TROUBLESHOOTING PROCEDURE 

• Make sure furnace blower is operating and thermostat is calling for heat.

• Make sure the Outdoor Temperature Sensor is connected to the “ODT” terminals of the control. (For Manual Operation, 

make sure Manual Mode Resistor Case is in place.)

• Check wiring diagram for correct

Humidifier Control installation.

• Check voltage at Humidifier Control “R”

and “C” terminals. Voltage should be 
22 VAC minimum – 30 VAC maximum.

• Check Current Sensing Relay (if used)

for correct installation (see Current
Sensing Relay Installer’s Guide. The
Guide ships with the relay or may be
obtained from your local distributor).
Do not use Current Sensing Relay in
transformer circuit or “R” and “C”
circuit of Humidifier Control. Current
Sensing Relay is to be used in the “H”
circuit only.

• In “Test” mode, humidifier will

operate for 1 minute only. DO NOT
LEAVE IN TEST MODE AS
HUMIDIFIER WILL NOT OPERATE

• Make sure saddle valve is open.

Humidifier Control Troubleshooting Guide

Applies to both Automatic and Manual Operation unless indicated otherwise.

SYMPTOM

Humidifier does
not operate in
“Test” mode

System Checkout

1. For system Test/Reset, be sure that 24 VAC is applied to the “R” and “C” terminals 

of Humidifier Control.

2. Snap the door back onto the Humidifier Control Base.
3. Activate furnace blower and be sure thermostat is calling for heat.
4. Rotate the control knob of Humidifier Control clockwise to the “Test/Reset” position.

When the knob is set in the “Test/Reset” position, the green “Change Humidifier Pad”
light will blink. Make sure the knob is not left in the “Test/Reset” position when the 
installation is done. Rotating knob to test position resets the humidifier pad change timer
to zero. The Control must be energized to reset the Humidifier Pad Indicator.

5. If all is set up properly, you should be able to hear the solenoid valve click open. 

In “Test/Reset” mode, the Humidifier will operate for 1 minute.

6. If the humidifier does not activate with the

Humidifier Control in the “Test/Reset” position,
refer to troubleshooting guide.

7. Setting the Humidifier Control:

• If home is occupied, set Humidifier Control to

“Normal” (For Manual Operation, set to 35%)

• If home is vacant, set Humidifier Control to “Off”

8. Inform homeowner to refer to the Owner’s Manual

for the initial adjustment period.

9. Make sure the Red Diagnostic Light is not lit. If the

Red Diagnostic Light is lit, re-check your wiring. 

HUMIDIFIER CONTROL TEMPLATE

Sharp edges on the opening may cause cuts. Use care when cutting the plenum opening and installing
the Humidifier Control.

• Do not mount Humidifier Control on supply plenum or duct. The Control will not withstand supply 

temperatures and will malfunction!

• When installing Humidifier Control on counterflow furnaces, ensure blower continues to run after a

heat call is satisfied to eliminate high temperatures from damaging the Humidifier Control. 

• Do not mount Humidifier Control downstream of the bypass outlet. The Control will not operate correctly

due to false humidity readings.

1. CUT OUT TEMPLATE ALONG EDGES.

2. PLACE TEMPLATE ON THE RETURN PLENUM UPSTREAM OF (BEFORE) THE HUMIDIFIER CONNECTION.

3. TRACE OUTSIDE EDGES OF TEMPLATE.

4. REMOVE TEMPLATE AND ACCURATELY CUT PLENUM OPENING.

5. USING 4 SHEET METAL SCREWS, INSTALL HUMIDIFIER CONTROL IN PLENUM OPENING.

AUTOMATIC CONTROL

WIRING TERMINALS

PO

WER

BYP

ASS

SWITCH POSITION

R

C

H

ODT

24V

24 VAC

OUTDOOR
TEMPERATURE
SENSOR

FAN POWERED
HUMIDIFIER

FURNACE

LOW VOLTAGE

TERMINALS

(2 VA MINIMUM)

B / C

W1

HUMIDIFIER CORD
PLUGGED INTO
120 VAC POWER SOURCE

AUTOMATIC CONTROL

WIRING TERMINALS

R

C

H

ODT

24V

OUTDOOR
TEMPERATURE
SENSOR

FAN POWERED
HUMIDIFIER

HUMIDIFIER CORD
PLUGGED INTO
120 VAC POWER SOURCE

24 VAC

120 VAC

TRANSFORMER

(NOT SUPPLIED)

120 VAC

“HUM” OR “EAC”

TERMINALS

ON FURNACE

PO

WER 

BYP

ASS 

SWITCH POSITION 

AUTOMATIC CONTROL 

WIRING TERMINALS 

R C 

H ODT 

24V 

24 VAC 

120 VAC 

TRANSFORMER 

(FURNISHED) 

FURNACE 

ACCESSORY 
TERMINALS 

“HUM”   “HUM” 

H              N 

120 VAC 

“HUM” OR “EAC” 

TERMINALS 

ON FURNACE 

24 VAC 

120 VAC 

TRANSFORMER 

(FURNISHED) 

AUTOMATIC CONTROL 

WIRING TERMINALS 

R C 

H ODT 

24V 

BYPASS
HUMIDIFIER

BYPASS
HUMIDIFIER

OUTDOOR 
TEMPERATURE 
SENSOR 

OUTDOOR 
TEMPERATURE 
SENSOR 

Diagram A

FOR HUMIDIFIER
OPERATION DURING
“HEAT CALL” ONLY

Diagram B

FOR HUMIDIFIER
OPERATION WHEN
BLOWER IS ENERGIZED

Diagram C

FOR HUMIDIFIER
OPERATION DURING
“HEAT CALL” ONLY

Diagram D

FOR HUMIDIFIER
OPERATION WHEN
BLOWER IS ENERGIZED

FAN POWERED HUMIDIFIER WIRING DIAGRAM

BYPASS HUMIDIFIER WIRING DIAGRAM

90-1048

90-1125

CAUTION

WARNING