Trane MCC 518 AB Installation Manual Download Page 7

MCC-SVN01A-EN

7

Leak Check and System Evacuation

Leak Check

After the connection operation of
refrigerant lines to both the outdoor
and indoor unit is completed, the field
brazed connections must be checked
for leaks. Pressurize the system
through the service valve with dry
nitrogen to 250 psi. Use soap
bubbles or other leak-checking
methods to ensure that all field joints
are leak free. If not, release pressure,
repair and repeat leak test.

System Evacuation

1. After completion of leak check,

evacuate the system.

2. Attach appropriate hoses from

manifold gauge to gas and liquid
line pressure taps.

Note:

 Unnecessary switching of

hoses can be avoided and
complete evacuation of all lines
leading to sealed system can be
accomplished with manifold
center hose and connecting
branch hose to a cylinder of
R-22 and vacuum pump.

3. Attach center hose of manifold

gauges to vacuum pump.

4. Evacuate the system to hold a

350 micron vacuum.

5. Close off valve to vacuum pump

and observe the micron gauge.
If gauge pressure rised above
500 microns in one (1) minute,
then evacuation is incomplete or
the system has a leak.

6. If vacuum gauge does not rise

above 500 microns in one (1)
minute, the evacuation should
be complete.

7. With vacuum pump and micron

gauge blanked off, open valve on
R-22 cylinder and allow refrigerant
pressure to build up to about 40
psig.

8. Close valve on the R-22 supply

cylinder. Close valves on manifold
gauge set and remove refrigerant
charging hoses from liquid and
gas gauge ports.

9. Leak test the entire system. Using

proper procedures and caution,
repair any leaks found and repeat
the leak test.

Refrigerant Charging Procedure

Charge refrigerant through the gauge
port on the liquid line until pressure at
gauge is up to 120-150 psi. Once the
charge enters the system, backseat
(open) the liquid line service valve and
disconnect the charging line and
replace the cap on the gauge port.

Gaseous Charging

This procedure is accomplished
with the unit operating. Electrical
connections must be complete.
Do not proceed until the system is
ready to operate.

Procedure

1. Connect R-22 drum with gauge

manifold to the Schrader valves
(pressure taps) on the compressor
discharge and suction lines.

2. Turn on power to the unit. Allow

the system to run for five to ten
minutes to stabilize operating
conditions.

3. Once proper airflow is established,

observe the suction and head
pressure gauges on the gauge
manifold. Pressure reading should
fall approximately at the normal
points. Add or remove refrigerant
(gas only) as required to obtain
correct head and suction pressures.
Check suction line superheat and
condenser sub-cooling to ensure
the unit is operating properly.

4. Disconnect all power to the unit.
5. Remove the charging system from

the unit and close the opening in
the bottom of the control box with
the pivotal cover before attempting
to replace access panel.

Liquid pressure

Suction pressure

Vacuum pump

R-22

Service hose

Liquid line

Suction

line

Electrical connection

Figure 16

Summary of Contents for MCC 518 AB

Page 1: ...MCC SVN01A EN Models Cooling Only MCC 518 AB MCC 524 AB MCC 530 AB MCC 536 AB February 2000 Installation Manual Split System 1 5 Tons 18 000 38 000 Btu Underceiling Type MCC Series 50 Hz CASSETTE...

Page 2: ...n 7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warning Warnings are provided at appropria...

Page 3: ...ormation 2 Indoor Unit Installation 4 Outdoor Unit Installation 5 Connection of Refrigerant Tubing and Condensate Drain Piping 6 Leak Check and System Evacuation 7 Electrical Installation 8 Wiring Dia...

Page 4: ...re 1 also ensure that the position dose not interfere with light fitting sprinkle head etc Determine the ceiling hole by using the paper pattern Determine the mounting position on ceiling by using pos...

Page 5: ...r do not disturb the users or their neighbors Easy access to check and to maintain Ensure the spaces indicated by arrows from the wall ceiling fence or other obstacles Caution Installation in the foll...

Page 6: ...to prevent dust or water from getting into the tubes before they are used 8 Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together This...

Page 7: ...valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas gauge ports 9 Leak test the entire system Using proper procedures and caution repair any leaks found and repeat...

Page 8: ...trical Connections See Section Wiring System Diagram Bare the ends of electric wire After retaining the wire check that all the terminal screws are firmly tightened Indoor Unit Remove the right side p...

Page 9: ...MCC SVN01A EN 9 220 240 1 50 Hz MCC518 536AB Wiring Diagram...

Page 10: ...bove suspension brackets 180 mm 180 mm 230 mm 230 mm C Height of condensate drain above ceiling 230 mm 230 mm 280 mm 280 mm D Pipe exit position 165 mm 165 mm 215 mm 215 mm 950 390 340 512 330 370 350...

Page 11: ...MCC SVN01A EN 11 Notes...

Page 12: ...reserves the right to change design and specifications without notice Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey Bangkok 10110 http www trane com An American Standar...

Reviews: