heating or cooling Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other rooms being controlled by the thermostat The thermostat should be mounted 4 to 5 feet above the floor Low voltage control w...

Page 7: ...oints are tight 7 Be sure the return air filter is installed 8 Operate complete system in each mode to verify proper performance Verify operation of supplementary electric heater 7 3 13 Maintenance The system air filter s should be inspected cleaned or replaced at least monthly Make certain that the access panels are replaced and secured properly before placing the unit back in operation This prod...

Page 8: ...ctric heaters 8 N E C class2 24volts Factory default fan speed is medium FM red wire connected to FR 4 For HI speed connect FM black wire to FR 4 For LOW speed connect FM blue wire to FR 4 and FM red wire to FR 6 Always connect the unused FM wire to the dummy terminal CN3 connect the plug to electric heaters kit when applied FM T A T S O M R E H T O T PLUG PLATE SEE NOTE 4 SCHEMATIC DIAGRAM COMPON...

Page 9: ... 1290 1263 1196 1116 1051 980 907 Med 1298 1252 1198 1147 1094 1037 976 910 842 Low 1149 1105 1056 1008 960 909 856 791 726 36 EXTERNAL STATIC PRESSURE in w c 24 30 MODEL JMM4A BLOW ER SPEEDS 18 Shaded boxes represent airflow outside the required 300 450 cfm ton NOTES 1 Airflow based upon dry coil at 230V with no electric heat and factory approved filter 2 Airflow is equivalent for front or bottom...

Page 10: ...applications section for more detail Primary drain conncetion 3 4 female pipe thread NPT Auxiliary drain connection 3 4 female pipe thread NPT NOTE Hand tighten only Section 7 Dimensional Data DIMENSIONAL DATA 18 88 101 40 46 MODEL SIZE Dimensions inch mm UNIT HEIGHT H IN mm UNIT WIDTH W IN mm UNIT LENGTH D IN mm 88 101 40 46 24 UNIT WIDTH W1 IN mm UNIT WEIGHT SHIPPING WEIGHT LBS kg UNIT LENGTH D1...

Page 11: ...MENSIONS A B C JMM4A0A18S21SAA 24 9 10 150 10 1 8 61 119 1 20 717 JMM4A0A24S21SAA 24 9 10 150 10 1 8 61 119 1 20 717 JMM4A0B30S21SAA 24 9 10 150 10 1 8 61 132 795 JMM4A0B36S31SAA 24 9 10 150 10 1 8 61 132 795 Model number Dimension inch mm ...

Page 12: ...our local dealer distributor Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change the design and specification without notice 16123000A19244 V2 0 www oxboxhvac com 2019TwentyThreeC LLC 800 Beaty Street ...

Reviews: