Installation Manual

ILLUSION

Split System Concealed Type

MCD Series 50/60 Hz

General Information

Introduction  

This Installation Manual is given as a guide to good practice in the installation by the installer of MCD mini-split system. 

Installation procedures should be performed in the sequence that they appear in this manual.  

For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the 

services of a qualified service technician should be employed, through the maintenance contract with a reputable service 

company.  

Read these installation instructions completely before installing the air conditioning system.  

About the Unit  

These MCD units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information 

contained in this manual applies to MCD units are designed to operate in cooling mode only and in cooling or heating modes.  

Important  

This document is customer property and is to remain with unit. Please place in service information pack upon completion 

of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be 

met in connection with installation. 

Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, 

the matter should be referred to your authorized Trane dealer.

Caution  

Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of 

potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit. 

MS-SVN004-EN

Reception

On arrival, inspect the unit before signing the delivery note. 

Specify any damage of the unit on the delivery note, and 

send a registered letter of protest to the last carrier of the 

goods within 72 hours of delivery. Notify the dealer at the 

same time.  

The unit should be totally inspected within 7 days of 

delivery. If any concealed damage is discovered, send a 

registered letter of protest to the carrier within 7 days of 

delivery and notify the dealer. 

About this Manual  

Cautions appear at appropriate places in this Installation 

Manual. Your personal safety and the proper operation of 

this machine require that you follow them carefully. 

The Trane Company assumes no liability for installations or 

servicing performed by unqualified personnel. All phases of 

the installation of this air conditioning system must conform 

to all national, provincial, state and local codes.  

Warranty  

Warranty is based on the general terms and conditions 

by country. The warranty is void if the equipment is 

modified or repaired without the written approval of The 

Trane Company, if the operating limits are exceeded or if 

the control system or the electrical wiring is modified.  

Damage due to inappropriate installation, lack of 

knowledge or failure to comply with the manufacturer’s 

instructions, is not covered by the warranty obligation. If 

the installation does not conform to the rules described in 

Installation Manual, it may entail cancellation of warranty 

and liabilities by The Trane Company. 

Warning  

Warnings are provided at appropriate places in this 

manual to indicate to installers, operators and service 

personnel of potentially hazardous situations which, if not 

avoided, COULD result in death or serious injury.

Children should be supervised to ensure that they do not 

play with the appliance. 

The appliance is not to be used by persons (including 

children) with reduced physical, sensory or mental 

capabilities, or lack of experience and knowledge, unless 

they been given supervision or instruction.

System Appearance

MCD 512-536 DB/D1

MCD 009-024 AA5

Outlet Collar

Motor

Blower

Evaporator Coil

Electric Heater

(Option)

Condensate Drain Pan

Return Air Plenum

(Standard)

B

B

Outlet Collar

Motor

Blower

Condensate Drain Pan

Electric Heater

(Option)

Evaporator Coil

A

A

Note 

A

 Hanger recommendation for without return plenum model

Note 

B

 Hanger recommendation for return plenum model

Units Installation

Figure 4 (TOP VIEW)

Figure 3 (SIDE VIEW)

Figure 5

Figure 6

Table 1

A

B

C

D

E

F

G

H

I

J

K

DISTANCE

(MM.)

Min. 750 Min. 800

100

150

50

200

Min. 200 Min. 100 Min. 50 Min. 300 Min. 300

NOTE: FOR DUCT LENGTH PLEASE SEE TABLE 2, 3, 4

A good flare should have the following characteristics:    

• Inside surface is glossy and smooth.    

• Edge is smooth.    

• Tapered sides are of uniform length.   

Cautions Before Connecting Tightly  

1. Be sure to apply a sealing cap or water-proof tape to prevent 

dust or water from getting into the tubes before they are used.  

2. Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. 

This is effective for reducing gas leaks (Figure 11).  

3. For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at 

first to obtain a smooth match (Figure 12). 

4. Tighten the flare nuts, using the appropriate wrench. 

Connecting the Unit with Brazing Prodecure  

1. Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 20-30 cm. longer than the tube 

length. 

2. Remove burrs at the end of the copper tube with a tube reamer (Figure 8).  

3. There are 2 ways to connect the copper tube 

- Use a coupling between the copper tube of Fan Coil Unit and the copper tube used for installation (Figure 13).

- Expand the copper tube by using a swaging tool set as in Figure 14. 

4. To braze the copper tube, before brazing a copper tube to a solder coupling or a copper tube to an expanded tube, do 

not forget to keep them tight as shown in Figure 15.  

5. While welding copper tube. You should to Nitrogen flow in tube for protect soot occured.

Figure 12

Figure 11

Location and Preparation of Units 

Indoor Unit  

1. Select a convenient location that allows the air to reach every corner of the room and where it is easy to route the 

refrigerant tubing, wiring and drain to the outside.  

2. The ceiling construction should be strong enough to support the weight of the unit.  

3. The refrigerant tubing, drain piping and wiring conduit are connected through the wall.  

4. Refrigerant tubes between the indoor and the outdoor units and drain pipes should be as short as possible.  

5. If a refrigerant charge adjustment is necessary, follow the Installation Manual for the Outdoor Unit.  

Outdoor Unit  

See instructions for location and preparation of the unit in the Installation Manual for the Outdoor Unit.  

Installation Method: 

Indoor Unit  

After selecting the location to place the unit, follow these steps:  

1. Make a hole in the wall to route tubing and wiring through a locally 

purchased PVC pipe. 

  The hole should slope downwards slightly, towards the outside 

(Figure 1).   

2. Before cutting, check that no pipes or studs are directly behind the place 

to be cut. 

Avoid areas where electrical wiring or conduits are located.  

3. Hang the unit on a solid and level roof. Noise, vibration or leakage could 

occur on and unstable foundation (Figure 3, 4). For correct installation of 

duct work see (Figure 6).  

4. Support the unit solidly.  

5. To have access to electrical terminals, remove the right side junction box (Figure 2).  

6. Note that refrigerant tubing, interconnecting wiring and drain hose should go through the wall. 

Shape these items so that they will easily fit through the wall.    

Outdoor Unit  

See the proper installation method provided in the Installation Manual for the Outdoor Unit. 

Figure 2

Figure 1

Connection of Refrigerant Tubing

Proper installation procedure is recommended in the Installation Manual Package, usually provided together with the 

outdoor unit. It is advisable to read before installing.  

The indoor unit refrigerant connections are located on the left hand side when facing the 

unit (Figure 7).   

Connecting the Units with Flaring Procedure  

1. Cut the copper tube to the required length with a tube cutter. 

  It is recommended to cut approx. 20-30 cm. longer than the tubing length.  

2. Remove burrs at the end of the copper tube with a tube reamer or file, as shown in 

Figure 8.    

When reaming, hold the tube end downward and be sure that no copper scraps fall into the 

tube (Figure 9).  

Figure 7

Figure 8

Figure 9

Figure 10

3. Remove the flare nut from the unit and be sure to insert on the copper tube.  

4. Make a flare at the end of the copper tube with a flare tool (Figure 10).

Flare Specification

Copper diameter, In.(mm.)

H, (mm.)

D, (mm.)

1/4" (6.35)

1.0 - 2.0

8.6 - 9.7

3/8" (9.53)

1.0 - 3.0

12.4 - 13.9

1/2" (12.70)

1.0 - 2.0

15.7 - 16.1

5/8" (15.88)

1.0 - 3.0

19.0 - 20.3

3/4" (19.05)

1.0 - 3.0

22.4 - 22.7

H

D

Figure 17

Model Series 5

Cooling Only 

(50 Hz)

MCD 009 AA5

MCD 012 AA5

MCD 018 AA5

MCD 024 AA5

MCD 030 EB5

MCD 036 EB5

MCD 042 EB5

MCD 048-060 DB/D1

MCD 030-042 EB5

MCDA 18-A36 DB/D1

MCDB42-B60 DB/D1