Inspect unit location for proper free air clearances.
☐
Inspect unit location for secure, level mounting
position.
☐
Verify condenser fans turn freely without rubbing
and are properly tightened on the shafts.
Refrigerant Piping
☐
Properly sized/constructed liquid and suction lines
connected to stubs at both the indoor and outdoor
units?
☐
Insulated the entire suction line?
☐
Insulated portions of liquid line exposed to
extremes in temperature?
☐
Performed initial leak test?
☐
Evacuated each refrigerant circuit to 500 microns?
☐
Charged each circuit with proper amount of R-410A/
R-22?
Electrical Wiring
☐
Provided unit power wiring (with disconnect) to
proper terminals in the unit control enclosure?
☐
Installed system indoor thermostat or zone sensor?
☐
Installed system low voltage interconnecting wiring
to proper terminals of outdoor unit, indoor unit and
system thermostat or zone sensor?
☐
Checked all electrical connections to verify all are
properly tightened and connected?
☐
Verified operation of crankcase heaters?